HEAT SOURCE 2 SPEED/LEVEL — When the Aquazone™
system control panel is configured for modulating heat source,
this point displays the percent open or percent heat capacity
requested. When the Aquazone system control panel is
equipped for staged output, this point displays the percent of
stages commanded. The actual number of stages active will be
determined by the staging cards ordered with the Aquazone
system control panel. See Table 8. The value displayed is
determined by a PID loop set to control the supply water
temperature at the Occupied Low set point.

Heat Source 2 Speed/Level

Display Units

%

Default Value

0

Display range 

0 100

Network Access Read/Write

SYSTEM FOR ZONE 1-18 — These Outputs are is used to
enable a group of thermostats by energizing and deenergizing
the associated zone relays. 

System for Zone 1-18

Display Units 

Discrete ASCII

Default Value

Off

Display Range

On/Off

Network Access Read/Write

Software Points — 

The software points are shown in

Table 14.

Table 14 — Software Points 65 to 96 (SWP65-96)

OUTSIDE AIR TEMPERATURE — This  software  point  is
included to receive an Outside Air Broadcast. If the system
is set up with Outside Air Broadcast, a control force will
be displayed on the OAT point of all system controllers.
For systems with factory-installed PremierLink™ controllers,
the individual unit leaving water temperature sensors are
connected to the OAT point. When OAT broadcast is enabled,
the leaving water temperature sensors connected to the
PremierLink controllers may be displayed temporarily by
removing the Outside Air Broadcast force. The Outside Air
Broadcast will be refreshed the next time the outside-air
temperature is broadcast. 

Outside Air Temperature:

Display Units

degrees F (degrees C)

Default Value

–40.0

Display Range

–40.0-245.0

Network Access Read/Write

LEAD PUMP CONSTANT FLOW — When  the  Aquazone
system control panel is configured for constant flow, this point
displays the current lead pump. This point may be forced to
keep the lead pump the same for more than the maximum
hours difference required for pump rotation. When the pump
runtime hours difference becomes greater than the maximum
number configured the pump runtime hours for both pumps
will reset to zero.

For example, the default maximum hours difference for

rotation is 50 hours. If the Lead Pump was forced to 2, so that
pump 2 is the lead pump, then the pump 2 runtime hours will
accumulate until the difference between the pump 1 and pump
2 runtime hours becomes greater than 50. The both will reset to
zero and pump 2 will start accumulating again.

Lead Pump Constant Flow:

Display Units 

Numeric

Default Value

1

Display Range

1 or 2

Network Access Read/Write

VARIABLE SPEED PUMPING — If  the  Aquazone  system
control panel is configured for variable speed pumping, this
point will indicate when the pumps are requested to be running.

Variable Speed Pumping:

Display Units 

Discrete ASCII

Default Value

Disable

Display Range

Enable/Disable

Network Access Read/Write

COOLING TOWER 1 — This point indicates when the first
cooling output is requested to control loop temperature.

Cooling Tower 1

Display Units 

Discrete ASCII

Default Value

Disable

Display Range

Enable/Disable

Network Access Read/Write

COOLING TOWER 2 — This point indicates when the sec-
ond cooling output is requested to control loop temperature.

Cooling Tower 2

Display Units 

Discrete ASCII

Default Value

Disable

Display Range

Enable/Disable

Network Access Read/Write

HEAT CONTROL 1 — This point indicates when the first
heat output is requested to control loop temperature.

Heat Control 1

Display Units 

Discrete ASCII

Default Value

Disable

Display Range

Enable/Disable

Network Access Read/Write

HEAT CONTROL 2 — This point indicates when the second
heat output is requested to control loop temperature.

Heat Control 2

Display Units 

Discrete ASCII

Default Value

Disable

Display Range

Enable/Disable

Network Access Read/Write

PUMP 1 RUN TIME — This  point  displays  the  number  of
hours that the pump has run. When the maximum number of
hours is exceeded (9999 hours), both pumps run time hours
will reset to 0.

Pump 1 Run Time

Display Units 

Numeric

Default Value

0

Display Range

0 to 9999

Network Access

Read/Write

DESCRIPTION

VALUE

NAME

Outside Air Temperature

94.94 dF

OAT

Lead Pump Const. Flow

1.00

LEAD

Variable Speed Pumping

Disable

VSPC

Cooling Tower 1

Disable

COOLT1

Cooling Tower 2

Disable

COOLT2

Heat Control 1

Enable

HEATC1

Heat Control 2

Disable

HEATC2

Pump 1 Run Time

253.00 HOURS

PUMP1RT

Pump 2 Run Time

250.00 HOURS

PUMP2RT

Содержание AQUAZONE 50RLP

Страница 1: ...e personnel When working on air conditioning equip ment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Improper installation adjustment alteration service main tenance or use can cause explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qualified installer service ag...

Страница 2: ...nd control all modes of cooling heating operation transmit unit number zone temperature zone temperature set points discharge air temperature fan status stages of heating stages of cooling leaving water temperature and alarm status information See Fig 3 COMPONENTS Aquazone System Control Panel Hardware The 50RLP Aquazone System Control Panel package consists of the following hardware See Fig 4 ENC...

Страница 3: ...es and digit 7 to specify heat addition stages See Fig 1 If variable speed cooling tower fan operation and or modulating valve operation for steam or water are utilized no output transducer card is specified The output transducer is a solid state multi stage device used for staging control from a single analog signal Output transducers are located in the upper left hand corner of the Aquazone Syst...

Страница 4: ...MFORT CONTROLLER REPEATER INTERFACE PC TO NETWORK TELINK WITH MODEM CONTROLLER DATA COLLECTION LOADSHED COMFORT CONTROLLER TENANT BILLING S S ROOM SENSOR TOWER BOILER PUMPS LT L E LIGHTS EQUIPMENT LOCAL COMPUTER REMOTE COMPUTER TELEPHONE LINE BLDG SYST MANAGEMENT PC ACCESS VENTILATION FAN MAIN STANDBY LOOP TEMP STAGE 1 STAGE 2 SPRAY PUMP FAN S ZONE 2 ZONE 1 Fig 3 CCN Water Source Heat Pump System ...

Страница 5: ...COMMON SIGNAL INPUT CHAIN OUTPUT INPUT TYPE UCS 421 MODE FLT SEQ MODE FLT SEQ A B C D MA V CH H3 H4 H5 A B C D 24V POWER COMMON SIGNAL INPUT CHAIN OUTPUT INPUT TYPE UCS 421 MODE FLT SEQ MODE FLT SEQ A B C D MA V CH H3 H4 H5 A B C D 24V POWER COMMON SIGNAL INPUT CHAIN OUTPUT INPUT TYPE UCS 421 MODE FLT SEQ MODE FLT SEQ A B C D MA V CH H3 H4 H5 A B C D 24V POWER COMMON SIGNAL INPUT CHAIN OUTPUT POWE...

Страница 6: ...ng the circuit breaker Control transformers are located on the bottom half of the system control panel Specifications for the control transformers are as follows Primary 120 208 240 vac Secondary 24 vac Frequency 60 Hz MOUNTING RAILS AND WIRING DUCT All exposed panel wiring is low voltage Line voltage wiring to the control transformers control circuits for pumps cooling tower fans and boilers is f...

Страница 7: ... When solenoid valves open the system pressure drops which results in the variable frequency drive speeding up to allow the pump to provide more water When solenoid valves close the system pressure rises which results in the variable frequency drive slowing down to allow the pump to provide less water WATER FLOW SWITCH A factory provided water flow switch is included with the Aquazone system contr...

Страница 8: ...ATURE SENSOR A factory installed leaving water temperature sensor is provided with PremierLink controller Wiring of the temperature sensor is shown in Fig 7 The sensor is a 10 kohm thermistor is protect ed by a stainless steel housing probe Probe is 1 4 inch in diam eter and 1 5 in long Wire is 22 AWG 7 30 copper wire PVC white 2 conductor type Field Supplied Hardware for Stand Alone Sys tems To u...

Страница 9: ...otection NEVERLOST memory 3 security levels 50QE900 220LA Aquazone Light Activated 7 Day Programmable 2 stages heating 2 stages cooling auto changeover 4 settings per day 24 vac Keypad lockout 5 minute compressor protection Occupied with lights on unoccupied with lights off NEVERLOST memory 3 security levels 50QE900 NPWS Aquazone Non programmable 2 stages heating 2 stages cooling auto changeover 5...

Страница 10: ...t SDP Remote Occupied Mode 24 vdc Input RMTOCC System Shut Down 24 vdc Input ALLSYS Override Input for Zones 1 2 24 vdc Input OVRIZ1 OVRIZ2 Pump Number 1 2 Speeds 4 20 mA Output PUMP1 PUMP2 Cooling Tower 1 2 Speed Level 4 20 mA Output CTL1 CTL2 Heat Source 1 2 Speed Level 4 20 mA Output BLRL1 BLRL2 System Enable for Zone 1 2 24 vdc Output SYSZ1 SYSZ2 First Optional I O Module Override Input for Zo...

Страница 11: ...electrical codes Connect the dedicated ground wire to the position in relationship to the main supply line and use shield cable to protect from any electrical interference CONTROL WIRING Low voltage wiring for the Aqua zone system control panel is shown in Fig 8 Table 3 PremierLink Controller Inputs and Outputs LEGEND INPUTS POWER TERMINAL S SPACE TEMPERATURE SPT AI 10 K Thermistor J6 7 J6 6 SET P...

Страница 12: ... 24 VAC Common Signal Input Chan Output 24 VAC Common Signal Input Chan Output SYSZ1 PUMP1 RED OFF AUTO SW ON 7 8 BRN 7 8 SYSZ5 7 8 SYSZ4 BRN 7 8 SYSZ3 BRN SYSZ6 7 8 BRN 7 8 SYSZ9 7 8 SYSZ8 BRN 7 8 SYSZ7 BRN 7 8 BRN BRN BRN RED 1 2 RMTOCC 3 4 ALLSYS 5 6 OVRZ1 7 8 OVRZ2 1 2 OVRZ3 3 4 OVRZ4 5 6 OVRZ5 7 8 OVRZ6 1 2 OVRZ7 3 4 OVRZ8 5 6 OVRZ9 7 8 OVRZ10 4 5 4 5 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18...

Страница 13: ...switch Two wires should be run to the switch for 24 VAC power The switch is supplied with wire leads for connection to the FLOW terminal When power is supplied to the device a warm up period is initiated During this period the right green LED will be lit Each LED to the left is successively lit until the farthest left red LED is lit Each LED will be turned off when the next is lit The warm up peri...

Страница 14: ...his LED indicates input output communications for accessory input output modules and the LID display The first six red LEDs on the controller will light The yellow LED will flash when the controller is broadcast ing CCN messages to a laptop or other computer The LID display will show the controller identification time and date as shown below Aquazone System hh mm mm dd yy Log On to the LID Display...

Страница 15: ...ding setting the clock 3 Press The LID display will show Time 00 00 4 Enter the time The time is entered in military time for example 14 59 for 2 59 pm Press the button The LID display will show Day of Week 1 5 Enter the day of week The numbers 1 through 7 corre spond to the days of the week 1 MON 2 TUE 3 WED 4 THUR 5 FRI 6 SAT 7 SUN Press The LID display will show Month 1 6 Enter the number of th...

Страница 16: ...e Loop Low Water Temperature set point 5 Press The LID display will show Occupied Hi Setpoint 90 00 This set point is the Loop High Water Temperature set point The down or up arrow will also display the Unoccupied Low and High Temperature set points These values should be kept the same as the occupied values 6 The system pressure set point SETPT02 is used for controlling variable speed pumps This ...

Страница 17: ...lays the Aquazone System Control Panel Controller items in the Status maintenance mode The user may view the current value or status of an item in the Status mode without actually logging on to the Aquazone System Control Panel Controller Knowing the current values or status of items can be useful when troubleshooting For example the user could determine if a point was forced NOTE Not all items ha...

Страница 18: ...ways to access items in the Edit mode are the same as in the Status mode except for an additional step pressing the key The user can access configuration data in the Edit mode in two ways Pressing the appropriate function key i e once to access a category i e alarms pressing and then continuing to press that key to scroll through all the items in that category i e Limit Alarm Setpoint Alarm Discre...

Страница 19: ...t N A N A N A N A N A 13 AO Static Pressure Voltage Output N A N A N A N A N A 14 DO Analog Custom Voltage Output N A N A N A N A N A 15 DO DX Staging VAV Discrete Output N A N A N A N A N A 16 DO Electric Heat CV Stepper Motor Output N A N A N A N A N A 17 DO Electric Heat VAV Discrete Software Point N A N A N A N A N A 18 DO Enthalpy Comparison Analog Software Point N A N A N A N A N A 19 DO Int...

Страница 20: ...es When the lead output is at 100 and the set point is not being maintained the lag output modulates to produce staging from another two or four stage output transducer The value output by each analog output is determined by a PID calculation of leaving water temperature versus the system low leaving water temperature set point In the event that the system low water temperature set point cannot be...

Страница 21: ... is used to measure the pressure of the supply water to the system of water source heat pumps This sensor should be located 2 3 of the way down the supply water distribution piping or in a location that will provide a good reference of the supply water pressure This sensor is used to control the speed of variable frequency drives pumping water to the water source heat pumps Each water source heat ...

Страница 22: ...tput is controlling the temperature the first will be held at 100 When the second output ramps down to zero percent the first output will resume temperature control Table 13 Total Number of Stages COOLING TOWER 1 SPEED LEVEL When the Aqua zone system control panel is configured for variable speed cooling tower control this point displays the speed of tower fan 1 When the Aquazone system control pa...

Страница 23: ...onfigured the pump runtime hours for both pumps will reset to zero For example the default maximum hours difference for rotation is 50 hours If the Lead Pump was forced to 2 so that pump 2 is the lead pump then the pump 2 runtime hours will accumulate until the difference between the pump 1 and pump 2 runtime hours becomes greater than 50 The both will reset to zero and pump 2 will start accumulat...

Страница 24: ...o 9999 9 Default Value 10 0 Global Dictionary The Global Dictionary table is shown in Table 17 Table 17 Global Dictionary AQUAMASC PUMP CONTROL TYPE This configuration determines how the pump outputs will be controlled If the pump relays were ordered with the Aquazone system control panel then the pump control type should be set to 0 If the pump outputs will control variable speed pumps then the c...

Страница 25: ...ed the schedules 1 through 18 in the Aquazone system control panel may be reconfigured to be schedules 65 through 82 so that they may be used as global schedules If this is done this configuration must be set to 1 Local inputs for overriding zones 1 to 18 or the remote occupancy input will then affect the global schedules 65 through 82 In this condition local override of individual PremierLink con...

Страница 26: ...PANCY SCHEDULE For flexibility of scheduling the occupancy programming is broken into eight separate peri ods For each period the schedule contains the following fields Day of Week Occupied From and Occupied To DAY OF WEEK The Day of Week configuration consists of eight fields corresponding to the seven days of the week and a holiday field in the following order Monday Tuesday Wednesday Thursday F...

Страница 27: ... during a holiday There are 16 different holiday schedules that can be created Holiday schedules can also last more than one day as long as the days are consecutive Holiday schedules must be configured on the time and date broadcaster element on the CCN If the Comfort Controller on the Aquazone system control panel is the broadcaster it will send holiday status to all other system elements on the ...