Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
FURNACE
INPUT
(BTUH)
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of
Opening and
Duct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
Free Area of
Opening and
Duct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
Free Area of
Opening and
Duct
Sq. In (mm)
Round Duct
In. (mm) Dia.
40,000*
20 (12904)
5 (127)
14 (8696)
5 (127)
10 (6452)
4 (102)
60,000
30 (19355)
6 (152)
20 (13043)
5 (127)
15 (9678)
5 (127)
80,000
40 (25807)
7 (178)
27 (17391)
6 (152)
20 (12904)
5 (127)
100,000
50 (32258)
8 (203)
34 (21739)
7 (178)
25 (16130)
6 (152)
120,000
60 (38709)
9 (229)
40 (26087)
7 (178)
30 (19355)
6 (152)
EXAMPLES: Determining Free Area
FURNACE
WATER HEATER
TOTAL INPUT
100,000
+
30,000
= (130,000 divided by 4,000)
= 32.5 Sq. In. for each two Vertical Ducts or Openings
60,000
+
40,000
= (100,000 divided by 3,000)
= 33.3 Sq. In. for each Single Duct or Opening
80,000
+
30,000
= (110,000 divided by 2,000)
= 55.0 Sq. In. for each two Horizontal Ducts
Table 4 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30
40
50
40
60
80
100
120
Space Volume Ft
3
(M
3
)
0.60
1,050 (29.7)
1,400 (39.6)
1,750
(49.5)
1,400 (39.6)
1,500 (42.5)
2,000 (56.6)
2,500 (70.8)
3,000 (84.9)
0.50
1,260 (35.6)
1,680 (47.5)
2,100
(59.4)
1,680 (47.5)
1,800 (51.0)
2,400 (67.9)
3,000 (84.9)
3,600
(101.9)
0.40
1,575 (44.5)
2,100 (59.4)
2,625
(74.3)
2,100 (59.4)
2,250 (63.7)
3,000 (84.9)
3,750
(106.1)
4,500
(127.3)
0.30
2,100 (59.4)
2,800 (79.2)
3,500
(99.1)
2,800 (79.2)
3,000 (84.9)
4,000
(113.2)
5,000
(141.5)
6,000
(169.8)
0.20
3,150 (89.1)
4,200
(118.9)
5,250
(148.6)
4,200
(118.9)
4,500
(127.3)
6,000
(169.8)
7,500
(212.2)
9,000
(254.6)
0.10
6,300
(178.0)
8,400
(237.8)
10,500
(297.3)
8,400
(237.8)
9,000
(254.6)
12,000
(339.5)
15,000
(424.4)
18,000
(509.2)
0.00
NP
NP
NP
NP
NP
NP
NP
NP
NP = Not Permitted
L12F012
Fig. 6 -- Air for Combustion, Ventilation, and Dilution for
Outdoors
L12F013
Fig. 7 -- Air for Combustion, Ventilation, and Dilution from
Indoors