Table 32 — WSHP Troubleshooting (cont)
LEGEND
FAULT
HEATING
COOLING
POSSIBLE CAUSE
SOLUTION
Over/Under Voltage —
Code 7 (Auto Resetting)
X
X
Under voltage
Check power supply and 24 vac voltage before and during operation.
Check power supply wire size.
Check compressor starting.
Check 24 vac and unit transformer tap for correct power supply voltage.
X
X
Over voltage
Check power supply voltage and 24 vac before and during operation.
Check 24 vac and unit transformer tap for correct power supply voltage.
Performance Monitor —
Code 8
X
Heating mode FP2>125
F
Check for poor airflow or overcharged unit.
X
Cooling mode FP1>125
F OR
FP2<40
F
Check for poor water flow or airflow.
FP1 and FP2 Thermistors
— Code 9
X
FP1 temperature is higher
than FP2 temperature.
Swap FP1 and FP2 thermistors.
X
FP2 temperature is higher
than FP1 temperature.
Swap FP1 and FP2 thermistors.
No Fault Code Shown
X
X
No compressor operation
See Scroll Compressor Rotation section.
X
X
Compressor overload
Check and replace if necessary.
X
X
Control board
Reset power and check operation.
Swapped Thermistor —
Code 9
X
X
FP1 and FP2 swapped
Reverse position of thermistors.
Unit Short Cycles
X
X
Dirty air filter
Check and clean air filter.
X
X
Unit in 'Test Mode'
Reset power or wait 20 minutes for auto exit.
X
X
Unit selection
Unit may be oversized for space. Check sizing for actual load of space.
X
X
Compressor overload
Check and replace if necessary.
Only Fan Runs
X
X
Thermostat position
Ensure thermostat set for heating or cooling operation.
X
X
Unit locked out
Check for lockout codes. Reset power.
X
X
Compressor overload
Check compressor overload. Replace if necessary.
X
X
Thermostat wiring
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in Test mode.
Only Compressor Runs
X
X
Thermostat wiring
Check G wiring at heat pump. Jumper G and R for fan operation.
Check Y and W wiring at heat pump. Jumper Y and R for compressor
operation in test mode.
X
X
Fan motor relay
Jumper G and R for fan operation. Check for line voltage across BR
contacts.
Check fan power enable relay operation (if present).
X
X
Fan motor
Check for line voltage at motor. Check capacitor.
Unit Does Not Operate in
Cooling
X
Reversing valve
Set for cooling demand and check 24 vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating, engage and disengage RV coil voltage to push valve.
X
Thermostat setup
Check for 'O' RV setup not 'B'.
X
Thermostat wiring
Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.
Insufficient Capacity/
Not Cooling or Heating
Properly
X
X
Dirty filter
Replace or clean.
X
Reduced or no airflow in heating
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
Reduced or no airflow in cooling
Check for dirty air filter and clean or replace.
Check fan motor operation and airflow restrictions.
External static too high. Check blower performance per Tables 9-13.
X
X
Leaky ductwork
Check supply and return air temperatures at the unit and at distant duct
registers if significantly different, duct leaks are present.
X
X
Low refrigerant charge
Check superheat and subcooling per Tables 20-23.
X
X
Restricted metering device
Check superheat and subcooling per Tables 20-23. Replace.
X
Defective reversing valve
Set for cooling demand and check 24 vac on RV coil and at control.
If RV is stuck, run high pressure up by reducing water flow and while
operating, engage and disengage RV coil voltage to push valve.
X
X
Thermostat improperly located
Check location and for air drafts behind thermostat.
X
X
Unit undersized
Recheck loads and sizing check sensible cooling load and heat pump
capacity.
X
X
Scaling in water heat exchanger
Perform condenser cleaning.
X
X
Inlet water too hot or cold
Check load, loop sizing, loop backfill, ground moisture.