TROUBLESHOOTING
Refer to Tables 32-34 for unit troubleshooting.
EconoMi$er2 Troubleshooting
ECONOMI$ER2 CHECKOUT PROCEDURE — Prepare
the EconoMi$er2 for troubleshooting by performing the fol-
lowing procedure:
1. Disconnect power at TR and TR1. Free Cool, unit con-
trol, indoor fan, and exhaust control contacts should be
open.
2. Disconnect device at P and P1.
3. Disconnect device at Q and Q1.
4. Jumper P to P1.
5. Jumper Q to Q1.
6. Turn Minimum Position potentiometer fully CCW
(counterclockwise).
7. Turn Maximum Position potentiometer fully CW
(clockwise).
8. Place 6.8 kohm resistor across T and T1.
9. Jumper TR to 1.
10. If connected, remove enthalpy sensor from terminals S
O
and +. Connect 1.2 kohm 4074EJM checkout resistor
across terminals S
O
and +.
11. Set both ISI and Exhaust potentiometers fully CCW.
12. Put 620-ohm resistor across terminals S
R
and +.
13. Set enthalpy potentiometer to D.
14. Apply power (24 vac) to terminals TR and TR1.
DIFFERENTIAL ENTHALPY — To check differential
enthalpy:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Place 620-ohm resistor across S
O
and +.
3. Place 1.2 Kohm resistor across S
R
and +. The Free Cool
LED should be lit.
4. Remove 620-ohm resistor across S
O
and +. The Free
Cool LED should turn off.
5. Return EconoMi$er2 settings and wiring to normal after
completing troubleshooting.
SINGLE ENTHALPY — To check single enthalpy:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMi$er2 settings and wiring to normal after
completing troubleshooting.
ISI (INDOOR AIR QUALITY) AND POWER
EXHAUST — To check ISI and Power Exhaust:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both ISI and Power Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9V battery to AQ (positive node) and AQ1
(negative node). The LED for both ISI and the Exhaust
Fan should turn on. The actuator should drive to 90 to
95% open.
4. Turn the exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the poten-
tiometer is approximately 90%. The actuator should re-
main in position.
5. Turn ISI potentiometer CW until ISI LED turns off. The
ISI LED should turn off when the potentiometer is ap-
proximately 9V. The actuator should drive fully closed.
6. Turn ISI and Exhaust potentiometers CW until the Ex-
haust LED turns on. Forty-five seconds after the Exhaust
LED turns on, the exhaust contacts will close.
7. Return EconoMi$er2 settings and wiring to normal after
completing troubleshooting.
FREEZE PROTECTION — To check freeze protection:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Connect a 9V battery to AQ (positive node) and AQ1
(negative node). The LED for both ISI and the Exhaust
Fan should turn on. The actuator should drive to 90 to
95% open.
3. Remove the 6.8 Kohm resistor from T and T1. The Ex-
haust LED should turn off and the actuator should drive
fully closed.
4. Replace the 6.8 Kohm resistor across T and T1. The Ex-
haust LED should turn on and the actuator should drive to
90 to 95% open.
5. Return EconoMi$er2 settings and wiring to normal after
completing troubleshooting.
MINIMUM AND MAXIMUM POSITION — To check min-
imum and maximum position:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Connect a 9V battery to AQ (positive node) and AQ1
(negative node). The LED for both ISI and the Exhaust
Fan should turn on. The actuator should drive to 90 to
95% open.
3. Turn the Maximum Position potentiometer to midpoint.
The actuator should drive to 20 to 80% open.
4. Turn the Maximum Position potentiometer to fully CCW.
The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive 20 to 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Return EconoMi$er2 settings and wiring to normal after
completing troubleshooting.
AIR CHANGE, SHUTDOWN, AND PURGE — To check
air change, shutdown, and purge:
1. Make sure EconoMi$er2 checkout procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open.
3. Turn the Minimum Position Potentiometer to midpoint.
The actuator should drive 20 to 80% open.
4. Make sure that the Air Change, Purge, and Shutdown ter-
minals are empty. The Exhaust LED should turn on. The
Unit Control and Indoor Fan contacts will close.
5. Jumper the Air Change terminals. The exhaust LED turns
on. The Unit Control contacts open. The Indoor Fan con-
tacts remain closed. The actuator drives fully open.