11
Fig. 9 — VFD Nameplate
Recommended Control and Signal Wire Sizes
The recommended minimum size wire to connect I/O signals to
the control terminal blocks is 18 AWG (American Wire Gauge).
Recommended terminal tightening torque is 7 to 9 in.-lb (0.79 to
1.02 N-m).
Recommended Airflow Clearances
Be sure there is adequate clearance for air circulation around the
enclosure. A 6-in. (152.4 mm) minimum clearance is required
wherever vents are located in the VFD enclosure.
Match Power Module Input and Supply Power Ratings
It is important to verify that building power will meet the input
power requirements of the Machine Electrical Data nameplate in-
put power rating. Be sure the input power to the chiller corre-
sponds to the chiller’s nameplate voltage, current, and frequency.
Refer to machine nameplate in Fig. 12. The machine electrical
data nameplate is located on the right side of the control center.
PROVIDE MACHINE PROTECTION
Protect machine and VFD enclosure from construction dirt and
moisture. Keep protective shipping covers in place until machine
is ready for installation.
If machine is exposed to freezing temperatures after water circuits
have been installed, open waterbox drains and remove all water
from cooler and condenser. Leave drains open until system is
filled.
It is important to properly plan before installing a 23XRV unit to
ensure that the environment and operating conditions are satisfac-
tory. The installation must comply with all requirements in the cer-
tified prints.
Chiller should be installed in an indoor environment where the
ambient temperature is between 40 and 104°F (4 and 40°C) with
relative humidity of 95% or less.
Nameplate 1: Specifications and Custom Catalog Number
representing options installed at factory.
See Nameplate 2 (Location behind HIM)
for equivalent base catalog number and separate options.
Cat No: 20GYAN
C
367
ANONNNNNQBQ
UL Open Type/IP00
Rear-UL Type 4X/IP66 with 4X flange kit
Series: A
400V Class
480V Class
Power ND (HD)
Input: 3 Phase 47-63Hz
AC Voltage Range
Amps ND (HD)
Output: 3 Phase 0-400 Hz
AC Voltage Range
Base Frequency (default)
Continuous Amps ND (HD)
60 Sec Ovid Amps ND (HD)
3 Sec Ovid Amps ND (HD)
COOLANT
RATED PRESSURE
200kW (180kW)
342-440
359.5 (295.9)
0-400
50 Hz
367 (302)
403.7 (453)
550.5 (550.5)
432-528
300 HP (250 HP)
338.9 (283.5)
0-460
60 Hz
361 (302)
397.1 (453)
541.5 (543.6)
Treated Water/R134A
185 PSIG
Mfd. on 2015/06/24
Original Firmware: 11.002
Serial Number: 42127997
PRODUCT OF USA FAC 1100
N223
Allen-Bradley
AB
Table 1 — Drive Assembly and Power Module Ratings (LF-2 VFD)
CARRIER PART NUMBER
VFD
FRAME SIZE
ENCLOSURE
TYPE
INPUT
VOLTAGE (V)
RANGE
MAX INPUT
CURRENT
(AMPS)
MAX OUTPUT
CURRENT
a
at 4 kHz
(AMPS)
NOTE(S):
a. 110% output current capability for one minute, 150% output current for 5 seconds.
23XRB2AA_ _ _ _ _ _ _ _ _ _ _
Frame 2AA
NEMA 1
380 to 460
440
440
23XRB2BA_ _ _ _ _ _ _ _ _ _ _
Frame 2BA
NEMA 1
380 to 460
520
440
23XRB2BB_ _ _ _ _ _ _ _ _ _ _
Frame 2BB
NEMA 1
380 to 460
520
520
23XRB2CC_ _ _ _ _ _ _ _ _ _ _
Frame 2CC
NEMA 1
380 to 460
608
608
Table 2 — Drive Assembly and Power Module Ratings (Std Tier VFD)
a
NOTE(S):
a. All voltage and current combinations listed may not be available for sale. Please review Carrier Marketing literature for latest offering.
CARRIER PART NUMBER
ENCLOSURE
TYPE
INPUT VOLTAGE
(Digit Y of part number)
MAX INPUT
CURRENT
(AMPS)
MAX OUTPUT
CURRENT
b
at 2 kHz
(AMPS)
b. 110% output current capability for one minute, 150% output current for 5 seconds.
Y
Voltage/Hz
23XS0_ _ _00Y _ _ F0
c
(Rockwell; S = Air cooled)
c. Last character 0 indicates refrigerant-cooled; last digit A indicates air-cooled.
NEMA 1
3
4
5
7
9
380v / 60 Hz
416v / 60 Hz
460v / 60 Hz
575v / 60 Hz
400v / 50 Hz
230
269
335
445
230
269
335
445
Содержание AquaEdge 23XRV
Страница 53: ...53 Fig 58 23XRV Controls Schematic ...
Страница 54: ...54 Fig 58 23XRV Controls Schematic cont FROM 2000767952 SHEET 3 ...
Страница 55: ...55 Fig 58 23XRV Controls Schematic cont ...
Страница 56: ...56 Fig 59 23XRV Controls Schematic Rockwell Standard Tier VFD Shown ...
Страница 57: ...57 Fig 60 23XRV LF2 VFD Wiring Diagram ...
Страница 65: ...65 Fig 70 23XRV Insulation Area Units with P Compressor ...