ARI* capacities (cont)
OUTDOOR SOUND: ONE-THIRD OCTAVE BAND DATA — DECIBELS
FREQ.
Hz
UNIT 50HX
024
030
036
042
048
060
63
49.0
52.8
49.2
50.0
53.2
54.3
125
60.7
59.2
62.3
64.7
65.4
65.1
250
68.1
71.9
69.1
70.4
74.5
71.5
500
69.3
69.7
70.9
69.9
74.3
72.7
1000
70.6
70.4
74.7
75.3
75.2
73.9
2000
68.8
68.8
69.3
73.8
72.6
73.4
4000
65.2
65.2
65.2
75.1
68.6
71.7
8000
59.4
57.1
58.3
69.2
61.2
66.3
Physical data
UNIT 50HX
024
030
036
042
048
060
REFRIGERANT
R-22
Refrigerant Control*
Acutrol™ System
SHIPPING WEIGHT (lb)
Without Base Rail
309
340
368
368
411
425
With Optional Base Rail
296
327
355
355
398
412
COMPRESSOR Type
Scroll
INDOOR FAN
Centrifugal — Direct Drive
Speeds
3
3
3
3
Variable
Variable
Rpm (High Speed)
1075
1075
1100
1100
—
—
Diameter
10
10
10
10
10
10
Width (in.)
9
9
9
9
10
10
Nominal Airflow (Cfm)
800
1000
1300
1400
1600
1800
Motor Hp
1
⁄
4
1
⁄
4
1
⁄
2
1
⁄
2
1.0
1.0
INDOOR COIL
Rows...Fins/in.
3...15
3...15
4...15
4...15
4...15
4...15
Face Area (sq ft)
3.6
3.6
4.5
4.5
4.5
4.5
OUTDOOR FAN
Propeller — Direct Drive
Cfm
2200
2200
2200
2400
2400
2400
Rpm
1100
1100
1100
1100
1100
1100
Diameter (in.)
20
20
20
20
20
20
Motor Hp
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
3
1
⁄
3
OUTDOOR COIL
Rows...Fins/in.
2...17
2...17
2...17
2...17
2...17
2...17
Face Area (sq ft)
7.00
7.00
8.66
8.66
8.66
8.66
FILTER SIZE (in.)†
Throwaway
24 x 24
24 x 24
24 x 30
24 x 30
24 x 30
24 x 30
*Operating charge listed on unit nameplate.
†Recommended field-supplied filters are 1-in. thick.
NOTE: Sizes 048 and 060 are equipped with an indoor integrated control motor (ICM).