30
Fig. 29 — Schedule Menu
Table 24 — Configuring Schedules (Example)
When OCC1PxxS is set to a value of 65 or greater and a time
schedule is configured for at least one occupancy period, the
system will assume that the unit is going to be the master ele-
ment for this schedule (the system element doing the broad-
casting). In that case the unit Equipment and Supervisory part
table names will be automatically modified to OCCPCxxE and
OCCPCxxS.
By configuring their appropriate Time Schedule decisions to
the same number, other devices on the network can follow this
same schedule. The Enable-Off-Remote Contact must be in the
Enable position or the Remote Contact position with the con-
tacts closed for the unit to operate.
The Unit Run Status (
Main Menu
General Parameters
Run Status
) will indicate the current status of the machine de-
pending on the schedule. The unit Occupied status (
Main
Menu
General Parameters
Setpoint Occupied
) will in-
dicate the current occupied schedule according to the schedule,
either NO or YES.
The Status Unit Control Type (
Main Menu
General Pa-
rameters
) will be 0 when the switch is Off. The Status Unit
Control Type will be 2 when the Enable-Off-Remote Contact
switch input is On.
CCN Control
To operate under this control, Network must be selected under
the Select Machine Mode accessed by touching the Start/Stop
button (see “MACHINE CONTROL METHOD SELECTION”
on page 26).
An external CCN device such as Chillervisor controls the On/
Off state of the machine. Careful evaluation of Chilled Water
Plant control is necessary. In the event Local Control is estab-
lished, be sure that all pumps, valves, and other devices are ca-
pable of operating properly. In the event of a loss of communi-
cation with the network, the machine will start and be con-
trolled locally. The CCN device forces the variable
CHIL_S_S
to control the chiller. The Unit Run Status (
Main Menu
General Parameters
Run Status
) will indicate the current
status of the machine (OFF, RUNNING, STOPPING or DE-
LAY), depending on the CCN command. The unit Occupied
status (
Main Menu
General Parameters
) will indicate the
current occupied state according to the CCN command and
will be displayed as either NO or YES. The Status Unit Control
Type (
ctrl_typ
) will be LOCAL OFF when the Start/Stop but-
ton is Off. The Status Unit Control Type will be CCN when the
Enable-Off-Remote Contact switch input is Closed and the
CHIL_S_S
variable is Stop or Start. For dual chiller control
applications, the slave chiller must be enabled using the CCN
CONTROL option.
CHILLED WATER FLUID TYPE SELECTION
The chilled water fluid type must be configured to obtain the
proper leaving water set point control range and freeze protec-
tion. The Evaporator Fluid Type (flui_typ) (
Main Menu
Configuration Menu
Service Parameters
Evaporator
Fluid Type
) can be set to water or brine.
To configure this option:
Fresh Water
Configure the unit Evaporator Fluid Type to Water for units with-
out brine or glycol installed in the chilled water loop. The factory
default fluid type is fresh water. This option will allow for a water
ITEM
PATH
VALUE
Period 1
Occupied from
Main Menu
Configuration Menu
Schedule Menu
OCCPC01S
or
OCCPC02S
Page 1
00:00
Occupied to
03:00
Monday Select
Yes
Tuesday Select
No
Wednesday Select
No
Thursday Select
No
Friday Select
No
Saturday Select
No
Sunday Select
No
Holiday Select
No
Period 2
Occupied from
Main Menu
Configuration Menu
Schedule Menu
OCCPC01S
or
OCCPC02S
Page 2
07:00
Occupied to
18:00
Monday Select
Yes
Tuesday Select
Yes
Wednesday Select
No
Thursday Select
No
Friday Select
No
Saturday Select
No
Sunday Select
No
Holiday Select
No
Period 3
Occupied from
Main Menu
Configuration Menu
Schedule Menu
OCCPC01S
or
OCCPC02S
Page 3
07:00
Occupied to
21:30
Monday Select
No
Tuesday Select
No
Wednesday Select
Yes
Thursday Select
No
Friday Select
No
Saturday Select
No
Sunday Select
No
Holiday Select
No
Period 4
Occupied from
Main Menu
Configuration Menu
Schedule Menu
OCCPC01S
or
OCCPC02S
Page 4
07:00
Occupied to
17:00
Monday Select
No
Tuesday Select
No
Wednesday Select
No
Thursday Select
Yes
Friday Select
Yes
Saturday Select
No
Sunday Select
No
Holiday Select
No
Period 5
Occupied from
Main Menu
Configuration Menu
Schedule Menu
OCCPC01S
or
OCCPC02S
Page 5
07:00
Occupied to
12:00
Monday Select
No
Tuesday Select
No
Wednesday Select
No
Thursday Select
No
Friday Select
No
Saturday Select
Yes
Sunday Select
No
Holiday Select
No
DISPLAY
NAME
PATH
VALUE
SETPOINT
RANGE
Evaporator
Fluid
Type
Main Menu
Configuration Menu
Service Parameters
1 = Water
38 to 60°F
(3.3 to 15.5°C)
2 = Medium
brine
30 to 60°F
(–1.1 to 15.5°C)
3 = Low brine
15° to 60°F
(9.4° to 15.5°C)
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...