21
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW
will vary accordingly.
See Legend and Notes on page 22
Electrical Data
UNIT
SIZE
50JX
V-PH-Hz
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
IFM
FLA
ELECTRIC HEAT
SINGLE POINT POWER SUPPLY
Min
Max
RLA
LRA
Nominal kW*
FLA
MCA
Fuse or
Ckt Bkr
MOCP
024
208/230-1-60
187
253
10.8
56
0.90
2.0
—/—
3.8/5.0
5.4/7.2
7.5/10.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
16.4/16.4
39.0/42.4
48.9/53.9
61.5/68.5
20/20
40/45
60/60
—
—
—
—
70/70
030
208/230-1-60
187
253
14.0
73
0.9
2.1
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
20.5/20.5
43.1/46.5
53.0/58.0
65.6/72.6
88.2/98.6
25/25
45/50
—
—
—
—
—
70/70
70/80
90/100
208/230-3-60
187
253
10.4
63
0.9
2.1
—/—
3.8/5.0
7.5/10.0
11.3/15.0
—/—
10.4/12.0
20.8/24.1
31.3/36.1
16.0/16.0
29.0/31.0
42.1/46.1
55.1/61.1
20/20
35/35
45/50
—
—
—
—
60/70
036
208/230-1-60
187
253
16.7
97
1.6
3.6
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
26.1/26.1
48.6/52.1
58.6/63.6
71.2/78.2
93.8/104.2
35/35
50/60
—
—
—
—
—
70/80
80/80
100/110
208/230-3-60
187
253
11.2
75
1.6
3.6
—/—
3.8/5.0
7.5/10.0
11.3/15.0
—/—
10.4/12.0
36.1/41.7
31.3/36.1
19.2/19.2
32.2/34.2
45.2/49.3
58.3/64.3
25/25
35/35
50/50
—
—
—
—
60/70
460-3-60
414
506
5.4
37.5
0.9
1.9
—/—
5
10
15
—/—
6
12
18
9.6
17.1
24.6
32.1
15
20
25
35
—
—
—
—
042
208/230-1-60
187
253
18.4
104
0.9
4.1
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
28.0/28.0
50.6/54.0
60.5/65.5
73.1/80.1
95.7/106.1
118.3/132.2
35/35
60/60
—
—
—
—
—
—
80/90
80/90
100/110
125/150
208/230-3-60
187
253
12.4
88
0.9
4.1
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
—/—
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
20.5/20.5
33.5/35.5
46.6/50.6
59.6/65.6
72.5/80.5
25/25
40/40
50/60
—
—
—
—
—
60/70
80/90
460-3-60
414
506
5.8
44
0.9
2.0
—/—
5
10
15
20
—/—
6
12
18
24.1
10.2
17.7
25.2
32.7
40.2
15
20
30
35
45
—
—
—
—
—
048
208/230-1-60
187
253
23.4
126
1.6
4.1
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.0
34.9/34.9
57.4/60.9
67.3/72.4
80.0/86.9
102.5/113.0
125.1/139.0
45/45
—
—
—
—
—
—
70/70
90/90
90/90
110/125
150/150
208/230-3-60
187
253
13.0
93
1.6
4.1
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
—/—
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
21.9/21.9
34.9/36.9
47.9/51.9
60.9/67.0
73.8/81.8
30/30
40/40
50/60
—
—
—
—
—
70/70
80/90
460-3-60
414
506
6.4
46.5
0.9
2.0
—/—
5
10
15
20
—/—
6
12
18
24.1
10.8
18.3
25.8
33.3
40.8
15
20
30
35
45
—
—
—
—
—
060
208/230-1-60
187
253
28.8
169
1.4
6.2
—/—
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
—/—
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
43.6/43.6
66.2/69.6
76.1/181.1
88.7/95.7
111.3/121.7
133.9/147.8
60/60
—
—
—
—
—
—
70/80
100/110
100/100
125/125
150/150
208/230-3-60
187
253
17.3
123
1.4
6.2
—/—
3.8/5.0
7.5/10.0
11.3/15.0
15.0/19.9
—/—
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
29.2/29.2
42.3/44.3
55.2/59.4
68.3/74.3
81.2/89.2
35/35
50/50
60/60
—
—
—
—
—
70/80
90/90
460-3-60
414
506
9.0
62
0.9
3.2
—/—
5
10
15
20
—/—
6
12
18
24.1
15.4
22.9
30.4
37.9
45.4
20
25
35
40
50
—
—
—
—
—
Содержание 50JX Series
Страница 19: ...19 INDOOR THERMOSTAT DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER Typical piping and wiring ...
Страница 23: ...23 Typical wiring schematic 208 230 1 60 shown ...
Страница 24: ...24 Typical wiring schematic 208 230 3 60 shown ...
Страница 25: ...25 Typical wiring schematic 460 3 60 shown ...