14
4.2 -
Electrical data
30XW-PZE / 30XWHPZE
301
401
451
551
601
651
801
901
1001
1101
Power circuit
Nom. power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current
(1)
Circuit A
A
303
414
414
587
587
587
414
414
587
587
Circuit B
A
-
-
-
-
-
-
414
414
414
587
Option 81
A
-
-
-
-
-
-
529
543
716
751
Maximum start-up current
(2)
Circuit A
A
303
414
414
587
587
587
414
414
587
587
Circuit B
A
-
-
-
-
-
-
414
414
414
587
Option 81
A
-
-
-
-
-
-
597
621
794
855
Cosine phi
Nominal
(3)
0,79
0,86
0,87
0,85
0,87
0,89
0,86
0,87
0,85
0,85
Maximum
(4)
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,90
0,90
Total harmonic distortion
(4)
%
Closed to 0% (negligible)
Maximum power input
†
Circuit A
kW
86
112
126
148
165
174
112
126
148
148
Circuit B
kW
-
-
-
-
-
-
112
126
126
148
Option 81
kW
-
-
-
-
-
-
224
252
274
296
Nominal current drawn
(3)
Circuit A
A
91
115
129
164
177
194
115
129
164
164
Circuit B
A
-
-
-
-
-
-
115
129
129
164
Option 81
A
-
-
-
-
-
-
230
258
293
328
Maximum current drawn (Un)
†
Circuit A
A
143
183
207
268
291
306
183
207
268
268
Circuit B
A
-
-
-
-
-
-
183
207
207
268
Option 81
A
-
-
-
-
-
-
366
414
475
536
Maximum current drawn (Un -10%)
(4)
Circuit A
A
153
196
223
261
292
307
196
223
261
261
Circuit B
A
-
-
-
-
-
-
196
223
223
261
Option 81
A
-
-
-
-
-
-
392
446
484
522
Maximum power input with option 150B
†
Circuit A
kW
76
97
110
129
146
153
97
110
129
129
Circuit B
kW
-
-
-
-
-
-
97
110
110
129
Option 81
kW
-
195
220
239
258
Maximum current drawn (Un) with option 150B
†
Circuit A
A
123
158
179
209
237
249
158
179
209
209
Circuit B
A
-
-
-
-
-
-
158
179
179
209
Option 81
A
-
-
-
-
-
-
316
358
388
418
(1) Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values obtained at standard Eurovent conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C.
(2) Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values obtained at operation with maximum unit power input.
(3) Values obtained at standard Eurovent conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C
(4) Values obtained at operation with maximum unit power input.
†
Values obtained at operation with maximum unit power input. Values given on the unit nameplate.
4.3 -
Short-circuit stability current for all units
Short-circuit stability current for all units using the TN system (earthing system type): 50 kA (conditional system short-circuit current
Icc/Icf at the unit connection point as rms value).
The unit is equipped with protection fuses located in the control box immediately downstream from the unit connection point.
4 - PHYSICAL AND ELECTRICAL DATA