Carrier 50ZPM Скачать руководство пользователя страница 18

Outdoor Coil, Indoor Coil, and Condensate Drain Pan - 

Inspect the condenser coil, evaporator coil, and 

condensate drain pan at least once each year. 
 

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling 

season. Remove all obstructions, including weeds and shrubs, which interfere with the airflow through the condenser 

coil.  

 
Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft 

brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent and 

water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, 

wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer 

and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base. 
 

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain 

by removing all foreign matter from the pan. Flush the pan and drain trough with clear water. Do not splash water on 

the insulation, motor, wiring, or air filter(s). If the drain trough is restricted, clear it with a “plumbers snake” or similar 

probe device. 

 

Outdoor Fan Adjustment 

 

 

 
 

 

 

 

 
 

 

 

 

1.  Shut off unit power supply and install lockout tag. 
2.  Remove outdoor-fan assembly (grille, motor, motor cover, and fan) by removing screws and flipping assembly 

onto unit top cover. 

3.  Inspect the fan blades for cracks or bends. 

4.  If fan needs to be removed, loosen the setscrew and slide the fan off the motor shaft. 

5.  When replacing fan blade, position blade as shown in Fig. 9. Tighten setscrews. 

 

 

 

 

 
 

 

 

 

 
 

 

 

 

Fig. 9 - Outdoor Fan Adjustment 

Electrical Controls and Wiring - 

Inspect and check the electrical controls and wiring annually. Be sure to turn off the 

electrical power to the unit. Remove access panel to locate all the electrical controls and wiring. Check all electrical 

connections for tightness. Tighten all screw connections. If any smoky or burned connections are noticed, disassemble 

the connection, clean all the parts re-strip the wire end and reassemble the connection properly and securely. 

Check to ensure no wires are touching refrigerant tubing or sharp sheet metal edges. Move and secure wires to isolate 
from tubing and sheet metal edges.  

50ZPM 

Model 

“A” 

36 

25mm (0.98”) 

48 

25mm (0.98”) 

60 

25mm (0.98”) 

CAUTION

 

UNIT OPERATION HAZARD

 

Failure to follow this caution may result in equipment damage to unit components. 

 

Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top 

of unit. 

Page 18

Содержание 50ZPM

Страница 1: ...hese units can be placed on the side of a building or can be placed on a roof without roof curbs Each unit is designed to occupy a minimal space Piping and drain connections are readily accessible The...

Страница 2: ...5 Connect Condensate Drain 9 Step 6 Install Electrical Connections 10 PRE START UP 12 START UP 13 Step 1 Check for Refrigerant Leaks 13 Step 2 Start Up Cooling and Make Adjustments 13 Step 3 Refriger...

Страница 3: ...NING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used...

Страница 4: ...systems Do not use R 22 service equipment or components on Puron refrigerant equipment WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could cause personal injury deat...

Страница 5: ...ded 3 1 24 x 36 x 1 Evaporator Fan and Motor Section Fan Quantity Fan Size Diam x L in 12 0 x 10 5 Fan Type Drive Type Motor Type Indoor Motor Factory Speed Setting Low Motor Quantity Maximum HP Maxim...

Страница 6: ...ct Opening Center of Gravity mm LBS KG A B C X Y Z 36 279 127 30 12 765 14 0 357 7 13 7 348 14 356 19 483 14 0 356 48 305 139 34 13 867 19 9 506 14 13 9 354 14 356 19 483 16 0 406 60 352 160 42 13 107...

Страница 7: ...IVING AND INSTALLATION Step 1 Check Equipment IDENTIFY UNIT The unit model number and serial number are printed on the unit informative plate Check this information against shipping papers INSPECT SHI...

Страница 8: ...runoff levels Do not use unit if it has been under water Step 4 Select and Install Ductwork The design and installation of the duct system must be in accordance with the standards of the NFPA for ins...

Страница 9: ...ur L brackets are factory installed Supply air duct Two L brackets 9 7 in x 15 5 in Return air duct Two L brackets 14 in x 20 in Fig 2 Factory Installed Duct Flanges Table 1 Minimum Airflow for Safe E...

Страница 10: ...d at a slope of at least 1 in 25 4 mm for every 10 ft 3 m of horizontal run Be sure to check the drain tube for leaks Prime trap at the beginning of the cooling season start up Allowable glues for con...

Страница 11: ...ads and unit power leads as shown in Fig 7 and Fig 8 Route thermostat wires through grommet providing a drip loop at the panel Connect low voltage leads to the thermostat as shown in Fig 8 The unit tr...

Страница 12: ...s have been removed Fig 8 Control Connections Caution FIRE EXPLOSION ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death and or property damage 1 Follow rec...

Страница 13: ...own when control setting is satisfied 4 When using an automatic changeover room thermostat place both SYSTEM and FAN switches in AUTO positions Observe that unit operates in Cooling mode when temperat...

Страница 14: ...e value Step 4 Indoor Airflow and Airflow Adjustments Table 2 shows wet coil air delivery for horizontal discharge units Table 3 and Table 4 show pressure drops NOTE Be sure that all supply and return...

Страница 15: ...1521 1479 1445 1398 1357 2 1729 1740 1702 1670 1626 1585 1548 1508 1467 1424 3 1955 1976 1936 1904 1855 1820 1787 1748 1704 1666 60 1 1773 1727 1671 1624 1571 1510 1437 1383 1336 1273 2 1844 1798 174...

Страница 16: ...qualified service personnel should perform maintenance and service procedures that require unit top removal Refer to the following top removal procedures 1 Unplug all three wires from the outdoor fan...

Страница 17: ...se and oil with a mild solvent 6 Reassemble a Slip the wheel back in the housing with the hub set screw parented in the correct direction b Install the filler panel c Reinsert the motor assembly in th...

Страница 18: ...s If the drain trough is restricted clear it with a plumbers snake or similar probe device Outdoor Fan Adjustment 1 Shut off unit power supply and install lockout tag 2 Remove outdoor fan assembly gr...

Страница 19: ...650 psig 4482 kPA Low Pressure Switch The low pressure switch is located in the suction line and protects against low evaporator coil pressure It opens at 54 psig 372 kPA To check switches 1 Turn off...

Страница 20: ...gerant components such as filter drier pressure switch metering device coil accumulator or reversing valve Synthetic Roof Precautionary Procedure 1 Cover extended roof working area with an impermeable...

Страница 21: ...36 48 4 5 1 3 1 4 8 5 67 1 1 3 1 4 1 FLA Full Load Amps RLA Rated Load Amps LRA Locked Rotor Amps APP Application power at rated power supply voltage MCA Minimum Circuit Amps MOCP Maximum Overcurrent...

Страница 22: ...TYPICAL WIRING SCHEMATIC 50ZPM 400V 50Hz Page 22...

Страница 23: ...3 3 41 5 0 43 6 1 45 7 2 47 8 3 49 9 4 51 11 53 12 55 13 57 14 8 4 4 43 6 1 45 7 2 47 8 3 49 9 4 51 11 53 12 55 13 57 14 59 15 10 5 6 45 7 2 47 8 3 49 9 4 51 11 53 12 55 13 57 14 59 15 61 16 12 6 7 47...

Страница 24: ...6 81 2378 38 35 33 30 27 354 103 98 93 88 83 2440 39 36 34 31 28 364 105 100 95 90 85 2509 40 38 35 32 29 374 107 102 97 92 87 2578 41 39 36 33 30 384 108 103 98 93 88 2647 42 40 37 34 31 394 110 105...

Страница 25: ...line filter driers with rated working pressures less than 600 psig Do not leave R 410A refrigerant suction line filter driers in line longer than 72 hours Do not install a suction line filter drier in...

Страница 26: ...e leak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Dirty drier filter Replace filter Dirty co...

Страница 27: ...unit installation is level Check fan wheel and propeller for location in housing orifice and setscrew tightness III START UP ELECTRICAL SUPPLY VOLTAGE ______________________________________ COMPRESSO...

Страница 28: ...to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version 50ZPM IOM 50HZ 01 Catalog Number 50ZPM IOM 50HZ 02 Effective Dat...

Отзывы: