T-354
7–32
7.22.2
Controller Troubleshooting
A group of test points (TP) (see
) are provided on the controller for troubleshooting electrical circuits
). A description of the test points follows:
Figure 7.27 Controller Section of the Control Box
NOTE
Use a digital voltmeter to measure AC voltage between TPs and ground (TP9), except for TP8.
TP 2
- This test point enables the user to check if the internal protector for the compressor motor (IP-CP) or high
pressure switch is open.
TP 3
- This test point enables the user to check if the water pressure switch (WP) contact is open or closed.
TP 4
- This test point enables the user to check if the internal protector for the condenser fan motor (IP-CM) is open
or closed.
TP 5
- This test point enables the user to check if the internal protectors for the evaporator fan motors (IP-EM1 or
IP-EM2) are open or closed.
TP 6
- This test point enables the user to check if the controller water tank heater relay (TQ) is open or closed.
TP 7
- This test point is not used in this application.
TP 8
- This test point is not applicable to the units covered herein.
TP 9
- This test point is the chassis (unit frame) ground connection.
TP 10
- This test point enables the user to check if the heat termination thermostat (HTT) contact is open or closed.
Controller Software
Programming Port
Mounting Screw
Controller
Test Points
Содержание 69NT40-541-306
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 78: ...T 354 5 8 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode ...
Страница 142: ...T 354 8 2 Figure 8 2 Schematic Diagram Standard Unit Configuration BASED ON 62 66686 00 ...
Страница 143: ...8 3 T 354 Figure 8 3 Unit Wiring Diagram Standard Unit Configuration 1 of 2 BASED ON 62 66686 00 ...
Страница 144: ...T 354 8 4 Figure 8 4 Unit Wiring Diagram Standard Unit Configuration 2 of 2 BASED ON 62 66686 00 ...
Страница 148: ...T 354 8 8 ...
Страница 152: ......
Страница 153: ......