3-20
T-317
Table 3-6 Controller Alarm Indications (Sheet 3 of 3)
AL66 Suction Pressure
Transducer Failure
Alarm 66 is triggered by a suction pressure transducer reading outside the valid
range of 73.20 cm Hg (30 in Hg) to 32.34 Kg/cm
2
(460 psig). This is a display
alarm and has no associated failure action.
AL67 Humidity Sensor
Failure
Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%
to 100% relative humidity. If alarm AL67 is triggered when the dehumidification
mode is activated, then the dehumidification mode will be deactivated.
AL68 Condenser Pressure
Transducer Failure
Alarm 68 is triggered by a condenser pressure transducer reading outside the
valid range of 73.20 cm Hg (30 in Hg) to 32.34 Kg/cm
2
(460 psig). This is a dis-
play alarm and has no associated failure action.
AL69 Suction Temperature
Sensor Failure
Alarm 69 is triggered by a suction temperature sensor reading outside the valid
range of --60
_
C (--76
_
F) to 150
_
C (302
_
F). This is a display alarm and has no
associated failure action.
NOTE
If the Controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and
AL71 will be processed as Controller alarms AL70 and AL71.
ERR
#
Internal
Microprocessor
Failure
The Controller performs self-check routines. if an internal failure occurs, an
“ERR” alarm will appear on the display. This is an indication the Controller needs
to be replaced.
ERROR
DESCRIPTION
ERR 0 -- RAM failure
Indicates that the Controller working memory has
failed.
ERR
#
Internal
Microprocessor
Failure
EER 1 -- Program Memory
failure
Indicates a problem with the Controller program.
EER 2 -- Watchdog
time--out
The Controller program has entered a mode where-
by the Controller program has stopped executing.
EER 3 -- N/A
N/A
EER 4 -- N/A
N/A
EER 5 -- A-D failure
The Controller’s Analog to Digital (A-D) converter
has failed.
EER 6 -- IO Board failure
Internal program/update failure.
EER 7 -- Controller failure
Internal version/firmware incompatable.
EER 8--DataCorder failure Internal DataCorder memory failure.
EER 9 -- Controller failure
Internal controller memory failure.
In the event that a failure occurs and the display cannot be updated, the status
LED will indicate the appropriate EER code using Morse code as shown below.
E R R 0 to 9
ERR0 = . .--. .--. ----------
ERR1 = . .--. .--. . --------
ERR2 = . .--. .--. . . ------
ERR3 = . .--. .--. . . . ----
ERR4 = . .--. .--. . . . . --
ERR5 = . .--. .--. -- . . . .
ERR6 = . .--. .--. ---- . . .
ERR7 = . .--. .--. ------ . .
ERR8 = . .--. .--. -------- .
ERR9 = . .--. .--. -------- .
Entr
StPt
Enter Setpoint
(Press Arrow &
Enter)
The Controller is prompting the operator to enter a set point.
LO
Low Main Voltage
(Function Codes
Cd27--38 disabled
and NO alarm
stored.)
This message will be alternately displayed with the set point whenever the supply
voltage is less than 75% of its proper value.