19
connector allows the high-voltage power wires to pass through the
basepan. See Fig. 33 and 34.
Fig. 32 — Thru-the-Base Fitting Assembly (Shown in
Shipping Position)
Fig. 33 — Thru-Base Connection Fittings (Units Built
Prior to 4/15/2019)
Fig. 34 — Thru-Base Connection Fittings (Units Built
On and After 4/15/2019)
1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L” bracket
and discard the “L” bracket, but retain the washer head
screws and the gasket (located between the “L” bracket
and the connector plate assembly).
NOTE: Take care not to damage the gasket, as it is reused in the
following step.
3. Place the gasket over the embossed area in the basepan,
aligning the holes in the gasket to the holes in the basepan.
See Fig. 32.
4. Install the connector plate assembly to the basepan using 8
of the washer head screws.
NOTE: If electrical connections are not going to occur at this time,
tape or otherwise cover the fittings so that moisture does not get
into the building or conduit in the interim.
Check tightness of connector lock nuts before connecting electri-
cal conduits.
Field-supplied and field-installed liquid-tight conduit connectors
and conduit may be attached to the connectors on the basepan.
Pull correctly rated high voltage and low voltage through
appropriate conduits. Connect the power conduit to the internal
disconnect (if unit is so equipped) or to the external disconnect
(through unit side panel). Remove one of the two knockouts
located on the bottom left side of the unit control box. Use this
hole for the control conduit.
UNITS WITHOUT THRU-BASE CONNECTIONS (ELEC-
TRICAL CONNECTIONS)
1. Install power wiring conduit through side panel openings.
Install conduit between disconnect and control box.
2. Install power lines to terminal connections as shown in
Fig. 22 on page 15.
Voltage to compressor terminals during operation must be within
voltage range indicated on unit nameplate. On 3-phase units,
voltages between phases must be balanced within 2% and the cur-
rent within 10%. Use the formula shown in the example below to
determine the percent of voltage imbalance. Operation on improp-
er line voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation
would invalidate any applicable Carrier warranty.
Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
LOW VOLTAGE
CONDUIT
CONNECTOR
HIGH VOLTAGE
CONDUIT
CONNECTOR
AUXILIARY
POWER SUPPLY
(OPTIONAL)
% Voltage
Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage
=
(224 + 231 + 226)
=
681
=
227
3
3
% Voltage Imbalance = 100x
4
= 1.78%
227
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
A
B
C
MOTOR
Содержание 50HC Series
Страница 4: ...4 Fig 2 50HC 04 06 Units Built On and After 4 15 2019...
Страница 5: ...5 Fig 3 50HC 04 06 Units Built Prior to 4 15 2019...
Страница 6: ...6 Fig 4 50HC 04 06 Corner Weights and Clearances...
Страница 7: ...7 Fig 5 50HC 04 06 Base Rail Details...
Страница 8: ...8 Fig 6 50HC 04 06 Thru the Base Charts...
Страница 25: ...25 Fig 47 Electro Mechanical Control Wiring Diagram...
Страница 26: ...26 Fig 48 Electro Mechanical Control Wiring Diagram with Humidi MiZer System...
Страница 27: ...27 Fig 49 Electro Mechanical Control Power Wiring Diagram...
Страница 29: ...29 Fig 51 50HC ComfortLink Control with Humidistat Power Wiring Diagram 208 230V 460V 575V 3 Phase...
Страница 30: ...30 Fig 52 50HC ComfortLink Control with Humidi MiZer System Power Wiring Diagram 208 230V 460V 575V 3 Phase...
Страница 31: ...31 Fig 53 PremierLink Wiring Schematic...
Страница 32: ...32 Fig 54 PremierLink Wiring Schematic with Humidi MiZer System...
Страница 33: ...33 Fig 55 RTU Open System Control Wiring Diagram...
Страница 34: ...34 Fig 56 RTU Open System Control Wiring Diagram with Humidi MiZer System...
Страница 49: ......