13
Fig. 11 — Control Center Components (Std Tier VFD)
Fig. 12 — Machine Electrical Data Nameplate
Step 2 — Rig the Machine
The 23XRV machine can be rigged as an entire assembly. Large
interconnecting piping has flanged connections that allow the
compressor, cooler, and condenser sections to be separated and
rigged individually. In addition, the VFD can be removed and
rigged separately.
RIG MACHINE ASSEMBLY
See rigging instructions on label attached to machine. Also refer to
rigging guide (Fig. 13), physical data in Fig. 14 and 15, and
Tables 3-19.
Lift machine only from the points indicated in rigging
guide.
Each lifting cable or chain must be capable of supporting
the entire weight of the machine.
Contractors are not authorized to disassemble any part of the
chiller without Carrier's supervision. Any request otherwise must
be in writing from the Carrier Service Manager.
NOTE: Carrier suggests that a structural engineer be consulted if
transmission of vibrations from mechanical equipment is of
concern.
FRONT VIEW – DOORS REMOVED
2
1
3
7
8
6
9
10
5
LEGEND
CONTROL PANEL
ASSEMBLY
EXPANDED
VIEW
4
1
— Input Circuit Breaker
2
— Power Module
3
— Control Relays (CR1 - CR6)
4
— Location of Control Panel Assembly - see expanded view
5
— Drive Status Indicator
6
— Ground Lug
7
— 120V Control Transformer
8
— 120V Vaporizer Heater Transformer
9
— 15 Amp Control Circuit Breaker
10
— Cooling Fan
a23-1555
WARNING
Lifting machine from points other than those specified may
result in serious damage to the unit and personal injury. Rig-
ging equipment and procedures must be adequate for machine
weight. See Fig. 13 for machine weights.
NOTE: These weights are broken down into component sec-
tions for use when installing the unit in sections. For the com-
plete machine weight, add all component sections and
refrigerant charge together. See Tables 8-19 for machine com-
ponent weights.
Содержание AquaEdge 23XRV
Страница 53: ...53 Fig 58 23XRV Controls Schematic ...
Страница 54: ...54 Fig 58 23XRV Controls Schematic cont FROM 2000767952 SHEET 3 ...
Страница 55: ...55 Fig 58 23XRV Controls Schematic cont ...
Страница 56: ...56 Fig 59 23XRV Controls Schematic Rockwell Standard Tier VFD Shown ...
Страница 57: ...57 Fig 60 23XRV LF2 VFD Wiring Diagram ...
Страница 65: ...65 Fig 70 23XRV Insulation Area Units with P Compressor ...