EN
7.5 -
Air flow rate setting (indoor unit)
The air flow rate can be adjusted on-site directly via the control:
-
Parameter P155 (CCU Controller)
-
No control, inside the electrics box.
■
Min. air flow rate (m
3
/h) for 50CJ W with electric heater and/or humidifier
Unit W
W5
W8
W12
W16
W27
Min. air flow rate value (m³/h)
650
1000
1250
2000
3000
■
Min. air flow rate (m
3
/h) for Unit X
X unit
X5
X8
X10
X12
X15
X19
X24
X31
X36
X38
X48
Min. air flow rate value (m³/h)
600
900
950
2 000
2 000
4 000
4 000
6 000
6 000
8 000
8 000
7.6 - Condensate drain pump (option)
Specifications:
-
230 V-50 Hz-35 W power supply
-
Max flow rate: 30 l/h
-
Max. discharge height: 10 m
Condensate pan
Condensate drain pump
■
Table of actual flow rates
The pressure drops defined in this table are
calculated with a hose 6 mm in diameter
Discharge height
(m)
Total pipe length
5 m
(l/h)
10 m
(l/h)
20 m
(l/h)
30 m
(l/h)
NPSH 0 m
1
29
27
25
23
2
27,5
25,5
24
22
3
25,5
24
22
20,5
4
23,5
22
20
19
5
21
19,5
18
16,5
6
16,5
15
14
7
14
12,5
11,5
8
11,5
10
9
9
9
7,5
6,5
10
6
5
4
7 - TECHNICAL CHARACTERISTICS
55