23
4.4 -
Electrical data (continued)
30XA 252-902 - units with options 254 and 255 or units with options 254 and 255 and option 81
30XA
252
302
352
402
452
502
602
702
752
802
852
902
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
269
269
287
402
505
505
574
606
773
805
805
893
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
Nominal start-up current***
Circuit 1**
A
245
245
262
378
480
480
536
562
735
761
761
845
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
Cosine Phi maximum****
0.88
0.88
0.87
0.88
0.88
0.88
0.88
0.88
0.86
0.86
0.87
0.86
Cosine Phi nominal
†
0.85
0.85
0.84
0.84
0.85
0.85
0.85
0.85
0.83
0.84
0.84
0.85
Maximum power input
‡
Circuit 1**
kW
121
131
142
165
185
204
247
267
294
313
343
360
Circuit 2**
kW
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
-
Nominal unit current draw
†
Circuit 1**
A
151
167
186
210
242
268
325
352
412
437
453
512
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
Maximum unit current draw (Un)
‡
Circuit 1**
A
198
215
235
270
303
335
404
436
494
524
572
613
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 231
A
182
196
213
242
272
305
364
397
450
481
531
855
Maximum unit current draw (Un-10%)****
Circuit 1**
A
208
232
253
290
326
360
435
469
531
563
615
659
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
30XA 1002-1702 - units with options 254 and 255 or units with options 254 and 255 and option 81
30XA
1002
1112
1212
1312
1382
1402
1502
1702
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
941
587
587
772
772
893
941
805
Circuit 2**
A
-
772
772
772
772
587
587
761
Option 81
A
-
1085
1131
1198
1228
1248
1294
-
Nominal start-up current***
Circuit 1**
A
865
587
587
772
772
845
865
761
Circuit 2**
A
-
772
772
772
772
587
587
761
Option 81
A
-
1023
1039
1103
1118
1125
1143
-
Cosine Phi maximum****
0.87
0.86
0.87
0.87
0.87
0.86
0.87
0.87
Cosine Phi nominal
†
0.85
0.85
0.86
0.87
0.87
0.86
0.85
0.85
Maximum power input
‡
Circuit 1**
kW
420
182
211
256
278
390
420
343
Circuit 2**
kW
-
279
302
278
299
210
210
343
Option 81
kW
-
460
512
531
571
600
630
-
Nominal unit current draw
†
Circuit 1**
A
552
258
274
340
356
530
556
452
Circuit 2**
A
-
358
392
356
387
278
278
452
Option 81
A
-
616
666
696
743
808
834
-
Maximum unit current draw (Un)
‡
Circuit 1**
A
707
313
359
426
456
661
707
572
Circuit 2**
A
-
459
496
456
491
354
354
572
Option 81
A
-
771
855
882
947
1015
1061
-
Option 231
A
660
-
-
-
-
-
-
-
Maximum unit current draw (Un-10%)****
Circuit 1**
A
760
332
381
462
494
711
760
615
Circuit 2**
A
-
497
527
494
522
380
380
615
Option 81
A
-
828
908
956
1016
1091
1141
-
* Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at operation with maximum unit power input.
** 30XA 1402 to 1702 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D. 30XA 1112, 1212, 1312 and 1382 units: Circuit 1 supplies circuit A,
circuit 2 supplies circuit B.
*** Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor).
Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
**** Values obtained at operation with maximum unit power input.
† Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
‡ Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Notes:
1. Unit sizes 30XA 1112, 1212, 1312, 1382, 1402 to 1702 have two power connection points.