17
5. Remove two slot fillers in the bottom of the cover to per-
mit service tool cords to exit the cover.
6. Check for full closing and latching.
Fig. 23 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose
125v 15A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting wire
size, fuse or breaker requirements, and disconnect switch size
and location. Route 125v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to step down
the main power supply voltage to the unit to 115v at the duplex
receptacle. This option also includes a manual switch with
fuse, located in a utility box and mounted on a bracket behind
the convenience outlet; access is through the unit’s control box
access panel. See Fig. 22.
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is a
customer option. If local codes permit, the transformer primary
leads can be connected at the line-side terminals on the unit-
mounted non-fused disconnect switch; this will provide service
power to the unit when the unit disconnect switch is open. Oth-
er connection methods will result in the convenience outlet cir-
cuit being de-energized when the unit disconnect switch is
open. See Fig. 24.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often
require that two disconnects be opened to de-energize all pow-
er to the unit. Treat all units as electrically energized until the
convenience outlet power is also checked and de-energization
is confirmed. Observe National Electrical Code Article 210,
Branch Circuits, for use of convenience outlets.
Fuse On Power Type
The factory fuse is a Bussman “Fusetron”
1
T-15, non-renew-
able screw-in (Edison base) type plug fuse.
Fig. 24 — Powered Convenience Outlet Wiring
Duty Cycle
The unit-powered convenience outlet has a duty cycle limita-
tion. The transformer is intended to provide power on an inter-
mittent basis for service tools, lamps, etc; it is not intended to
provide 15-amps loading for continuous duty loads (such as
electric heaters for overnight use). Observe a 50% limit on cir-
cuit loading above 8 amps. Convenience outlet usage rating:
• Continuous usage: 8 amps maximum
• Intermittent usage: Up to 15 amps maximum for up to 2
hours maximum
See Fig. 25.
Test the GFCI receptacle by pressing the TEST button on the
face of the receptacle to trip and open the receptacle. Check for
proper grounding wires and power line phasing if the GFCI re-
ceptacle does not trip as required. Press the RESET button to
clear the tripped condition.
Fig. 25 — Convenience Outlet Utilization
Notice Label
1. Bussman and Fusetron are trademarks of Cooper Technologies
Company.
COVER - WHILE-IN-U
S
E
WEATHERPROOF
BA
S
EPLATE FOR
GFCI RECEPTACLE
GA
S
KET
GFCI RECEPTACLE
NOT INCLUDED
TOP
TO
P
TOP
WET LOC
ATIONS
W
ET
L
OC
ATI
ON
S
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230
240
L1: RED + YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460
480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575
600
L1: RED
L2: GRA
H1
H2
Содержание 50HCQ07
Страница 4: ...4 Fig 2 Unit Dimensional Drawing 07 08 Size Units ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing 07 08 Size Units cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing 09 Size Units ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing 09 Size Units cont ...
Страница 24: ...24 Fig 37 Electro Mechanical Control Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Страница 25: ...25 Fig 38 Electro Mechanical Control Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Страница 26: ...26 Fig 39 Electro Mechanical Control Wiring 50HCQ 08 09 208 230v 460v 575v ...
Страница 27: ...27 Fig 40 Electro Mechanical Power Wiring 50HCQ A07 D07 208 230v 460v 575v ...
Страница 28: ...28 Fig 41 Electro Mechanical Power Wiring 50HCQ D07 Tier 2 1 Compressor 208 230v 460v 575v ...
Страница 29: ...29 Fig 42 Electro Mechanical Power Wiring 50HCQ 08 09 208 230v 460v 575v ...
Страница 30: ...30 Fig 43 PremierLink Wiring Schematic 50HCQ07 09 208 230v 460v 575v ...
Страница 31: ...31 Fig 44 RTU Open System Control Wiring ...
Страница 46: ...46 Fig 52 Completing Installation of Return Air Smoke Sensor Fig 53 EconoMi er IV Wiring STEP 1 STEP 2 STEP 3 ...
Страница 49: ......