Table 4—Electrical Data—50GS
UNIT 50GS
SIZE
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
ELECTRIC HEAT
POWER SUPPLY
Min
Max
RLA
LRA
FLA
FLA
Nominal Kw*
FLA
MCA
Max Fuse orCkt Bkr
MOCP
018
208/230–1–60
187
254
9
45
0.80
1.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
13.9/13.9
24.8/28.3
34.7/39.8
47.4/54.3
20/20
25/30
35/40
50/60
—
—
—
—
024
208/230–1–60
187
254
12.8
61
0.8
2
-/-
3.8/5.0
5.4/7.2
7.5/10.0
-/-
18.1/20.8
2/30
36.1/41.7
18.8/18.8
25.1/28.5
35/40
47.6/54.6
25/25
305/30
35/40
50/60
—
—
—
—
030
208/230–1–60
187
254
14.4
73
0.8
2
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
20.8/20.8
25.1/28.5
35/40
47.6/54.6
70.2/80.6
25/25
25/30
35/40
50/60
—
—
—
—
—
80/90
208/230–3–60
187
254
8.3
68
0.8
2
-/-
3.8/5.0
7.5/10.0
11.3/15.0
-/-
10.4/12 .0
20.8/24.1
31.3/36.1
13.2/13.2
15.5/17.5
28.6/32.6
41.6/47.6
20/20
20/20
30/35
45/50
—
—
—
—
036
208/230–1–60
187
254
15.1
81
1.4
2.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
23.1/23.1
26.1/29.5
36.0/41.0
48.6/55.6
71.2/81.6
30/30
30/30
40/45
50/60
–
—
—
—
—
80/90
208/230–3–60
187
254
10.9
78
1.4
2.8
-/-
3.8/5.0
7.5/10.0
11.3/15.0
-/-
10.4/12.0
20.8/24.1
31.3/36.1
17.8/17.8
16.5/18.5
29.6/33.6
42.6/48.6
25/25
25/25
30/35
45/50
—
—
—
—
460–3–60
414
508
5.8
40
0.8
1.4
-
5
10
15
-
6
12
18
9.5
9.5
16.8
24.3
15
15
20
25
—
—
—
—
042
208/230–1–60
187
254
18.6
105
1.4
4
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
28.7/28.7
28.7/31.0
37.5/42.5
50.1/57.1
72.7/83.1
95.3/109.2
35/35
35/35
40/45
60/60
—
—
—
—
—
—
90/100
100/110
208/230–3–60
187
254
10.7
85
1.4
4
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/19.9
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
18.8/18.8
31.1/35.1
44.1/50.1
57.0/65.0
25/25
25/25
35/40
45/60
—
—
—
—
—
60/70
460–3–60
414
508
5.3
42
0.8
2
-
5
10
15
20
-
6
12
18
24.1
9.4
10.0
17.5
25.1
32.6
15
15
20
30
35
—
—
—
—
—
048
208/230–1–60
187
254
25.3
131
2.1
5
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
38.7/38.7
38.7/38.7
38.7/43.8
51.4/58.3
73.9/84.4
96.5/110.4
40/40
40/40
40/45
60/60
—
—
—
—
—
—
90/100
100/125
208/230–3–60
187
254
14.6
108
2.1
5
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/19.9
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
25.4/25.4
25.4/25.4
32.3/36.3
45.3/51.4
58.2/66.2
30/30
30/30
35/40
50/60
—
—
—
—
—
60/70
460–3–60
414
508
7.3
48
1.1
2.3
-
5
10
15
20
-
6
12
18
24.1
12.5
12.5
17.9
25.4
32.9
15
15
20
30
35
—
—
—
—
—
060
208/230–1–60
187
254
28.9
147
2.1
6.8
-/-
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-/-
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
45.0/45.0
45.0/45.0
41.0/46.0
53.6/60.6
76.2/86.6
98.8/112.7
60/60
60/60
45/50
—
—
—
—
—
—
60/70
90/100
100/125
208/230–3–60
187
254
18.6
125
2.1
6.8
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/19.9
-/-
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
32.2/32.2
32.2/32.2
34.6/38.6
47.6/53.6
60.5/68.5
40/40
40/40
40/40
50/60
—
—
—
—
—
70/70
460–3–60
414
508
8.5
66.5
1.1
3.2
-
5
10
15
20
-
6
12
18
24
14.9
14.9
19.0
26.6
34.1
20
20
20
30
35
—
—
—
—
—
(See legend following Electrical Data charts)
11