
29
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of the sensor
housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
CHANGING THE DIRT SENSOR TEST
By default, sensor dirty test results are indicated by:
• The sensor’s Dirty LED flashing.
• The controller’s Trouble LED flashing.
• The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so that the
controller’s supervision relay is not used to indicate test results.
When two detectors are connected to a controller, sensor dirty test
operation on both sensors must be configured to operate in the
same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of the sensor
housing for approximately 60 seconds until the sensor’s
Alarm LED turns on and its Dirty LED flashes twice.
2. Reset the sensor by removing the test magnet and then hold
-
ing it against the sensor housing again for approximately
2 seconds until the sensor’s Alarm LED turns off.
REMOTE STATION TEST
The remote station alarm test checks a test/reset station’s ability to
initiate and indicate an alarm state.
SD-TRK4 REMOTE ALARM TEST PROCEDURE
1. Turn the key switch to the RESET/TEST position for seven
seconds.
2. Verify that the test/reset station’s Alarm LED turns on.
3. Reset the sensor by turning the key switch to the RESET/
TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns off.
REMOTE TEST/RESET STATION DIRTY SENSOR TEST
The test/reset station dirty sensor test checks the test/reset station’s
ability to initiate a sensor dirty test and indicate the results. It must
be wired to the controller as shown in Fig. 41 and configured to
operate the controller’s supervision relay. For more information,
see “Changing the Dirty Sensor Test.”
Fig. 41 —
Remote Test/Reset Station Connections
DIRTY SENSOR TEST USING AN SD-TRK4
1. Turn the key switch to the RESET/TEST position for two
seconds.
2. Verify that the test/reset station’s Trouble LED flashes.
Detector Cleaning
CLEANING THE SMOKE DETECTOR
Clean the duct smoke sensor when the Dirty LED is flashing con
-
tinuously or sooner, if conditions warrant.
1. Disconnect power from the duct detector then remove the
sensor’s cover. (See Fig. 42.)
Table 6 —
Dirty LED Test
FLASHES
DESCRIPTION
1
0-25% dirty. (Typical of a newly installed detector)
2
25-50% dirty
3
51-75% dirty
4
76-99% dirty
NOTICE: OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an unnecessary
evacuation of the facility.
Changing the dirty sensor test operation will put the detector
into the alarm state and activate all automatic alarm responses.
Before changing dirty sensor test operation, disconnect all aux
-
iliary equipment from the controller and notify the proper au
-
thorities if connected to a fire alarm system.
NOTICE: OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an unnecessary
evacuation of the facility.
Changing the dirty sensor test operation will put the detector
into the alarm state and activate all automatic alarm responses.
Before changing the dirty sensor test operation, disconnect all
auxiliary equipment from the controller and notify proper au
-
thorities if connected to a fire alarm system.
NOTICE: OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an unnecessary
evacuation of the facility.
If the test/reset station’s key switch is left in the RESET/TEST
position for longer than seven seconds, the detector will auto
-
matically go into the alarm state and activate all automatic
alarm responses.
NOTICE: OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an unnecessary
evacuation of the facility.
Holding the test magnet to the target area for longer than seven
seconds will put the detector into the alarm state and activate all
automatic alarm responses.
NOTICE: OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an unnecessary
evacuation of the facility.
If the smoke detector is connected to a fire alarm system, first
notify the proper authorities that the detector is undergoing
maintenance then disable the relevant circuit to avoid generat
-
ing a false alarm.
1
12
14
13
19
15
2
20
3
RESET/TEST
Trouble
POWER
ALARM
SUPERVISION RELAY
CONTACTS [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 VDC (-)
18 VDC (-)
AUXILIARY
EQUIPMENT
+
−
WIRE MUST BE
ADDED BY
INSTALLER
SMOKE DETECTOR
CONTROLLER
Содержание 48TC series
Страница 40: ...40 Fig 56 Typical IGC Wiring Diagram...
Страница 41: ...41 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...
Страница 47: ...47 Fig 62 RTU Open Overlay for Economizer Wiring...
Страница 48: ...48 Fig 63 VFD Overlay for W2770 Controller Wiring...
Страница 96: ...96 Fig C 48TC D17 D30 Control Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 97: ...97 Fig D 48TC D17 D30 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 98: ...98 Fig E 48TC D17 D30 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 99: ...99 Fig F 48TC D17 D30 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 100: ...100 Fig G 48TC D17 D30 Control Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 101: ...101 Fig H 48TC D17 D30 Power Diagram 208 230 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 102: ...102 Fig I 48TC D17 D30 Power Diagram 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 103: ...103 Fig J 48TC D17 D30 Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 104: ...104 Fig K PremierLink System Control Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Страница 105: ...105 Fig L PremierLink System Control Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 106: ...106 Fig M RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Страница 107: ...107 Fig N RTU OPEN Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 109: ......