2

Fan wheels are designed to 
provide low operating costs

The forward-curved, centrifugal, 
double-inlet fans are statically and 
dynamically balanced at the factory to
minimize transmission of vibration 
to the building structure.

The belt-driven motor (single or 

three phase) has a variable-pitch pulley 
which adjusts at the jobsite to accom-
modate limited ranges of air quantities 
and pressures.

All motors (single and three phase) 

are UL listed, factory wired, single 
speed with thermal overload protec-
tion and are continuous duty rated. 
Motors are supplied with permanently 
lubricated bearings, class-B insulation 
and are open drip-proof. The motor 
mount has an adjustable platform for 
easy belt adjustment. The motor and 
its mounting are independently isolated 
from the cabinet and the blower. An 
adjustable pitch pulley allows cfm bal-
ancing to meet system requirements. 
Motor drive packages are provided 
with keyed pulleys.

Complete factory assembly 
minimizes on-the-jobsite costs 
and problems

Compact, lightweight units are designed 
for easy mounting. Knockouts designed 
to accept 

3

/

8

-in. threaded rods are 

provided on the top and bottom of each 
corner of the unit One-in. duct collars 
on discharge and on return are fur-
nished standard. These integral duct 
collars cut installation time and labor 
expense.

Durable construction means 
easy-to-maintain units

The 42BHC,BVC fan coils casings are 
fabricated from heavy-gage galvanized 
G90 steel, reinforced for maximum 
rigidity and structural strength. Remov-
able side panels with tool-less camlock 
fasteners allow easy access for servic-
ing interior components.

One-inch matte surface, fiberglass 

thermal/acoustical insulation lines the 
fan coil cabinets to prevent sweating 
and to muffle sound transmission.

The stainless steel, double-sloped 

condensate drain pan extends under 
full coil surface to cut maintenance 
costs.

Slide-in return-duct collar filter 

makes it possible to remove and 
replace the filter without disturbing 
return air ductwork.

Table of contents

Page

Features/Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Base Unit Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-21
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  22
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   23-33
Typical Wiring Schematics  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  37
Controls  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  38
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39,40

INTERNAL FEATURES OF A 42BHC FAN COIL UNIT

Содержание AIRSTREAM 42BHC

Страница 1: ...round comfort air conditioning with central station operating economy A variety of coil options reduces first cost Four 6 or 8 row cooling coils combine needed capacities with the most effi cient hea...

Страница 2: ...in threaded rods are provided on the top and bottom of each corner of the unit One in duct collars on discharge and on return are fur nished standard These integral duct collars cut installation time...

Страница 3: ...pprox lb per row of coil 0 240 0 240 0 324 0 324 0 420 0 492 0 768 1 020 FANS Number Size in 1 9 x 4 1 9 x 6 1 10 x 4 1 10 x 7 1 11 x 10 1 12 x 9 1 12 x 12 1 15 x 12 COPPER COIL CONN 8 ROW in Cooling...

Страница 4: ...12 kW 1 or 2 stage only single phase 1 to 40 kW 1 stage only 3 phase 4 to 40 kW 1 or 2 stage only 3 phase 12 to 40 kW 1 2 or 3 stage 3 phase Heater coils are constructed of high grade resistance wire...

Страница 5: ...ntrol valve 4 pipe ACO MCO automatic changeover manual changeover with on auto fan mode button one or 2 stage electric heat signal available purge cycle and temperature sensor for 2 pipe cold water ho...

Страница 6: ...C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201...

Страница 7: ...J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16 201 4 71 2 1...

Страница 8: ...A B C D E F J K 06 9 x 4 363 16 2811 16 181 2 71 8 109 16 137 8 11 8 241 16 167 16 273 16 351 4 08 9 x 6 363 16 2811 16 181 2 89 16 109 16 137 8 11 8 241 16 167 16 273 16 351 4 10 10 x 4 373 4 371 16...

Страница 9: ...BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 10 x...

Страница 10: ...pecifications are subject to change without notice 3 Right hand shown left hand opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BVC DIMENSIONS in Fan Size Depth Wid...

Страница 11: ...42BVC DIMENSIONS in Fan Size Depth Width Height Supply Duct Return Duct A B C E F 06 9 x 4 20 281 16 361 2 71 8 109 16 33 4 241 16 167 16 08 9 x 6 20 281 16 361 2 89 16 109 16 33 4 241 16 167 16 10 1...

Страница 12: ...1 55 47 52 55 51 52 47 205 With Heat 50 59 59 68 59 50 68 59 236 10 No Heat 63 71 55 63 71 63 63 55 253 With Heat 62 76 68 81 76 62 81 68 287 12 No Heat 64 72 56 64 72 64 64 56 256 With Heat 63 76 68...

Страница 13: ...39 29 20 10 20 46 35 23 12 30 74 55 37 18 40 98 74 49 25 NOTE Unit weights shown in pounds 10 are based on the 8 row coil and 1 Hp motor UNIT 42BVC CONFIGURATION RIGHT HAND UNITS LEFT HAND UNITS TOTA...

Страница 14: ...ET RIGHT HAND SIDE VIEWS W 4 2 4 C 1 H A A B A 2 4 MIXING BOX NOTE All dimensions in inches 42BHC BVC UNIT SIZE DIMENSIONS in H W A B C 06 18 5 28 6 24 11 08 18 5 28 6 24 11 10 20 25 37 8 33 13 12 20...

Страница 15: ...08 28 51 6 16 1 42BHC10 37 55 2 18 1 42BHC12 37 55 2 18 1 42BHC16 47 55 4 18 1 42BHC20 48 57 8 18 1 42BHC30 48 59 8 20 1 42BHC40 62 63 0 20 1 UNIT DIMENSIONS in W D A 42BVC06 28 35 5 16 1 42BVC08 28 3...

Страница 16: ...5 20 psig 1 in 14 72 19 38 2 774 8 247 20 65 25 19 8 17 psig High Close Off Power On Power Off 2 way 1 2 in 13 29 2 285 16 09 7 41 3 5 60 psig 3 4 in 13 59 3 156 18 59 7 936 4 6 60 psig 1 in 14 97 3 3...

Страница 17: ...Out 42BHC BVC UNIT SIZE HEAD STUB OUT SIZES in 8 Row Coil SO Nominal 6 Row Coil SO Nominal 4 Row Coil SO Nominal Heating 1 or 2 SO Row Coil Nominal 06 1 0 75 0 75 0 5 08 1 0 75 0 75 0 5 10 1 0 75 0 75...

Страница 18: ...1 8 47 8 6 0 61 8 123 4 81 8 211 16 1 31 2 63 4 133 8 151 2 211 16 211 16 93 16 33 4 2 313 16 61 8 123 4 1513 16 31 4 31 4 101 4 47 8 8 0 61 8 123 4 101 4 211 16 10 12 4 0 73 4 143 8 515 16 211 16 1 5...

Страница 19: ...d quick vent feature via knurled vent screw Application Optional replacement for manual air vent Automatically passes minute quantities of air through the fiber discs which expand upon contact with wa...

Страница 20: ...flow balancing 3 0 8 9 150 200 STRAINER Y type body with 50 mesh stainless steel screen Application Used for removal of small particles from system water during normal system operation Should not be u...

Страница 21: ...placed in the open position for second ary unit flushing constant water flow prior to start up etc Manual override is automatically disengaged when valve is electrically acti vated Consult factory fo...

Страница 22: ...Drop for Cv Factor and Water Flow Rate table on page 33 From the Cv Factor by Coil and Unit Size table on page 32 find the Cv value for unit size 16 with four rows Cv 7 2 P GPM 0 658 x Cv 2 7 0 0 658...

Страница 23: ...04 1 00 1 00 1 00 0 95 0 97 0 97 0 90 0 94 0 93 0 85 0 90 0 89 0 80 0 86 0 85 0 75 0 82 0 81 0 70 0 78 0 77 0 65 0 74 0 72 0 60 0 70 0 67 0 55 0 66 0 62 0 50 0 62 0 57 0 45 0 58 0 52 0 40 0 53 0 47 0...

Страница 24: ...38 4 25 1 45 30 3 21 7 50 22 5 18 6 8 40 42 6 27 2 45 33 7 23 3 50 24 7 19 8 10 1000 4 40 40 5 27 3 45 31 6 23 7 50 23 4 20 6 6 40 52 2 33 3 45 41 7 28 7 50 31 2 24 5 8 40 57 7 36 0 45 46 4 31 0 50 34...

Страница 25: ...42 4 99 4 11 3 119 2 91 1 25 9 8 122 3 92 7 8 0 99 8 83 2 6 0 75 6 75 6 11 8 147 9 102 7 9 9 124 0 93 0 8 0 100 3 84 0 14 1 175 8 112 1 12 0 150 4 102 4 10 0 125 5 93 3 DB Dry Bulb Temperature EWT Ent...

Страница 26: ...165 7 117 1 10 8 135 2 103 6 8 4 104 4 90 7 16 0 199 7 129 9 13 5 168 3 116 6 10 9 136 1 103 6 18 9 236 1 142 0 16 3 203 9 128 8 13 6 170 6 116 0 28 12 2 170 8 119 3 9 9 139 0 105 2 7 6 106 9 91 7 14...

Страница 27: ...2 27 6 220 5 134 1 22 2 177 4 117 0 16 9 135 1 101 5 18 13 4 120 7 96 0 9 6 86 3 82 0 6 3 56 3 56 3 18 0 162 2 112 6 13 7 122 9 96 9 9 3 84 1 84 1 23 2 208 8 129 3 18 5 166 1 112 7 13 8 124 6 97 8 DB...

Страница 28: ...0 29 4 51 8 36 2 66 5 34 6 65 9 41 2 45 26 0 26 0 32 8 32 8 37 9 23 8 38 3 30 8 53 0 29 4 52 6 36 1 50 18 9 18 9 25 9 25 9 21 8 18 0 25 9 25 9 37 2 23 7 38 3 31 0 1600 40 41 9 34 1 43 7 43 7 56 7 32 3...

Страница 29: ...0 37 3 68 6 44 6 84 6 42 7 83 7 49 8 45 40 4 32 9 42 2 42 2 54 6 31 2 54 6 38 6 70 6 36 9 70 1 44 2 50 27 5 27 5 34 9 34 9 38 6 24 9 40 2 33 0 54 7 30 9 55 2 38 5 1600 40 59 0 43 0 55 1 55 1 75 1 40 9...

Страница 30: ...2 10 in x 7 in 1000 629 0 13 688 0 15 744 0 18 789 0 20 849 0 22 898 0 24 946 0 26 991 0 29 1035 0 31 1100 656 0 16 712 0 19 765 0 21 816 0 23 865 0 26 912 0 28 958 0 30 1002 0 33 1044 0 35 1200 686 0...

Страница 31: ...1292 0 63 1326 0 66 1359 0 69 1392 0 72 1400 1124 0 55 1162 0 58 1198 0 61 1234 0 64 1269 0 67 1304 0 70 1338 0 73 1371 0 77 1404 0 80 16 11 in x 10 in 1400 985 0 42 1018 0 45 1051 0 48 1083 0 51 111...

Страница 32: ...7 0 22 0 11 0 06 0 09 0 18 1100 0 08 0 29 0 44 0 58 0 03 0 07 0 14 0 20 0 27 0 14 0 08 0 11 0 22 1200 0 09 0 35 0 52 0 69 0 04 0 08 0 16 0 24 0 32 0 16 0 09 0 13 0 26 1300 0 11 0 41 0 61 0 81 0 05 0 0...

Страница 33: ...4 4 15 7 18 4 21 3 24 5 27 9 31 5 4 8 0 6 0 9 1 2 1 6 2 0 2 5 3 0 3 6 4 2 4 9 5 6 6 4 7 2 8 1 9 0 10 0 11 0 12 1 13 2 14 4 16 9 19 6 22 5 25 6 28 9 5 0 0 5 0 8 1 1 1 4 1 8 2 3 2 7 3 3 3 9 4 5 5 2 5 9...

Страница 34: ...34 Typical wiring schematics BASE UNIT SINGLE PHASE POWER MOTOR CONTROL DISCONNECT OPTION SINGLE PHASE POWER...

Страница 35: ...35 BASE UNIT THREE PHASE POWER MOTOR CONTROL DISCONNECT OPTION THREE PHASE POWER...

Страница 36: ...PERATION AND HONEYWELL THERMOSTAT 2 PIPE OR 4 PIPE HEATING COOLING WITH SINGLE SPEED FAN OPERATION AND HONEYWELL DIGITAL THERMOSTAT NOTES 1 Optional valves are field wired 2 No HW valve with electric...

Страница 37: ...s that Carrier s fan coil units have been examined by UL and comply with the organization s applicable standards of U S and Canadian national product safety standard UL 1995 CSA C22 2 No 236 kW 42BHC...

Страница 38: ...ric heat options and control option Interlocking disconnect switch Heater power fusing 24 v class 2 transformer 40 va 8 pole control terminal strip Auto reset temperature limit switch Manual reset bac...

Страница 39: ...onnection and 1 2 in male MPT stainless secondary drain connection capped when not required The outside surface of the drain pan shall be insulated with 1 8 in closed cell insulation C Fans Belt drive...

Страница 40: ...the event of an air failure 2 Single phase heaters shall be available in 115 208 230 or 277 volts 60 Hz Three phase electric heat shall be available in 208 230 or 460 volts 60 Hz 2 Field Installed Ac...

Отзывы: