Carrier 50HB Скачать руководство пользователя страница 15

15

Horizontal package air conditionners

Possible problems at commissioning

All indications given in this brochure must be respected and 
complied with to guarantee a correct operation of the units.

Next, several possible operation problems are stated which could 
happen if the conditions of the commissioning are not appropriate.

- Air 

 ow lack: very high differences between inlet and outlet, originated 

by a high pressure drop in the ducts, or by other causes that impede 
the correct air circulation.

-  Air recirculation in the unit, originated by some obstacle in the air 

aspiration or outlet.

-  Noise problems because of excessive air 

 ow in the grille.

-  Water over

 owing to the pan problems, originated by an excessive 

 ow, an incorrect siphon installation or because a defective unit level.

-  Refrigerant circuit humidity problem, because of an incorrect vacuum 

realization.

-  If the refrigerant load is lower than required, the suction pressure 

will be rather lower than normal, and overheating when suctioning 
from the compressors will be high. This can cause an interruption 
in operation due to activation of the refrigerant load safety device.

  To adjust the refrigerant load, 

a schrader valve is built into 
the unit on the liquid line, 
located inside the compressor 
enclosure.

-  When commissioning the compressors, check 

the subcooling and overheating and thus verify 
if the refrigerant load is appropriate to the 
operating conditions.

R 410A

Control of the refrigerant load

-  Check the unit operation and verify the safety devices.

-  Verify the absence of any leaks of the refrigerant. In case of a leak:

•  Completely empty the unit using a specifi

 c recovery unit for R-410A 

and repair the leak. 

•  Next, reload the gas into the unit according to load data provided 

in the technical characteristics table and in the unit’s data plate.

•  Add the refrigerant via the schrader valve of the liquid line using 

the appropriate equipment and tools, with the compressor stopped, 
monitoring the pressures to control any anomaly.

High-pressure schrader valve 

(optional pressure gauge 

connection)

Low-pressure schrader valve 

(optional pressure gauge 

connection)

Schrader valve for 

refrigerant load

Check the unit operation by verifying the electronic control and the 
safety devices.
It is also recommendable to create a report, taking note of the date, 
which includes the following information: 
-  the nominal voltage, 
-  current absorbed by the compressors, fans and other electrical 

components,

- signi

 cant temperatures in the cooling circuit (see attached table), 

-  other aspects considered interesting such as alarms detected by the 

electronic control of the unit. 

The recording of these parameters whilst the unit is running allows 
controlling the installation performance and it is the best possible way 
to avoid breakdowns since the analysis of these data makes early 
detection of anomalies possible or the provision of the necessary means 
available to ensure that they do not take place.

Operational checks

Cooling MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air
condenser

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Air
evaporator

Air inlet temperature

ºC

Air outlet temperature

ºC

Liquid inlet temperature

ºC

Evaporation outlet temperature (4) ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Heating MODE

Compressor

Suction pressure

bar

Suction temperature (1)

ºC

Condensation pressure

bar

Condensation temperature (2)

ºC

Air
evaporator

Liquid inlet temperature

ºC

Gas outlet temperature (4)

ºC

Air inlet temperature

ºC

Outdoor temperature

ºC

Air outlet temperature

ºC

Air
condenser

Air inlet temperature

ºC

Air outlet temperature

ºC

Gas inlet temperature

ºC

Liquid outlet temperature (3)

ºC

Subcooling (2) - (3)

ºC

Overheating (4) - (1)

ºC

Содержание 50HB

Страница 1: ...PERATION AND MAINTENANCE INSTRUCTIONS 50HB HF Nominal cooling capacity 12 5 35 9 kW Nominal heating capacity 14 2 41 0 kW 50 Hz Horizontal package air conditionners Translation of the original document 80053 09 2016 ...

Страница 2: ...ations 7 8 Checking before commissioning 8 Electrical Connections 8 Checks at centrifugal fans 9 Interchangeable position of air supply 0 Interchangeable position of air return 11 Air ducts connections 11 Condensate drain connection 11 9 Options 12 Condensation pressure control 12 Air flow control 12 Clogged filter detector 12 Filters 12 Electrical heater 12 10 Safety elements 14 11 Commissioning 14...

Страница 3: ...2014 35 EU PED 2014 68 EC Category 2 RoHS 2011 65 EU Eco design 2009 125 CE Eco labelling 2010 30 EU and with Harmonised Standard EN 378 2 2012 After manufacturing all units are charged with refrigerant and are tested at the factory verifying the correct operation of all their components within the operating range for which they are intended Those in charge of the installation commissioning operat...

Страница 4: ...arate RL 32CF Mobil EAL Artic 22CC Voulme of oil l 1 6 1 6 1 6 3 0 3 3 3 3 Electrical characteristics Electrical power supply 400 V III ph 50 Hz 10 Power supply 3 Wires Ground Maximum absorbed current Compressor A 15 0 19 0 19 0 22 0 29 0 35 0 Outdoor fan A 2 7 3 6 3 6 5 0 5 0 6 9 Indoor fan A 1 6 2 7 2 7 3 6 3 6 6 9 Control A 2 0 2 0 2 0 2 0 2 0 2 0 Total A 21 3 27 3 27 3 32 6 39 6 50 8 Refrigera...

Страница 5: ...ortant Immediately repair any refrigerant leak using a recovery unit specific for R 410A that avoids a possible mixture of refrigerants and or oils Refrigerant leaks A periodical check must be performed for refrigerant gas leaks as per Regulation EC Nº517 2014 over certain greenhouse effect fluoride gases Please consult the frequency of checks in chapter of Maintenance Components of the R 410A R 32 ...

Страница 6: ...6 609 609 266 65 253 585 617 268 603 615 268 80 332 755 746 308 775 743 308 90 375 764 769 307 744 766 307 120 472 1 104 917 340 1 106 906 340 160 521 1 096 921 343 1 097 910 343 Assembling These units can be installed on the floor or on a brick frame or steel profile Foresee appropriate damping devices in these fixtures to ensure that noise and vibration transmission is avoided Location designation ...

Страница 7: ...the air supply and return grille slats due to being tightly closed If in the indoor outdoor circuit the air return is not ducted it is necessary to foresee in the plenum formed by the ceiling framework and walls adequately sized grids appropriate so that the circuit in question aspires the return air Sound level These units are designed to work with a low acoustic level In any case the design of t...

Страница 8: ...rm signal optional 2 wires 6 Safety electrical heaters opt 2 wires The same power supply used for powering the control board must also be used for powering the terminal The thermostat must be fixed at a height of 1 5 m y all possible interferences must be avoided sun outdoor air internal heat sources Mount the thermostat to the wall using the bracket do not leave it hanging from the wire or embeddi...

Страница 9: ...nd the room is very important so that the flows and pressures provided to the duct network are as required Pulley and belt adjustment Both for the indoor circuit motorfans as well as the outdoor circuit are coupled by pulleys and belts In this type of fans the following must be taken into considerations The pulleys must be on the same plane so it is important to check them with the help of a ruler ...

Страница 10: ...e the motor by unscrewing the 2 fixation bolts of the motor feet one on each side of the motor Turn the motor 180 degrees and reassemble it on the fan The change of the position of the pulleys is done to facilitate access in the new location The fan pulley and the belt must be placed on the same side as the motor pulley Mount the panel and the motorised fan unit in its new location First of all rem...

Страница 11: ...o the technical characteristics table The duct calculation and design must be made by qualified technical personnel It is advisable to take into consideration the following recommendations Bendsinthefandischargesupplymustbeavoided Itisrecommendable to have a straight section of duct measuring approximately 1 metre If it is not possible they must be as smooth as possible using indoor deflectors when ...

Страница 12: ...rol is advisable for units that work in cooling with an outdoor temperature below 15º C In units with centrifugal fan a check is performed per damper in the fan outlet A servomotor opens or closes the damper depending on the proportional signal 0 10V received from the electronic control system Clogged filter detector Differential pressostat for indication of maintenance to filters Automatic reactiva...

Страница 13: ...anel Step 4 close the access panel The outlet is ready for ducting Inordertoremovetheelectrical heaters the power supply cables must be disconnected from the terminal board and the hose taken out Rail Then unscrew the screw that fastens the resistor frames and take out by the rail as shown in the following images Hose Electrical heaters Safety thermistors Kit assembly When the frame with the heate...

Страница 14: ...TE RECALENTAMIENTO DE ACEITE DEL CÁRTER KOENNEN TO ALLOW THE COMPRESSOR S STARTING AU PREMIER DÉMARRAGE OU APRÈS UNE ABSCENCE TENSION 24 HEURES AVANT D AUTORISER LE DÉMARRAGE DU DES COMPRESSEUR S AL PRIMO AVVIAMENTO U DOPO UNA INTERRUZIONE PROLUNGATA DELLA ALIMENTAZIONE ELETTRICA LASCIARE LA MACCINA SOTTO TENSIONE PER 24 ORE PRIMA DI AUTORIZZARE L AVVIAMENTO DEL DEI COMPRESSORE I ANTES DEL PRIMER ...

Страница 15: ...he refrigerant via the schrader valve of the liquid line using the appropriate equipment and tools with the compressor stopped monitoring the pressures to control any anomaly High pressure schrader valve optional pressure gauge connection Low pressure schrader valve optional pressure gauge connection Schrader valve for refrigerant load Check the unit operation by verifying the electronic control a...

Страница 16: ...ravimetric filter can be extracted easily by both sides Clean usually Depending on the installation conditions the filter aspect must be examined to define the cleaning periodicity Cleaning the filtering mesh can be done with a household vacuum cleaner or else by submerging it in water Outdoor circuit condensate drain Indoor circ pan Indoor circ coil Outdoor circ pan Outdoor circ coil General recommen...

Страница 17: ... circuit clean and without humidity neutralizing the acids that can be found in the cooling circuit Verify dirt measuring the difference in temperature at the tubing level at the inlet and at the outlet of the dehydrant If necessary replace Refrigerant Only qualified personnel must perform a periodic tightness control in accordance with the regulation CE Nº 517 2014 The frequency of checks is no lo...

Страница 18: ... air or water in condenser very low air or water flow very high adjust flow f Repair Compressor does not start does not make noise humming a No power b The contacts of a control element are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor Klixon open a Check differential magnetothermals b Verify the safety chain of the electronic control c ...

Страница 19: ......

Страница 20: ...Order No 10053 09 2016 Supersedes order No 05 2015 Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union ...

Отзывы: