33
R e s i d e n t i a l P a c k a g e d U n i t s - 6 0 H z P u r o n
®
R e v. : 4 J a n . , 2 0 1 2
Unit Commissioning And Operating Conditions
Table 8a: Building Operating Limits
Operating Limits
Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels
could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.
Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature,
and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be
at normal levels to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air
will adversely affect unit performance, reliability, and service life. Consult Table 8a for operating limits.
Commissioning Conditions
Consult Table 8b for the particular model. Starting conditions vary depending upon model and are based upon the following
notes:
Notes:
1. Conditions in Table 8b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions
to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a
regular basis.
2. Voltage utilization range complies with AHRI Standard 110.
&RROLQJ
+HDWLQJ
$LU/LPLWV
0LQDPELHQWDLU'%
)>&@
)>&@
5DWHGDPELHQWDLU'%
)>&@
)>&@
0D[DPELHQWDLU'%
)>&@
)>&@
0LQHQWHULQJDLU'%:%
)>&@
)>&@
5DWHGHQWHULQJDLU'%:%
)>&@
)>&@
0D[HQWHULQJDLU'%:%
)>&@
)>&@
:DWHU/LPLWV
0LQHQWHULQJZDWHU
)>&@
)>&@
1RUPDOHQWHULQJZDWHU
)>&@
)>WR&@
0D[HQWHULQJZDWHU
)>&@
)>&@
&RPPLVVLRQLQJ/LPLWV
1RUPDO:DWHU)ORZ
WRJSPWRQ
>WROPSHUN:@
,IZLWKDFWLYH:KROH+RXVH'HKXPLGLILFDWLRQʞʝ
7DEOHE%XLOGLQJ&RPPLVVLRQLQJ/LPLWV
*73;*73*
Cooling
Heating
Cooling
Heating
Air Limits
Min. ambient air, DB
45ºF [7ºC]
39ºF [4ºC]
45ºF [7ºC]
39ºF [4ºC
Rated ambient air, DB
80.6ºF [27ºC]
68ºF [20ºC]
80.6ºF [27ºC]
68ºF [20ºC
Max. ambient air, DB
110ºF [43ºC]
85ºF [29ºC]
110ºF [43ºC]
85ºF [29ºC]
Min. entering air, DB/WB
60/45ºF [16/7ºC]
40ºF [4.4ºC]
60/50ºF [16/10ºC]
45ºF [7ºC]
Rated entering air, DB/WB
80.6/66.2ºF [27/19ºC]
68ºF [20ºC]
80.6/66.2ºF [27/19ºC]
68ºF [20ºC
Max. entering air, DB/WB
100/75ºF [38/24ºC]
80ºF [27ºC]
95/75ºF [35/24ºC]
80ºF [27ºC]
Water Limits
Min. entering water
30ºF [-1ºC]
20ºF [-6.7ºC]
30ºF [-1ºC]
20ºF [-6.7ºC]
Normal entering water
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
50-110ºF [10-43ºC]
30-70ºF [-1 to 21ºC]
Max. entering water
120ºF [49ºC]
90ºF [32ºC]
120ºF [49ºC]
90ºF [32ºC]
GT-PG
GT-PX
Operating Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Rev.: 20 May, 2009S
Содержание 50 YEH
Страница 2: ...This page was intentionally left blank...
Страница 49: ...49 Residential Packaged Units 60Hz Puron Rev 4 Jan 2 0 1 2 Notes...
Страница 50: ...Re s i d e n t ia l Packaged Units 60Hz Puron R ev 4 J an 2012 50 Notes...
Страница 51: ...51 Residential Packaged Units 60Hz Puron Rev 4 Jan 2 0 1 2 Notes...