91
ENERGYX
CONTROL BOARD (EXCB)
See Fig. 44 and Table 35.
The EXCB continuously monitors input/output channel informa-
tion received from its inputs and from the Universal Protocol
Converter (UPC). The EXCB receives inputs from transducers
and discrete inputs. See Options and Accessories section. The
EXCB has relay analog outputs, and is equipped with a LCD
screen. The EXCB communicates with a Modbus protocol and is
not a CCN device. The EXCB has a reset button that is used to
force all the outputs and reset communication.
NOTE: There are hardware jumpers set throughout the board. Do
not change these jumpers.
Fig. 44 — EnergyX Control Board (EXCB)
Table 35 — EXCB Input/Output Connections
POINT DESCRIPTION
SENSOR LOCATION
Input/Output
TYPE OF Input/Output
CONNECTION PIN NUMBER
Download
N/A
Both
Communication
J1
LCD
Low voltage control box
Both
Communication
J2
Power from TRANS
Control box
Input
24VAC
J3, 1-2
Power to Relays
Low voltage control box
Output
24VAC
J4, 1
Power to UPC
Low voltage control box
Output
24VDC
J4, 3-4
Wheel Rotation Sensor
Attached to scoop
Input
Switch
J5, 2-4
Frost Switch
Attached to scoop
Input
Switch
J6, 3-4
Filter Status Switch
Attached to scoop and in Exhaust
air section
Input
Switch
J7, 3-4
Motor Status Switches
Integrated in motors
Input
Switch
J8, 3-4
Leaving Air Temp
Scoop section
Input
10K
J15, 1-2
Exhaust Air Temp
Exhaust air section
Input
10K
J16, 1-2
Wheel Relay
High voltage control box
Output
Relay
J17, 4
2-position Exhaust damper
relay
Exhaust damper assembly
Output
Relay
J19, 4
OA fan speed signal
N/A
Output
2-10vdc
J21, 1-3
OA Modulating Damper
Intake damper assembly
Output
2-10vdc
J21, 1-4
EX fan speed signal
N/A
Output
2-10dvc
J22, 1-3
Modbus to UPC
Control box
Both
Communication
J23, 1-3
Outside Air pressure
Transducer
Low voltage control box
Input
Digital 0-5vdc
J24
Exhaust Air pressure
Transducer
Low voltage control box
Input
Digital 0-5vdc
J25
Building Pressure Sensor
Low voltage control box
Input
4-20mA
J10, 1-6
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......