Table 18 — Fan Performance 50HJQ007 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils.
See Table 8 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2615. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Tables 6
and 7 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
906
0.62
700
1002
0.78
771
1084
0.93
891
1163
1.10
1081
1235
1.29
1190
1900
945
0.72
779
1037
0.88
843
1119
1.04
1006
1194
1.21
1158
1266
1.40
1310
2000
984
0.82
867
1072
0.98
924
1154
1.16
1106
1226
1.33
1258
1297
1.63
1353
2100
1024
0.93
998
1108
1.10
1056
1190
1.29
1207
1259
1.47
1361
1327
1.66
1473
2200
1064
1.05
1081
1145
1.22
1148
1225
1.43
1353
1294
1.62
1447
1359
1.81
1595
2300
1104
1.18
1140
1183
1.36
1233
1260
1.57
1499
1330
1.78
1526
1392
1.97
1709
2400
1145
1.32
1224
1222
1.52
1378
1296
1.73
1604
1365
1.94
1683
1426
2.15
1892
2500
1186
1.48
1335
1262
1.68
1517
1331
1.89
1718
1400
2.12
1910
1461
2.34
2076
2600
1228
1.66
1482
1301
1.86
1604
1367
2.07
1823
1435
2.31
2136
1497
2.54
2283
2700
1269
1.83
1595
1341
2.05
1691
1404
2.26
1936
1471
2.51
2326
1532
2.75
2504
2800
1311
2.03
1639
1381
2.25
1840
1442
2.47
2145
1506
2.72
2512
1603
3.28
3290
2900
1354
2.24
1814
1420
2.47
1989
1481
2.69
2335
1542
2.94
3262
—
—
—
3000
1396
2.46
2032
1460
2.69
2223
1521
2.93
2444
1649
3.73
3360
—
—
—
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1303
1.48
1301
1371
1.69
1387
1433
1.90
1517
1481
2.10
1761
1525
2.29
1967
1900
1330
1.59
1404
1396
1.81
1499
1460
2.03
1613
1509
2.24
1874
1554
2.45
2093
2000
1362
1.73
1482
1422
1.94
1613
1485
2.16
1744
1535
2.38
2029
1581
2.61
2266
2100
1393
1.87
1595
1452
2.08
1761
1510
2.31
1910
1561
2.65
2224
1607
2.79
2485
2200
1423
2.02
1726
1483
2.24
1919
1538
2.46
2093
1590
2.72
2441
1637
2.97
2645
2300
1454
2.18
1884
1515
2.41
2076
1569
2.64
2272
1622
2.91
2616
1670
3.18
2832
2400
1485
2.36
2015
1544
2.59
2249
1601
2.84
2467
1655
3.14
2823
1704
3.43
3055
2500
1518
2.55
2232
1575
2.78
2405
1635
3.11
2848
1690
3.43
3089
1740
3.75
3340
2600
1552
2.76
2436
1620
3.14
2964
1662
3.51
3215
1739
3.88
3488
1791
4.24
3776
2700
1612
3.21
3141
1683
3.65
3445
1747
4.08
3737
—
—
—
—
—
—
2800
1687
3.82
3738
1761
4.36
4115
—
—
—
—
—
—
—
—
—
2900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP
—
Factory-Installed Option
Watts —
Input Watts to Motor
Содержание 50HJQ004-007
Страница 42: ...42 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown ...
Страница 43: ...43 Fig 43 Typical Wiring Schematic 50HJQ006 007 Shown cont ...
Страница 45: ......
Страница 47: ......