background image

Step 8—Install Electrical Connection

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC
(National Electrical Code) ANSI/NFPA (latest edition) and
local electrical codes. In Canada, follow Canadian Electrical
Code CSA (Canadian Standards Association) C22.1 and local
electrical codes.

INSTALLATION REQUIREMENTS
Failure to follow these precautions may result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC

ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.

2. Use only

copper

conductor for connections between

field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.

3. Be sure that high-voltage power to unit is within operating

voltage range indicated on unit rating plate.

4. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc.
Consult local power company for correction of improper
voltage.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-
supplied, waterproof, disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing. See Table 3 for electrical data.

The field-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
low-voltage entry points are used. See Fig. 2 & 3 for acceptable
location.

See unit wiring label and Fig. 10 for reference when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.

Single phase units:

1. Run the high-voltage (L1, L2) and ground leads into the

control box.

2. Connect ground lead to chassis ground connection.

3. Connect L1 to pressure lug connection 11 of the compressor

contactor.

4. Connect L2 to pressure lug connection 23 of the compressor

contactor.

SPECIAL PROCEDURES FOR 208-V OPERATION

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Make sure that the power supply to the unit is switched OFF
and lockout tag installed before making any wiring changes.

CONTROL VOLTAGE CONNECTIONS

NOTE:

Do not use any type of power-stealing thermostat. Unit

control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, insulated
(35 C minimum) wires to make the control voltage connections

Table 2—Minimum Airflow for Safe Electric Heater

Operation (Cfm)

SIZE

024

030

036

042

048

060

Cfm

800

1000

1200

1400

1600

1750

Fig. 9—Vertical Duct Cover Removed

C99012

DUCT COVERS REMOVED

9

Содержание 50SD

Страница 1: ...RING 16 REFRIGERANT CIRCUIT 16 EVAPORATOR AIRFLOW 17 METERING DEVICE ACCURATER 17 TROUBLESHOOTING 17 START UP CHECKLIST 17 NOTE TO INSTALLER Before the installation READ THESE INSTRUCTIONS CAREFULLY A...

Страница 2: ...esult in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 5A This is necessary for unit drain to function properly Refer to accessory roof curb installation instructio...

Страница 3: ...TS UNIT TOP 48 00 1219 2 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 304 8 12 00 FROM WALL SYSTEM THEN SYSTEM PERFORMANCE MAYBE COMPROMISE REQU...

Страница 4: ...230 1 60 460 209 46 98 1193 21 0 533 20 5 520 17 1 434 50SD048 208 230 1 60 480 218 46 98 1193 21 0 533 20 0 508 17 4 442 50SD060 208 230 1 60 492 223 46 98 1193 21 0 533 20 0 508 17 6 447 A05126 REQ...

Страница 5: ...6 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 CPRFCURB009A00 14 356 16 3 16 411 17 3 8 441 40 5 16 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 NOTES 1 Dimensions in are in millimeters 2 Roof curb is...

Страница 6: ...See Fig 7 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in tra...

Страница 7: ...mmer Push louver down to break rear and left side tabs Fig 8 9 4 If unit ductwork is to be attached to vertical opening flanges on the unit composite base jackstand applications only do so at this tim...

Страница 8: ...Contractors National Association SMACNA and Air Conditioning Contractors of America ACCA minimum installation standards for heating and air conditioning systems Secure all ducts to building structure...

Страница 9: ...correction of improper voltage HIGH VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Re...

Страница 10: ...0 28 5 28 5 28 5 31 2 50 3 57 2 72 8 83 3 95 4 109 3 37 6 42 6 35 35 35 35 60 60 40 45 80 90 100 110 060 208 230 1 60 187 253 25 0 148 0 1 5 6 2 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 5 4 7 2 18 1 20 8...

Страница 11: ...ake the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disconnected wires etc b Inspect for oil at all refrigerant tubing connections and on unit ba...

Страница 12: ...Fig 12 Wiring Diagram 208 230 60 1 A05112 12...

Страница 13: ...rvice fitting c Suction low side pressure psig 5 Using Cooling Charging Charts compare outdoor air tem perature F db with the suction line pressure psig to determine desired system operating suction l...

Страница 14: ...son To troubleshoot heating or cooling of units refer to tables at the back of the book NOTE TO EQUIPMENT OWNER Consult your local dealer about the availability of a maintenance contract FIRE EXPLOSIO...

Страница 15: ...crews that secure motor mount brackets to hous ing and slide motor and motor mount out of housing 2 Remove and clean blower wheel as follows a Ensure proper reassembly by marking wheel orientation b L...

Страница 16: ...8 1457 1362 1271 High Watts 798 772 738 700 Cfm 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 Cfm 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 639 607...

Страница 17: ...s publication as an aid in determining proper control operation REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base for oil accumulations annually Detecting oil generally...

Страница 18: ...tion in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set to...

Страница 19: ...lation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 C S __________ Compressor Amps L1 C __________ Indoor Evaporator Fan Amp...

Страница 20: ...ianapolis IN 46231 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 6 Tab 6 8 PC 101 Printed in U...

Отзывы: