
54
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
LEGEND
SCREEN NAME
POINT NAME
PASSWORD
LEVEL
EDITABLE
RANGE
DEFAULT
NOTES
Configuration
Service
Configuration
# of Fan Speeds
Admin Password
level access only
X
1,2,3
3
Used to set number of
fan motor speeds
G Output Type
X
Fan On/Fan Low
Fan On
When set to Fan On, G output is
energized when ever any fan speed
is active (re
q
uired for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Low Speed
Compressor Stages
X
One Stage/Two Stages
One Stage
Defines the number of
stages of compression
Reversing Valve Type
X
O type output/B type output
O type
Determines reversing valve
signal output type
Leaving Air Auxiliary
Heat Type
X
None/2-Position HW/1 Stage
Electric/Modulating HW
None
Determines Auxiliary
Reheat Coil Type
Entering Air Water
Economizer Type
X
None/2-Position/Modulating
None
Determines Entering Air
Economizer Coil Type
2-Position Water
Valve Type
X
Normally Closed/Normally Open
Normally
Closed
Determines type of 2-position
water valve used
Modulating Water
Valve Type
X
Normally Closed/Normally Open
Normally
Closed
Determines type of modulating
water valve used
Ventilation Damper
Type
X
None/2-Position/DCV
None
Determines Type of ventilation
damper control to be used
Damper Actuator Type
X
(0-10 volt)/(2-10 volt)
0-10 volt
Used to determine ventilation
damper output signal range
(closed - open)
Humidity Sensor
X
None/Installed
None
Set to Installed if Humidity
sensor is present
Factory Dehumidifica-
tion Reheat Coil
X
None/Installed
None
Set to Installed if factory-installed
dehumidification reheat coil
is present
Occupancy
Input Logic
X
Occupied Open/Occupied Closed
Occupied
CLOSED
Used to determine external occu-
pancy switch contact occupied state
Condensate Switch
Alarm Delay
X
5 - 600 seconds
10 sec
Delay before e
q
uipment alarms on
high condensate level
Condensate Switch
Alarm State
X
Alarm OPEN/Alarm CLOSED
Alarm
CLOSED
Determine Alarm state of
condensate switch input
Minimum Condenser
Water Temperature in
Heating
X
25 - 60
F
60
F
Determines the minimum
acceptable water loop temperature
to start heating
Maximum Condenser
Water Temperature in
Heating
X
65 - 100 F
90 F
Determines the maximum
acceptable water loop temperature
to start heating
Minimum Condenser
Water Temperature in
Cooling
X
30 - 60
F
60
F
Determines the minimum
acceptable water loop temperature
to start cooling
Maximum Condenser
Water Temperature in
Cooling
X
85 - 120 F
95 F
Determines the maximum
acceptable water loop temperature
to start cooling
IAQ sensor
minimum input
X
0 - 5 ma
4 ma
Minimum output current (mA)
for IAQ sensor
IAQ sensor
maximum input
X
5 - 20 ma
20 ma
Maximum output current (mA) for
IAQ sensor
IAQ sensor
minimum output
X
0 - 9999 ppm
0 ppm
Corresponding value in ppm for
minimum output current
IAQ sensor
maximum output
X
0 - 9999 ppm
2000 ppm
Corresponding value in ppm for
maximum output current
→
°
°
°
°
°
°
°
°
BAS —
Building Automation System
DCV —
Demand Controlled Ventilation
IAQ
—
Indoor Air Quality
OAT
—
Outdoor Air Temperature
RH
—
Relative Humidity
SAT
—
Supply Air Temperature
SPT
—
Space Temperature
TPI
—
Third Party Integration