59SP6A: Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43
Size the Vent and Combustion Air Pipes
General
Furnace combustion air and vent pipe connections are sized for 2-in. (50
mm ND) PVC/ABS DWV pipe. The combustion air and vent pipe
connections also accommodate 60 mm polypropylene venting systems
with outside diameters of approximately 60 mm (2-3/8 inches). Any pipe
diameter change should be made outside furnace casing in vertical pipe.
Any change in diameter to the pipe must be made as close to the furnace
as reasonably possible. See
.
A93034
Fig. 50 – Combustion Air and Vent Pipe Diameter Transition
Location and Elbow Configuration
The Maximum Vent Length for the vent and combustion air pipe (when
used) is determined from the Maximum Equivalent Vent Length in
minus the number of fittings multiplied by the deduction for
each type of fitting used from
.
NOTE:
Maximum Equivalent Vent Length (MEVL) includes standard
and concentric vent termination and does NOT include elbows. Use
Table 13 – Maximum Equivalent Vent Length - Ft. (M)
NOTE:
1.40K Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia.) shipped in the loose parts bag or available through Replacement Components required under 10-ft. (3 M)
TEVL in all orientations. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level. Failure to use an outlet restrictor may result in flame disturbances or flame sense
lock-out.
2.60K Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia. available through Replacement Components) required for less than 5-ft. (1.5 M) TEVL in downflow and
horizontal orientations only. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.
3.
120K Inducer Outlet Restrictor disk (P/N
337683-402
; 1.50-in. (38 mm) Dia. available through
Replacement Components
) required for less than 5-ft. (1.5 M) TEVL in downflow and
horizontal orientations only. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.
A13110
NOTICE
!
OPTIONAL CONFIGURATION FOR COMBUSTION AIR INLET
PIPE
In applications where there is a risk of excessive moisture entering the
combustion air inlet pipe, a moisture trap may be added to the inlet pipe
to help prevent moisture from entering the furnace from the combustion
air inlet pipe. See
When sizing venting systems, the equivalent length of the optional
moisture trap (15 feet/5 M) must be taken into account.
FURNACE
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
NOT IN
HORIZONTAL
SECTION
Unit Size
40,000
1
60,000
2
80,000
100,000
120,000
3
140,000
3
Altitude
(feet)
Pipe Dia.
(in)
1
½
2
2
½
1
½
2
2
½
3
1
½
2
2
½
3
4
2
2
½
3
4
2
½
3
4
2
½
3
4
0-2000
40
155
185
20
100
175
200
15
55
130
175
200
20
80
175
200
10
75
185
5
65
155
2001-3000
35
150
175
95
165
185
10
49
125
165
185
15
75
165
185
70
175
N/A
60
140
3001-4000
30
135
160
16
90
155
175
115
155
175
155
175
5
65
165
120
4001-4500
25
130
155
15
85
150
170
44
110
150
165
10
70
170
N/A
60
160
50
110
4501-5000
125
145
80
145
165
145
160
65
150
165
45
100
5001-6000
20
120
130
75
140
155
41
100
135
150
140
155
155
35
80
6001-7000
15
110
120
13
70
130
145
N/A
38
90
125
140
60
135
145
50
140
30
65
7001-8000
10
100
110
10
65
120
135
36
120
125
N/A
55
125
135
46
130
25
45
8001-9000
90
95
5
60
115
125
33
80
110
115
50
115
125
43
120
15
30
9001-10000
5
80
85
N/A
55
105
115
30
75
100
105
45
100
115
39
115
10
15
Maximum Equivalent Vent Length - Meters
Unit Size
40,000
1
60,000
2
80,000
100,000
120,000
3
140,000
3
Altitude
(meters)
Pipe Dia.
(mm)
38
51
64
38
51
64
76
38
51
64
76
102
51
64
76
102
64
76
102
64
76
102
0-610
12.1 47.2 56.3 6.0 30.4 53.3 60.9 4.5 16.7 39.6 53.3 60.9 6.0 24.3 53.3 60.9 3.0 22.8 56.3 1.5 19.8 47.2
611-914
10.6 45.7 53.3
28.9 50.2 56.3
3.0
14.9 38.1 50.2 56.3 4.5 22.8 50.2 56.3
21.3 53.3
NA
18.2 42.6
915-1219
9.1
41.1 48.7 4.8 27.4 47.2 53.3
35.0 47.2 53.3
47.2 53.3 1.5 19.8 50.2
36.5
1220-1370
7.6
39.6 47.2
4.5
25.9 45.7 51.8
13.4 33.5 45.7 50.2
3.0
21.3
51.8
NA
18.2 48.7
15.2 33.5
1371-1524
38.1 44.1
24.3 44.1 50.2
44.1 48.7
19.8 45.7 50.2
13.7 30.4
1525-1829
6.0
36.5 39.6
22.8 42.6 47.2
12.4 30.4 41.1 45.7
42.6 47.2
47.2
10.6 24.3
1830-2134
4.5
33.5 36.5 3.9 21.3 39.6 44.1
NA
11.5 27.4 38.1 42.6
18.2 41.1 44.1
15.2 42.6
9.1
19.8
2135-2438
3.0
30.4 33.5 3.0 19.8 36.5 41.1
10.9
36.5 38.1
NA
16.7 38.1 41.1
14.0 39.6
7.6
13.7
2439-2743
27.4 28.9 1.5 18.2 35.0 38.1
10.0 24.3 33.5 35.0
15.2 35.0 38.1
13.1 36.5
4.5
9.1
2744-3048
1.5
24.3 25.9 NA 16.7 32.0 35.0
9.1 22.8 30.4 32.0
13.7 30.4 35.0
11.8 35.0
3.0
4.5
Long
Medium
Mitered
Concentric
Standard 2-in., 3-in., or
optional 4-in. termination.
ELBOW CONFIGURATIONS
VENT TERMINAL CONFIGURATIONS