25
Machine Control Methods
This term refers to how the machine is started and stopped.
Several Machine Control Methods are available.
• Local On
• Local Schedule
• Network
• Remote
• Master
The Carrier Controller Start/Stop button
is used to select
one of the above control types; see Fig. 24. The Carrier Con-
troller Start/Stop button is used to select one of the above con-
trol types. Once the Start/Stop button is touched, and assuming
the unit is not running, the current start method will be indicat-
ed in green; if this is the case, the option to switch to “Local
Off” will also be available. See Fig. 24 for details. In addition,
when the Local control type is selected, this button can be used
to select a particular functional mode: On, Off, or Schedule
mode. If the Start/Stop button is green the unit is running. If the
Start/Stop button is gray the unit is not running. If the button is
flashing green then the unit is preparing to start.
Fig. 24 — Machine Control Methods
See Fig. 25 for Machine Control Methods Local Off.
LOCAL ON
With this mode selected, the unit is under local control and will
be allowed to start. The unit will ignore the Remote Control
Contacts, as well as the Enable-Off-Remote Switch (SW1) and
any network commands except Emergency Stop, as well as the
Enable-Off-Remote (SW1) input. Use this method if the unit is
to run all the time without direction from a Building Manage-
ment System or network.
Fig. 25 — Machine Control Methods showing Current
Start Method and Local Off Option
LOCAL SCHEDULE
With this mode selected, the unit is under local control and will
be allowed to start if Occupancy Schedule 1
Configuration
Menu
Schedule Menu
OCCPC01S
indicates the current
time is within an occupied period. Otherwise, the unit will re-
main off. See “DEFINING OCCUPANCY SCHEDULE” on
page 28 for details on configuring a local schedule. The unit
will ignore the Remote Control Contacts, as well as the En-
able-Off-Remote (SW1) and any network commands except
Emergency Stop. Use this method if the unit is to run based on
an occupancy schedule without direction from a Building Man-
agement System or network.
NETWORK
With this mode selected, the unit is under CCN control and will
be controlled by CCN commands. The unit will ignore the Re-
mote Control Contacts, as well as the Enable-Off-Remote
(SW1) input. Use this method if the unit is to run based on a
Building Management System or network.
REMOTE
With this mode selected, the unit is under remote control and will
be allowed to start if the Enable-Off-Remote Switch (SW1) is in
the Remote position and the Remote Contacts (TB5-9 and -10) are
closed. Alternatively, if the Enable-Off-Remote Switch (SW1) is
in the Enable position, the unit will operate regardless of the Re-
mote Contact status (TB5-9 and -10), since it will be bypassed.
The unit will ignore any network commands except Emergency
Stop. Use this method if the unit is to operate the chiller via a con-
tact closure from a Building Management System.
MASTER
With this mode selected, the unit is operating as the Master unit of
a 2-unit Master-Slave Chiller Plant. The Master unit can be started
under Local On, Local Schedule, Network, or Remote. The excep-
tions noted for each of the control methods will still apply. Use
this method if the unit is to run as the Master unit.
Table 19 summarizes the available operating types.
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...