58
Fig. 61 — Communications Interface Board Status LEDs (LF-2 VFD)
Fig. 62 — Drive Status Indicator Status LEDs (Std Tier VFD)
DPI Communications Interface Board
Status LEDs
a23-1592
2
8
5
7
9
1
3
4
6
Allen-Bradley
a19-1815
NOTES:
1. A Type 1 alarm indicates that a condition exists. Type 1 alarms are user configurable.
2. A Type 2 alarm indicates that a configuration error exists and the drive cannot be started. Type 2 alarms are not configurable.
NAME
COLOR
STATE
DESCRIPTION
STS (Status)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
Drive is not running. A type 2 (non-configurable) alarm condition exists and the drive cannot be started.
Steady
Drive is not running, a type 1 alarm condition exists. The drive can be started.
Red
Flashing
A major fault has occurred. Drive cannot be started until fault condition is cleared.
Steady
A non-resettable fault has occurred.
Red/Yellow
Flashing Alternately
A minor fault has occurred. When running, the drive continues to run. System is brought to a stop under
system control. Fault must be cleared to continue. Use parameter 950 [Minor Flt Config] to enable. If not
enabled, acts like a major fault.
Green/Red
Flashing Alternately
Drive is flash updating.
ENET
None (Unlit)
Off
Adapter and/or network is not powered, adapter is not properly connected to the network, or adapter needs
an IP address.
Red
Flashing
An Ethernet/IP connection has timed out.
Steady
Adapter failed the duplicate IP address detection test.
Red/Green
Flashing Alternately
Adapter is performing a self-test.
Green
Flashing
Adapter is properly connected but is not communicating with any devices on the network.
Steady
Adapter is properly connected and communicating on the network.
LINK
None (Unlit)
Off
Adapter is not powered or is not transmitting on the network.
Green
Flashing
Adapter is properly connected and transmitting data packets on the network.
Steady
Adapter is properly connected but is not transmitting on the network.
NOTE: Key pad is not standard.
Содержание AquaEdge 23XRV
Страница 53: ...53 Fig 58 23XRV Controls Schematic ...
Страница 54: ...54 Fig 58 23XRV Controls Schematic cont FROM 2000767952 SHEET 3 ...
Страница 55: ...55 Fig 58 23XRV Controls Schematic cont ...
Страница 56: ...56 Fig 59 23XRV Controls Schematic Rockwell Standard Tier VFD Shown ...
Страница 57: ...57 Fig 60 23XRV LF2 VFD Wiring Diagram ...
Страница 65: ...65 Fig 70 23XRV Insulation Area Units with P Compressor ...