37
SETUP
SWITCH
SWITCH NAME
NORMAL
POSITION
DESCRIPTION OF USE
SW1-1
Status Code Recovery
OFF
Turn ON to retrieve up to 7 stored status codes for troubleshooting
assistance when R thermostat lead is disconnected.
SW1-2
Low Heat Only
(Adaptive Heat Mode
when SW1-2 is OFF)
OFF
When SW1-2 is OFF allows two-stage operation with a single stage
thermostat. Turn ON when using two- stage thermostat to allow
Low Heat operation when R to W/W1 closes and High Heat
operation when R to W/W1 and W2 close.
SW1-3
Low Heat Rise
Adjustment
OFF
Turn ON to increase Low Heat airflow by 18 percent. This
compensates for increased return air temperature caused with
bypass humidifier.
SW1-4
Comfort/Efficiency
Adjustment
ON
Turn ON to decrease low heat airflow by approximately 7 percent
and high heat by approximately 10 percent for maximum comfort
SW1-5
CFM per ton adjust
OFF
Turn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton. See
also SW2.
SW1-6
Component Self Test
OFF
Turn ON to initiate Component Self Test for troubleshooting
assistance when R thermostat lead is disconnected. Turn OFF
when Self Test is completed.
SW1-7 & SW1-
8
Blower OFF delay
ON or OFF
Blower Off Delay time – adjustable 90 seconds to 180 seconds.
See table in Adjustments section or refer to unit wiring diagram.
SW2-1
Twinning
OFF
Allows for selection of furnace Main (OFF) or Secondary (ON) when
Twinned furnace setup is required. See kit instructions for further
directions on installation and setup.
Allows additional CFM per ton selections when used with SW 1-5
325 CFM per ton (nominal) when SW 2-2 ON and SW 1-5 OFF
350 CFM per ton (nominal) when SW 2-2 OFF and SW 1-5 OFF
370 CFM per ton (nominal) when SW2-2 ON and SW 1-5 ON
400 CFM per ton (nominal) when SW 2-2 OFF and SW 1-5 ON
See Air Delivery Tables for model specific CFM vs. static pressure
SW 2-6, 7, 8
AC (Cooling Airflow)
OFF
The AC setup switches select desired cooling or high stage cooling
(two stage units) airflow. See Cooling Air Delivery Tables for
specific switch settings.
The CF setup switches select desired Continuous Fan Airflow
The CF switch position is the low cooling airflow selection for two
stage cooling units.
The CFM values are shown in the Air Delivery Tables below for
SW 2 settings. SW 2-3, 4, 5 cannot be set for airflow higher than
SW 2-6, 7, 8. See Continuous Fan Air Flow Table for specific
switch settings.
CF (Continuous Fan)
Furnace Setup Switch Description
OFF
OFF
SW 2-3, 4, 5
SW2-2
CFM per ton Adjust
A14312
Fig. 52 -- Furnace Setup Switch Description
MODEL SIZE
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
SW2
A/C (8 7 6)
CF (5 4 3)
045-12 / 036045
DEF
525
2
700 875 1050
1
1150 1150 1175
070-16 / 048070
DEF
525
2
700 875 1050
1225
1400
1
1685
090-16 / 048090
DEF
525
2
700 875 1050
1225
1400
1
1750
*110-22 / 066110
DEF
700
2
875 1050 1225 1400 1750
1
1925
*135-22 / 066135
DEF
700
2
875 1050 1225 1400 1750
1
1925
1. Default A/C airflow when A/C switches (SW2-6, 7, 8) are in OFF position
2. Default continuous fan airflow when CF switches (SW2-3, 4, 5) are in OFF position
* Continuous fan (CF) airflow for 110 and 135 models is the same as 090-16 / 048090
NOTE: CF airflow will not be higher than the selected A/C airflow
A14313
Fig. 53 -- Airflow Selection (based on 350 CFM/TON) for A/C (SW2--6, 7, 8) and *CF (SW2--3, 4, 5)