16
Motormaster III Control — Recommended mounting location
is beneath the control box, mounted to the partition that sepa-
rates the control box section from the indoor section.
NOTE: If unit power is supplied through the roof curb and
basepan of the unit, mount the Motormaster III control on the
corner post adjacent to the conduit running from the basepan to
the bottom of the control box.
CONDENSER HOOD — The condenser hood is available as
a factory-supplied, field-installed option or as a kit (part
no. CRODHOOD001A00).
Install the condenser hood:
1. Remove and save 4 screws attaching the hood to coil. See
Fig. 28.
2. Install brackets with top flange facing toward coil reusing
screws from Step 1. See Fig. 29 and 30.
3. Remove and save screws on the front and end of con-
denser. See Fig. 31.
4. Slide hood top flange under top cap. Reinstall screws in
top cap.
5. Slide angle baffle between brackets and hood.
6. Secure the hood by installing the 19 screws supplied with
instructions. See Fig. 32.
Be sure to support parts as screws are removed.
NOTE: Dimensions in (
) are in mm.
Fig. 25 — Wind Baffle Details
SENSOR
LOCATION
HAIRPIN END
50TJ016
NOTE: All sensors are located on the eighth hairpin up from the bottom.
Fig. 26 — Motormaster® III Sensor Locations —
50TJ016
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
50TJ024
50TJ028
NOTE: All sensors are located on the eighth hairpin up from the bottom.
Fig. 27 — Motormaster III Sensor Locations —
50TJ024 and 50TJ028