background image

29

The 30MPA units that use air-cooled or evaporative con-

densers must have adequate means for head pressure control

when operating below 65°F (18.3°C) ambient.

The 30MPA remote condenser requirements are as follows: 

• If multiple units are connected to a single condenser,

ensure each refrigerant circuit has its own head pressure

control

• Condenser must provide 15°F (8.3°C) subcooling, maxi-

mum of 40°F (22.2°C) difference between saturated

condensing temperature and outdoor ambient tempera-

ture (to prevent overload at high ambient temperatures),

and a minimum of 20°F (11.1°C) difference (to ensure

subcooling).

• Do not manifold multiple refrigerant circuits into a

single condenser.

• If air-cooled condenser is located below chiller, refer to

condenser manufacturer’s performance data for avail-

able liquid lift.

• Refer to condenser installation instructions for location

guidelines.

Carrier recommends that a field-supplied pressure relief de-

vice be installed in each discharge line of 30MPA units. Most

local codes require the discharge line relief valve to be vented

directly to the outdoors. The vent 

must not

 be smaller than the

discharge line relief valve outlet.

The 30MPA units are shipped with a discharge line loop to

facilitate factory testing. Relieve the pressure caused by the ni-

trogen holding charge. Cut the discharge line loop as close as

possible to the elbow. This will leave approximately 2-in.

(50 mm) of straight tubing for liquid line connection. Uncap

the discharge line. Be sure to connect the discharge line to the

larger line. Do not leave the reducing coupling in place.
30MPW  UNITS  WITH  NITROGEN  CHARGE — For

30MPW units with the factory nitrogen charge option, re-

lieve the pressure caused by the nitrogen holding charge

and proceed to the Evacuation and Dehydration section.

It is best practice to minimize the amount of time the sys-

tem is exposed to ambient air.
EVACUATION AND DEHYDRATION — Because the

30MP compressor oil can absorb moisture, it is important to

minimize the amount of time that the system interior is

exposed to the atmosphere. Minimizing the exposure time of

the oil to the atmosphere will minimize the amount of moisture

that needs to be removed during evacuation. 

Once all of the piping connections are complete, leak test

the unit and then pull a deep dehydration vacuum. Connect the

vacuum pump to the charging valve in the suction line and to

the liquid line service valve. For best results, it is recommended

that a vacuum of at least 500 microns (0.5 mm Hg) be

obtained. 

Afterwards, to ensure that no moisture is present in the sys-

tem, perform a standing vacuum-rise test. With the unit in deep

vacuum (500 microns or less), isolate the vacuum pump from

the system. Observe the rate-of-rise of the vacuum in the sys-

tem. If the vacuum rises by more than 50 microns in a 30-min-

ute time period, continue the dehydration process. Maintain a

vacuum on the system until the standing vacuum requirement

is met. This will ensure a dry system.

By following these evacuation and dehydration procedures,

the amount of moisture present in the system will be

minimized.   
30MPW CONDENSER DESCRIPTION  — All  30MPW

units use a brazed-plate heat-exchanger-type condenser.

These heat exchangers are made of embossed plates of

acid-resistant stainless steel. Every other plate is reversed

so that the ridges of the herringbone pattern intersect one

another on adjacent plates, forming a lattice of contact

points. These plates are vacuum-brazed together to form a

compact and pressure-resistant heat exchanger.

After brazing, the impressions in the plates form 2 separate

systems of channels where the refrigerant and water flows are

counterflow. The number of plates varies depending on unit

capacity. The condensers provide approximately 10° to 12°F

(6° to 8°C) liquid subcooling at the standard Air-Conditioning,

Heating and Refrigeration Institute (AHRI) rating condition.
30MPW CONDENSER  — When  facing  the  unit  control

box, the condenser is the uninsulated heat exchanger located on

the left-hand side. The water connections are on the right-hand

side of the heat exchanger with the LIQUID-IN connection at

the bottom, and the LIQUID-OUT connection at the top. For

30MPW units with water manifold option, refer to manifold

Victaulic spacer fitting kit accessory installation instructions.

A strainer with a minimum of 40 mesh must be installed

within 10 ft (3 m) of the chiller closest to the water header

inlet to prevent debris from clogging or damaging the

chiller’s heat exchangers. 

To install the Victaulic coupling (see Fig. 29):

1. Use Victaulic couplings designed for use on IPS dimen-

sioned materials; for example, Style 75, Style 77, Quick

Vic Style 107, or Style 177.

2. Lubricate the gasket lips and stretch the gasket over the

end of the heat exchanger coupling. Avoid twisting the

gasket when installing.

3. Bring the pipe and heat exchanger coupling ends together

into alignment. Slide the gasket so that it is centered over

the ends. Apply a light film of lubricant to the gasket, or

to the outside diameter of the pipe. Avoid twisting the

gasket during installation.

4. Install the inside coupling half over the gasket and then

install the outer half. Connect with nuts and bolts. Tighten

the nuts equally on both sides. Ensure there is no gap be-

tween the two halves of the coupling.

Fig. 2

8

 — Double Discharge Riser   

Construction Detail

a30-1245

TO
CONDENSER

B

RED.
TEE

90 DEGREE
STR ELLS

FROM
CHILLER

45 DEGREE
STR ELLS

A

LEGEND

RED. TEE

Reducing Tee

STR ELLS —

Street El

b

ows

a30-1979ef

1118

Содержание AquaSnap 30MPA050

Страница 1: ...controls The 30MPA units are condenserless units and the 30MPW units are fluid cooled See Fig 1 4 for dif ferent unit configurations See Fig 5 for model number no menclature and Fig 6 19 for unit dim...

Страница 2: ...2 Fig 1 30MPA Unit Size 020 045 a30 6023 Fig 2 30MPA Unit Size 050 071 a30 6024 Fig 3 30MPW Unit Size 016 045 a30 6025 Fig 4 30MPW Unit Size 050 071 a30 6026...

Страница 3: ...Interrupt High Condensing and Hot Gas Bypass 071 71 250 2 Fused Disconnect Switch selected models 0 Comfort Cooling Duty 32 60 F 0 0 16 5 C Std 1 Water Manifold Piping Includes Combination Valve 2 Wa...

Страница 4: ...to the nearest beams Additional weight of factory installed sound enclosure op tion is 75 lb 34 kg Additional operating weight of 30MPA water manifold option is 218 lb 99 kg Additional operating weigh...

Страница 5: ...37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown i...

Страница 6: ...59 9 mm 27 39 695 7 mm 37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Страница 7: ...h local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing coupling is required Consult Installation Instructions for...

Страница 8: ...34 42 874 2 mm 30MPA071 1724 782 kg 14 52 368 8 mm 29 96 760 9 mm 35 01 889 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions in are in mi...

Страница 9: ...equired Consult Installation Instructions for dis charge and liquid pipe connection sizes UNIT OPERATING WEIGHT lb DIMENSIONS in NUMBER OF COMPRESSORS STANDARD UNIT A B C D E F G H J 30MPW016 671 305...

Страница 10: ...and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing...

Страница 11: ...12 58 319 5 27 76 705 1 mm 35 27 895 5 mm 30MPW071 1719 780 kg 12 79 324 9 27 67 702 9 mm 35 02 889 5 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Страница 12: ...mm 3 30MPW045 1734 788 kg 12 69 332 mm 29 47 748 mm 32 19 818 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensi...

Страница 13: ...ntrol panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding...

Страница 14: ...13 26 336 8 mm 27 63 701 8 mm 31 36 796 5 mm 30MPW071 2155 977 5 kg 13 42 340 8 mm 27 55 699 8 mm 31 17 791 7 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of...

Страница 15: ...CLARITY STYLE B 11 38 in TYPICAL SEE DETAIL A 64 78 in TOP VIEW FRONT VIEW SIDE VIEW 57 00 in UNIT SIZES 016 045 65 05 in UNIT SIZES 050 071 68 81 in a30 6003 NOTE Style B water manifold is used on 30...

Страница 16: ...70 63 in TOP VIEW FRONT VIEW SIDE VIEW SEE DETAIL A 6 VICTAULIC CONNECTIONS SPACER PIPE ACCESSORY DETAIL A CORNER POSTS REMOVED FOR CLARITY a30 6004 STYLE B 11 38 in TYPICAL NOTE Style B water manifol...

Страница 17: ...3 Minimum Step Capacity 8 15 15 15 10 10 EVAPORATOR Weight lb empty 33 47 92 87 112 158 Net Fluid Volume gal 1 1 1 2 2 8 2 4 3 1 4 7 Maximum Refrigerant Pressure psig 505 505 565 650 565 565 Maximum F...

Страница 18: ...PORATOR Weight lb empty 143 143 167 167 190 Net Fluid Volume gal 3 9 3 9 4 7 4 7 5 4 Maximum Refrigerant Pressure psig 650 650 650 650 650 Maximum Fluid Side Pressure psig 300 300 300 300 300 Evaporat...

Страница 19: ...Net Fluid Volume L 4 1 4 7 10 5 8 9 11 8 17 9 Maximum Refrigerant Pressure kPa 3482 3482 3896 4479 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 2068 Evaporator Connections in In...

Страница 20: ...14 1 17 0 17 0 19 6 Maximum Refrigerant Pressure kPa 4481 4481 4481 4481 4481 Maximum Fluid Side Pressure kPa 2070 0 2070 0 2070 0 2070 0 2070 0 Water Connections in Inlet and Outlet Victaulic IPS 21...

Страница 21: ...70 214 W045 413 256 393 235 W050 484 398 403 317 W055 490 402 407 319 W060 508 424 416 332 W065 519 432 424 337 W071 516 432 427 344 UNIT 30MP WITH MANIFOLD MOUNTING HOLE lb A B C D A020 258 326 134 2...

Страница 22: ...9 249 319 259 W050 369 367 310 313 368 311 W055 372 370 312 315 371 313 W060 382 383 324 323 382 323 W065 388 389 328 327 389 327 W071 388 388 331 330 388 330 ESTIMATED WEIGHT DISTRIBUTION AT EACH MOU...

Страница 23: ...final position remove the packaging and remove the mobility kit wheels if equipped Remove the 3 8 in wheel nuts to remove the wheels from the unit legs Lev el the unit using a level and bolt the unit...

Страница 24: ...pressor mounting rail These RED bolts are for shipping purposes only COMPRESSOR HOLDDOWN BOLTS RED TO BE REMOVED BOTH SIDES COMPRESSOR HOLDDOWN BOLTS TO BE REMOVED BOTH SIDES NOTE For 30MP050 071 unit...

Страница 25: ...tem Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See product data for minimum system fluid volume This system may...

Страница 26: ...not intended for a specific installation Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards 3 All wiring must comply with applicable local...

Страница 27: ...e adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit With 30MPA 09DP matched condensers this is accomplished internally in the 09DP unit Double riser may be requi...

Страница 28: ...piping techniques Refer to Carrier System Design Manual part 3 Carrier E20 II software Refrigerant Piping program or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning E...

Страница 29: ...crons or less isolate the vacuum pump from the system Observe the rate of rise of the vacuum in the sys tem If the vacuum rises by more than 50 microns in a 30 min ute time period continue the dehydra...

Страница 30: ...s in the line Maintain system pressure by using a pressure tank or a combination of relief and reducing valves For units with water manifold option refer to manifold Victaulic spacer fitting kit acces...

Страница 31: ...00 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop GPM LEGEND NOTE Pressure drop curves assume water temperature of 68 F 20 C 1 30MP016 6 30MP045 2 30MP020 7 30MP050 055 3 30MP030 8 30MP060 065...

Страница 32: ...30 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6 7 8 9...

Страница 33: ...30MP045 2 30MP030 6 30MP050 55 3 30MP032 7 30MP060 065 071 4 30MP040 40 35 30 25 20 15 10 5 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 W...

Страница 34: ...170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 Water Pressure Drop GPM Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6...

Страница 35: ...eaking this is the best place to install an air separator if possible 1 Install automatic air vents at all high points in the system If the 30MP unit is located at the high point of the system a vent...

Страница 36: ...ATURE STRAINER 30MP CHILLER CONTROL BOX T SHIELDED GROUNDED WIRE 30MP CHILLER 30MP CHILLER CONTROL BOX CONTROL BOX DISTRIBUTION PUMP EXPANSION TANK S AIR SEPARATOR WITH VENTS DECOUPLER CHILLER 1 CHILL...

Страница 37: ...ine water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 38 during the cleaning process Filter side flow ra...

Страница 38: ...und in the 30MPA MPW control box which contains the low voltage field wiring terminal strip LVT All low voltage field wiring connections are made to this terminal block see Fig 39 Three 7 8 in 22 mm k...

Страница 39: ...236 v AC 238 v Average Voltage 243 236 238 3 239 v Determine maximum deviation from average voltage AB 243 239 4 v BC 239 236 3 v AC 239 238 1 v Maximum deviation is 4 v Determine percent voltage imba...

Страница 40: ...A EA LRA EA RLA EA LRA EA MCA ICF MOCP REC FUSE 016 208 230 3 60 187 253 24 8 240 0 17 2 164 N A N A 48 2 257 2 70 60 380 3 60 342 418 16 0 134 0 12 2 73 32 2 146 2 45 40 460 3 60 414 508 12 4 130 0 8...

Страница 41: ...TS NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 85 1 436 85 1 436 191 5 521 1 250 225 380 3 60 342 418 49 3 252 49 3 252 11...

Страница 42: ...NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 79 4 418 79 4 418 178 7 497 1 250 200 380 3 60 342 418 48 1 252 48 1 252 108 2...

Страница 43: ...o 90 amps is 6 AWG to 3 0 e Incoming wire size range for non fused disconnect with MCA from 90 1 amps to 250 amps is 4 AWG to 350 kcmil f Incoming wire size range for fused disconnect is 6 AWG to 10 A...

Страница 44: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300182 01 Printed in U S A Form 30MP 21SI Pg 44 1118 12 17 Replaces 30M...

Отзывы: