38
LEGEND
Table 28 — 50PC070 Typical Unit Operating Pressures and Temperatures
ENTERING
WATER
TEMP (°F)
WATER
FLOW
(GPM/TON)
COOLING
HEATING
Suction
Pressure
(PSIG)
Discharge
Pressure
(PSIG)
Water
Temp
Rise (°F)
Air Temp
Drop
(°F) DB
Suction
Pressure
(PSIG)
Discharge
Pressure
(PSIG)
Water
Temp.
Rise (°F)
Air Temp.
Drop (°F)
30
12
—
—
—
—
68-84
256-313
5-7
19-23
16
—
—
—
—
73-89
261-319
4-5
20-25
40
12
117-143
182-222
11-14
21-26
81-99
277-339
7-8
22-26
16
114-139
170-208
15-18
22-27
86-105
283-346
5-6
23-28
50
12
120-147
215-263
14-17
20-25
93-114
299-365
8-9
24-29
16
117-143
201-246
11-13
21-26
99-121
305-373
6-7
25-31
60
12
123-150
248-304
14-17
20-24
106-129
321-392
9-11
26-32
16
119-146
232-284
10-13
21-25
113-138
327-400
7-8
28-34
70
12
126-154
282-344
14-17
19-24
118-145
342-418
10-12
29-35
16
122-149
263-322
10-13
20-25
126-154
349-427
8-9
30-37
80
12
129-157
315-385
13-16
19-23
131-160
364-444
11-14
31-38
16
125-153
294-360
10-12
19-24
139-170
371-454
8-10
33-40
90
12
132-161
348-426
13-16
18-22
143-175
385-471
12-15
33-41
16
128-156
326-398
10-12
19-23
152-186
393-480
9-11
35-43
100
12
134-164
382-466
12-15
17-21
—
—
—
—
16
131-160
357-436
9-11
18-22
—
—
—
—
DB
—
Dry Bulb
—
—
No Operation in This Temperature Range