T-354
7–2
Figure 7.2 Manifold Gauge Set
A. Connection to Low Side of System
B. Connection to either: Refrigerant Cylinder or Oil Container
C. Connection to High Side of System
- - - - -
7.3
MANIFOLD GAUGE SET
The manifold gauge set (see
) is used to determine system operating pressure, add refrigerant charge,
and to equalize or evacuate the system.
When the suction pressure hand valve is frontseated (turned all the way in), the suction (low) pressure can be
checked. When the discharge pressure hand valve is frontseated, the discharge (high) pressure can be checked.
When both valves are open (turned counter-clockwise all the way out), high pressure vapor will flow into the low
side. When the suction pressure valve is open and the discharge pressure valve shut, the system can be charged.
Oil can also be added to the system.
A R-134a manifold gauge/hose set with self-sealing hoses (see
) is required for service of the models
covered within this manual. The manifold gauge/hose set is available from Carrier Transicold. (Carrier Transicold
P/N 07-00294-00, which includes items 1 through 6,
). To perform service using the manifold gauge/
hose set, do the following:
Preparing Manifold Gauge/Hose Set For Use
If the manifold gauge/hose set is new or was exposed to the atmosphere, it will need to be evacuated to remove
contaminants and air as follows:
1. Back seat (turn counterclockwise) both field service couplings (see
) and midseat both hand
valves.
2. Connect the yellow hose to a vacuum pump and refrigerant 134a cylinder.
3. Evacuate to 10 inches of vacuum and then charge with R-134a to a slightly positive pressure of 0.1kg/cm
(1.0psig).
4. Front seat both manifold gauge set valves and dis connect from cylinder. The gauge set is now ready for
use.
OPENED (Backseated )
HAND VALVE
CLOSED (Frontseated)
HAND VALVE
SUCTION
PRESSURE
GAUGE
DISCHARGE
PRESSURE
GAUGE
A
B
C
Содержание 69NT40-541-306
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 78: ...T 354 5 8 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode ...
Страница 142: ...T 354 8 2 Figure 8 2 Schematic Diagram Standard Unit Configuration BASED ON 62 66686 00 ...
Страница 143: ...8 3 T 354 Figure 8 3 Unit Wiring Diagram Standard Unit Configuration 1 of 2 BASED ON 62 66686 00 ...
Страница 144: ...T 354 8 4 Figure 8 4 Unit Wiring Diagram Standard Unit Configuration 2 of 2 BASED ON 62 66686 00 ...
Страница 148: ...T 354 8 8 ...
Страница 152: ......
Страница 153: ......