Outdoor air leakage is shown in Table 9. Return air pressure
drop is shown in Table 10.
Table 9 — Outdoor Air Damper Leakage
Table 10 — Return Air Pressure Drop (in. wg)
ECONOMI$ERIV STANDARD SENSORS
Outdoor Air Temperature (OAT) Sensor — The outdoor air
temperature sensor (HH57AC074) is a 10 to 20 mA device
used to measure the outdoor-air temperature. The outdoor air
temperature is used to determine when the EconoMi$erIV can
be used for free cooling. The sensor must be field-relocated.
See Fig. 33. The operating range of temperature measurement
is 40 to 100 F.
Supply Air Temperature (SAT) Sensor — The supply air
temperature sensor is a 3 K thermistor located at the inlet of the
indoor fan. See Fig. 34. This sensor is factory installed. The op-
erating range of temperature measurement is 0° to 158 F. See
Table 11 for sensor temperature/resistance values.
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
Low Temperature Compressor Lockout Switch — The Econo-
Mi$erIV is equipped with an ambient temperature lockout
switch located in the outdoor airstream which is used to lockout
the compressors below a 42 F ambient temperature. See Fig. 33.
Table 11 — Supply Air Sensor Temperature/
Resistance Values
DAMPER STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
LEAKAGE (cfm)
35
53
65
75
90
102
CFM
4500
5000
5400
6000
7200
7500
9000 10,000 11,250
0.040 0.050 0.060 0.070 0.090 0.100 0.110
0.120
0.140
TEMPERATURE (F)
RESISTANCE (ohms)
–58
200,250
–40
100,680
–22
53,010
–4
29,091
14
16,590
32
9,795
50
5,970
68
3,747
77
3,000
86
2,416
104
1,597
122
1,080
140
746
158
525
176
376
185
321
194
274
212
203
230
153
248
116
257
102
266
89
284
70
302
55
ECONOMI$ERIV
OUTDOOR AIR
TEMPERATURE SENSOR
(INSTALLED OPERATION
POSITION)
SCREWS
SCREWS
FRAME
TOP
LOW TEMPERATURE
COMPRESSOR
LOCKOUT SWITCH
ACTUATOR
ECONOMI$ERIV
FLANGE
AND SCREWS
(HIDDEN)
CONTROLLER
SUPPLY AIR
TEMPERATURE SENSOR
LOCATION
TR
1
24
Va
c
CO
M
TR
24
Va
c
HO
T
1
2
3
4
5
EF
EF
1
+
_
P1
T1
P
T
N
EX
H
2V
10
V
EX
H
Se
t
Se
t
2V
10
V
2V
10
V
DC
V
DC
V
Fr
ee
Co
ol
B
C
A
D
SO
+
SR
+
SR
SO
AQ
1
AQ
DC
V
Mi
n
Po
s
Op
en
Ma
x
N1
Fig. 33 — EconoMi$erIV Component Locations —
End View
Fig. 34 — EconoMi$erIV Component Locations —
Side View
FRAME
TOP
SCREWS
ECONOMI$ER2
SCREWS
Fig. 35 — EconoMi$er2 Component Locations
Содержание 48TM016
Страница 3: ...3 Fig 2A Roof Curb Details 48TM016 025 ...
Страница 4: ...4 Fig 2B Roof Curb Details 48TM028 ...
Страница 6: ...6 Fig 4 Base Unit Dimensions 48TM016 020 ...
Страница 7: ...7 Fig 5 Base Unit Dimensions 48TM025 ...
Страница 8: ...8 Fig 6 Base Unit Dimensions 48TM028 ...
Страница 32: ...32 Fig 46 MoistureMi er Dehumidification Operation Diagram TXV Thermostatic Expansion Valve ...
Страница 48: ...48 Fig 57 Typical Wiring Schematic 48TM016 020 208 230 V Shown ...
Страница 49: ...49 Fig 58 Typical Component Arrangement ...
Страница 56: ...56 Fig 60 EconoMi erIV Functional View ...
Страница 59: ......