Fig. 11C—Accessory Electric Heater Wiring
A05209
Table 6—Electrical Data—50ZHA
UNIT SIZE
50ZHA
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
IFM
FLA
ELECTRIC HEAT
SINGLE POINT POWER SUPPLY
MIN
MAX
RLA
LRA
Nominal KW*
FLA
MCA
FUSE OR
CKT BKR
MOCP
024
208/230–1–60
187
253
10.9
54.0
0.9
4.1
—/—
3.8/5.0
7.5/10.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
26.0/30.0
18.6/18.6
41.2/44.7
63.8/70.7
51.1/56.1
25/25
45/50
—
50/50
—
—
60/70
—
030
208/230–1–60
187
253
13.5
72.5
0.9
4.1
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
21.8/21.8
44.4/47.9
57.0/73.9
89.5/100.0
54.3/59.3
30/30
50/50
—
—
60/60
—
—
70/70
90/100
—
036
208/230–1–60
187
253
17.5
88.0
1.5
6.0
—/—
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
29.4/29.4
52.0/55.4
74.5/81.5
97.1/107.5
61.9/66.9
35/35
60/60
—
—
—
—
—
80/80
100/100
70/70
042
208/230–1–60
187
253
19.4
104.0
1.5
6.0
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
31.7/31.7
54.3/57.8
76.9/83.8
99.4/109.9
122.0/135.9
63.2/69.2
40/40
—
—
—
—
—
—
60/70
80/90
100/110
110/150
70/80
048
208/230–1–60
187
253
24.7
116.0
1.5
7.7
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
40.0/40.0
62.6/66.1
85.1/92.1
107.7/118.1
130.3/144.2
72.5/77.5
50/50
—
—
—
—
—
—
80/80
100/100
110/125
125/125
90/90
060
208/230–1–60
187
253
28.0
118.0
3.0
7.7
—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
—/—
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
45.7/45.7
68.2/71.7
90.8/97.8
113.4/123.8
135.9/149.9
78.2/83.2
60/60
—
—
—
—
—
—
90/90
100/110
125/125
125/150
90/100
FLA
Full Load Amps
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
RLA
Rated Load Amps
NOTES:
1.
In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be Power Supply fuse. The CGA (Canadian Gas Association) units may be fuse or circuit breaker.
2.
Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC.
12