Carrier 50ZP024 Скачать руководство пользователя страница 15

15

Table 2 – Dry Coil Air Delivery* Horizontal Discharge (Deduct 10% for 208 Volt Operation)

Unit

Motor

Speed

Air

Delivery

External Static Pressure (IN. W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

024

Low

Watts

288

285

282

279

274

268

261

-

-

Cfm

875

820

802

734

668

582

478

-

-

Med

Watts

390

383

378

369

360

350

340

-

-

Cfm

1131

1090

1038

978

917

830

721

-

-

High

Watts

528

520

510

495

480

460

450

-

-

Cfm

1391

1338

1285

1200

1115

1018

920

-

-

030

Low

Watts

288

285

282

279

274

268

261

-

-

Cfm

875

820

802

734

668

582

478

-

-

Med

Watts

390

383

378

369

360

350

340

-

-

Cfm

1131

1090

1038

978

917

830

721

-

-

High

Watts

528

520

510

495

480

460

450

-

-

Cfm

1891

1338

1285

1200

1115

1018

920

-

-

036

Low

Watts

450

435

420

400

380

335

326

311

-

Cfm

1231

1218

1204

1120

1008

950

863

751

-

Med

Watts

470

450

445

410

388

359

338

321

-

Cfm

1302

1264

1205

1163

1081

940

873

783

-

High

Watts

660

635

610

575

540

505

485

460

-

Cfm

1700

1660

1581

1450

1297

1190

1095

999

-

042

Low

Watts

478

458

440

411

378

350

327

317

-

Cfm

1303

1270

1224

1179

1126

1022

911

816

-

Med

Watts

481

468

450

438

404

370

338

320

735

Cfm

1310

1280

1241

1181

1110

1022

943

811

-

High

Watts

-

798

678

647

618

578

540

500

-

Cfm

-

1736

1688

1618

1510

1421

1309

1187

1060

048

Low

Watts

-

-

801

760

730

688

650

600

570

Cfm

-

-

1898

1841

1757

1682

1564

1429

1365

High

Watts

-

-

870

842

818

782

696

632

628

Cfm

-

-

2000

1903

1799

1718

1625

1446

1333

060† 2

Speed

Low

Watts

890

850

810

790

735

680

580

480

422

Cfm

1834

1820

1791

1762

1703

1640

1415

1159

950

Med

Watts

1040

1018

1000

950

890

835

790

650

580

Cfm

2230

2102

2025

1960

1901

1855

1752

1468

1121

High

Watts

1073

1038

1001

958

896

840

800

691

575

Cfm

2230

2202

2160

2122

2052

1926

1791

1588

1202

060 3

Speed

Low

Watts

1058

1008

942

891

860

828

750

700

630

Cfm

2384

2200

2197

2071

1989

1889

1820

1729

1640

Med

Watts

1266

1086

1021

1002

977

924

860

819

700

Cfm

2724

2476

2392

2344

2262

2132

2001

1910

1820

High

Watts

1301

1216

1197

1127

1058

1011

979

869

870

Cfm

2760

2618

2543

2423

2292

2169

2056

1943

1832

* Air delivery values are based on operating voltage of 230 v dry coil, without filter. Deduct wet coil, filter pressure drops to obtain external static pressure avail-

able for ducting.

See Tables 3---NO TAG.

NOTES:

1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at

airflows below this point.

2. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.

Table 3 – Wet Coil Pressure Drop

UNIT SIZE 50ZP

AIRFLOW (CFM)

PRESSURE DROP (IN. W.C.)

024

600

0.02

700

0.05

800

0.06

900

0.07

030

900

0.06

1000

0.06

1200

0.08

036

1000

0.07

1200

0.09

1400

0.11

1600

0.12

042

1000

0.04

1200

0.06

1400

0.08

1600

0.09

048

1400

0.07

1600

0.08

1800

0.09

060

1700

0.07

1800

0.08

2100

0.09

2300

0.10

Table 4 – Filter Pressure Drop (IN. W.C.)

UNIT SIZE 50ZP

FILTER SIZE IN. (mm)

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

024-042

24 x 24

(610 x 610)

0.06

0.07

0.08

0.08

0.09

0.09

0.09

0.10

0.11

0.12

048, 060

24 x 30

(610 x 762)

-

-

-

-

-

-

-

-

0.08

0.09

UNIT SIZE 50ZP

FILTER SIZE IN. (mm)

CFM

1500

1600

1700

1800

1900

2000

2100

2200

2300

024-042

24 x 24

(610 x 610)

0.14

0.15

-

-

-

-

-

-

-

048, 060

24 x 30

(610 x 762)

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.18

50Z

P

Содержание 50ZP024

Страница 1: ...gency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing C00001 Fig 1 50ZP Size 036...

Страница 2: ...E OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE W...

Страница 3: ...DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT...

Страница 4: ...T 0 DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 U...

Страница 5: ...the unit where water ice or snow from an overhang or roof will damage or flood the unit The unit may be installed on wood flooring or on Class A B or C roof covering materials Step 4 Place Unit Unit...

Страница 6: ...arge ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on the system turn off main power to unit and i...

Страница 7: ...ive 10x8 254 x 203 800 550 1000 3 Low 1 4 10x8 254 x 203 1000 550 1000 3 Med 1 4 10x8 254 x 203 1200 800 1050 3 Low 1 2 10x9 254 x 229 1400 800 1050 3 Med 1 2 10x9 254 x 229 1600 1000 1100 2 Low 3 4 1...

Страница 8: ...local electrical codes governing such wiring In Canada all electrical connections must be in accordance with CSA standard C22 1 Canadian Electrical Code Part 1 and applicable local codes Refer to uni...

Страница 9: ...rigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrige...

Страница 10: ...rging charts are different from the type normally used Charts are based on charging the units to the correct superheat for the various operating conditions Accurate pressure gage and temperature sensi...

Страница 11: ...46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00016 Fig 15 Cooling Charging Chart 50ZP030 Units OUTDOOR TEMP F C 115 46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00017 Fig 16 Cooling Charging Chart 5...

Страница 12: ...als of the thermostat On units with a compressor time delay relay there is a 5 minute 45 sec delay between compressor starts Energizing the compressor contactor supplies power to the compressor and th...

Страница 13: ...d result in personal injury or death Disconnect electrical power and install lockout tag to the unit before cleaning and lubricating the blower motor and wheel WARNING To clean the blower wheel 1 Acce...

Страница 14: ...proper operation If discrepancies are observed in operating cycle or if a suspected malfunction has occurred check each electrical component with the proper electrical instrumentation Refer to the un...

Страница 15: ...25 1960 1901 1855 1752 1468 1121 High Watts 1073 1038 1001 958 896 840 800 691 575 Cfm 2230 2202 2160 2122 2052 1926 1791 1588 1202 060 3 Speed Low Watts 1058 1008 942 891 860 828 750 700 630 Cfm 2384...

Страница 16: ...16 A10093 Fig 21 50ZP 208 230 1 Wiring Diagram 50ZP...

Страница 17: ...17 A10094 Fig 22 50ZP 208 230 3 Wiring Diagram 50ZP...

Страница 18: ...Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate re...

Страница 19: ...at unit installation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 __________ L2 L3 __________ L3 L1 __________ Compressor Am...

Страница 20: ...W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 02 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...