T-359
7–30
7.19.2
Sensor Replacement
a. Turn unit power OFF and disconnect power supply.
NOTE
Include white date code label when cutting out and removing defective sensors. The label could be
required for warranty returns.
b. Cut cable. Slide the cap and grommet off a bulb type sensor and save for reuse.
Do not cut the grommet.
c. Cut one wire of existing cable 40 mm (1-1/2 inches) shorter than the other wire.
d. Cut replacement sensor wires (opposite colors) back 40 mm (1-1/2 inches). (See
e. Strip back insulation on all wiring 6.3 mm (1/4 inch).
Figure 7.14 Sensor Types
f. Slide a large piece of heat shrink tubing over the cable, and place the two small pieces of heat shrink tubing,
one over each wire, before adding crimp fit tings as shown in
.
Figure 7.15 Sensor and Cable Splice
1. Cable
2. Sensor (Typical)
3. Large Heat Shrink Tubing (1)
4. Heat Shrink Tubing, 2 or 3 as required
- - - - -
Sensor
40mm (1--1/2 inch)
6.3mm (1/4--inch)
Mounting Stud Type
Sensor
40 mm (1-1/2 inches)
6.3--mm (1/4--inch)
Bulb Type
Содержание 69NT40-561-019
Страница 2: ......
Страница 4: ......
Страница 74: ......
Страница 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Страница 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Страница 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Страница 130: ......
Страница 134: ......
Страница 135: ......