Carrier 48TC series Скачать руководство пользователя страница 53

53

Fig. 74 — 

CO

Sensor Maximum Range Settings

EXHAUST SETPOINT ADJUSTMENT
The exhaust setpoint will  determine when the exhaust fan runs

based  on  damper  position  (if  accessory  power  exhaust  is  in

-

stalled). The setpoint is modified with the Exhaust Fan Setpoint

(EXH SET) potentiometer. See Fig. 69. The setpoint represents

the damper position above which the exhaust fans will be turned

on. When there is a call for exhaust, the EconoMi$er IV controller

provides a 45 ± 15 second delay before exhaust fan activation to

allow the dampers to open. This delay allows the damper to reach

the appropriate position to avoid unnecessary fan overload.
MINIMUM POSITION CONTROL
There  is  a  minimum  damper  position  potentiometer  on  the

EconoMi$er IV controller. See Fig. 69. The minimum damper po

-

sition maintains the minimum airflow into the building during the

occupied period.

When using demand ventilation, the minimum damper position

represents the minimum ventilation position for Volatile Organic

Compound  (VOC)  ventilation requirements. The maximum de

-

mand ventilation position is used for fully occupied ventilation.

When demand ventilation control is not being used, the minimum

position potentiometer should be used to set the occupied ventila

-

tion position. The maximum demand ventilation position should

be turned fully clockwise.

Adjust  the  minimum  position  potentiometer  to  allow  the  mini

-

mum amount of outdoor air, as required by local codes, to enter

the building. Make minimum position adjustments with at least

10°F temperature difference between the outdoor and return-air

temperatures.

To determine the minimum position setting, perform the following

procedure:

1. Calculate the appropriate mixed air temperature using the

following formula:

T

O

 = Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

 = Return-Air Temperature

RA = Percent of Return Air

T

M

 = Mixed-Air Temperature

As an example, if local codes require 10% outdoor air during oc

-

cupied conditions, outdoor-air temperature is 60°F, and return-air

temperature is 75°F.

(60 x 0.10) + (75 x 0.90) = 73.5°F

2. Disconnect the supply air sensor from terminals T and T1.

3. Ensure that the factory-installed jumper is in place across

terminals P and P1. If remote damper positioning is being

used, make sure that the terminals are wired according to

Fig.  68  and  that  the  minimum  position  potentiometer  is

turned fully clockwise.

4. Connect 24 vac across terminals TR and TR1.

5. Carefully adjust the minimum position potentiometer until

the  measured  mixed  air  temperature  matches  the  calcu

-

lated value.

6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when

requiring additional temporary ventilation. If a field-supplied re

-

mote  potentiometer  (Honeywell  part  number  S963B1128)  is

wired to the EconoMi$er IV controller, the minimum position of

the damper can be controlled from a remote location.

To control the minimum damper position remotely, remove the

factory-installed  jumper  on  the  P  and  P1  terminals  on  the

EconoMi$er IV controller. Wire the field-supplied potentiometer

to the P and P1 terminals on the EconoMi$er IV controller. (See

Fig. 72.)
DAMPER MOVEMENT
Damper movement from full open to full closed (or vice versa)

takes 2

1

/

2

 minutes.

THERMOSTATS
The EconoMi$er IV control works with conventional thermostats

that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1),

W2 (heat stage 2), and G (fan). The EconoMi$er IV control does

not support space temperature sensors. Connections are made at

the thermostat terminal connection board located in the main con

-

trol box.
OCCUPANCY CONTROL
The factory default configuration for the EconoMi$er IV control

is occupied mode. Occupied status is provided by the black jump

-

er from terminal TR to terminal N. When unoccupied mode is de

-

sired, install  a field-supplied timeclock function in place of the

jumper  between  TR  and  N.  When  the  timeclock  contacts  are

closed,  the  EconoMi$er  IV  control  will  be  in  occupied  mode.

When the timeclock contacts are open (removing the 24-v signal

from  terminal  N),  the  EconoMi$er  IV  will  be  in  unoccupied

mode.
DEMAND CONTROLLED VENTILATION (DCV)
When using the EconoMi$er IV for demand controlled ventila

-

tion, there are some equipment selection criteria which should be

considered. When selecting the heat capacity and cool capacity of

the equipment, the maximum ventilation rate must be evaluated

for design conditions. The maximum damper position must be cal

-

culated to provide the desired fresh air.

Typically the maximum ventilation rate will be about 5 to 10%

more than the typical cfm required per person, using normal out

-

side air design criteria.

A proportional anticipatory strategy should be taken with the fol

-

lowing conditions: a zone with a large area, varied occupancy, and

equipment that cannot exceed the required ventilation rate at de

-

sign conditions. Exceeding the required ventilation rate means the

equipment can condition air at a maximum ventilation rate that is

greater than the required ventilation rate for maximum occupancy.

A proportional-anticipatory strategy will cause the fresh air sup

-

plied to increase as the room CO

2

 level increases even though the

CO

2

 setpoint has  not  been  reached. By  the time  the CO

2

 level

reaches the setpoint, the damper will be at maximum ventilation

and should maintain the setpoint.

In order to have the CO

2

 sensor control the EconoMi$er damper in

this manner, first determine the damper voltage output for mini

-

mum  or base  ventilation.  Base  ventilation is  the ventilation  re

-

quired to remove contaminants during unoccupied periods. The

(T

O  

 x

OA

) + (T

R

   x

RA

)

=  T

M

100

100

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

RANGE

C

ONFIGURA

TION

(ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

800 ppm

900 ppm

1000 ppm

1100 ppm

Содержание 48TC series

Страница 1: ...FRIGERANT 17 Refrigerant Charge 17 Using the Cooling Charging Charts 17 COOLING CHARGING CHARTS 18 COMPRESSORS 22 Lubrication 22 Filter Drier 22 TROUBLESHOOTING THE COOLING SYSTEM 23 CONVENIENCE OUTLE...

Страница 2: ...hen handling parts and servicing air conditioning equipment WARNING FIRE EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use...

Страница 3: ...ters and screens will need to be periodically re placed or cleaned RETURN AIR FILTERS Return air filters are a disposable fiberglass media type Access to the filters is through the small lift out pane...

Страница 4: ...belt condition and tension quarterly Inspect the belt for signs of cracking fraying or glazing along the inside surfaces Check belt tension by using a spring force tool such as Brown ing s Belt Tensio...

Страница 5: ...or a realignment of the pulleys after any adjustment of the movable flange Also reset the belt tension after each realignment The factory settings of the adjustable pulley is five turns open from full...

Страница 6: ...for the VFD can be found in the following manuals Variable Frequency Drive VFD Installation Setup and Troubleshooting Supplement MOTOR When replacing the motor use the following steps See Fig 10 Fig 1...

Страница 7: ...o increase fan wheel speed check the fan performance at the target speed and airflow rate to determine new motor loading bhp Use the fan performance tables or use the Packaged Rooftop Builder software...

Страница 8: ...A accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring painted metal surfaces or insulation Use of non recommended coil cleaners is strongly dis...

Страница 9: ...d pro tective clothing are recommended during mixing and application 2 Remove all surface loaded fibers and dirt with a vacuum cleaner as described above 3 Thoroughly wet finned surfaces with clean wa...

Страница 10: ...CD P N P920 0010 that allow the replacement of the Schrader valve core without having to re cover the entire system refrigerant charge Apply compressor re frigerant oil to the Schrader valve core s bo...

Страница 11: ...gerant then enters a Thermostatic Expansion Valve TXV decreasing the air pressure The refrigerant enters the TXV and evaporator coil at a tempera ture lower than the temperature in the standard coolin...

Страница 12: ...OMPRESSOR OUTDOOR AIR INDOOR AIR RH2 x VALVE RH1 x VALVE TXV VALVE CLOSED VALVE OPEN VALVE 3 WAY VALVE CONDENSER COIL HUMIDI MIZER COIL EVAPORATOR COIL COMPRESSOR OUTDOOR AIR INDOOR AIR RH2 x VALVE RH...

Страница 13: ...Freeze Protection Thermostat IFM Indoor supply Fan Motor LSV Liquid Solenoid Valve LTLO Low Temperature Lockout REHEAT Connection Strip REHEAT on CTB Table 3 Inputs Modes Outputs Summary INPUT MODE OU...

Страница 14: ...transformer and circuit beaker or fuses Solenoid coil burnout Check continuous over voltage is less than 10 Check under voltage is less than 15 Check for missing coil assembly parts Check for damaged...

Страница 15: ...410A refrigerant recover all refrigerant from the system 3 Remove the TXV support clamp 4 Disconnect the liquid line at the TXV inlet 5 Remove the liquid line connection at the TXV inlet 6 Remove the...

Страница 16: ...16 Fig 22 TXV Sensor Bulb Locations TXV SENSOR BULB CLAMP CIRCUIT 1 CIRCUIT 2 TXV CIRCUIT 2 TXV CIRCUIT 1 TXV SENSOR BULBS TXV SENSOR BULBS...

Страница 17: ...has a refrigerant leak If the evacuation level raises to 1100 microns and stabilizes then the system has moisture in it and should be dehydrated as GTAC2 5 recommends If the system continues to rise...

Страница 18: ...ig Suction Temperature 50HE501045 C 115F 46 1C 105F 40 6C 95F 35 0C 85F 29 4C 75F 23 9C 65F 18 3C 55F 12 8C 45F 7 2C COOLING CHARGING CHART 15 and 17 5 Ton Circuit A F 35 40 45 50 55 60 65 70 75 80 85...

Страница 19: ...on Temperature 50HE501089 C 115F 46 1C 105F 40 6C 95F 35 0C 85F 29 4C 75F 23 9C 65F 18 3C 55F 12 8C 45F 7 2C COOLING CHARGING CHART 20 Ton Circuit A F 35 40 45 50 55 60 65 70 75 80 85 90 95 100 C 1 7...

Страница 20: ...0 90 0 80 0 50HE501091 C 115F 46 1C 105F 40 6C 95F 35 0C 85F 29 4C 75F 23 9C 65F 18 3C 55F 12 8C 45F 7 2C COOLING CHARGING CHART 25 0 Ton Circuit A F 45 50 55 60 65 70 75 80 85 90 95 100 C 7 2 10 5 1...

Страница 21: ...21 Fig 29 Cooling Charging Chart 27 5 Ton Circuit A Fig 30 Cooling Charging Chart 27 5 Ton Circuit B COOLING CHARGING CHART 27 5 Ton Circuit A COOLING CHARGING CHART 27 5 Ton Circuit B...

Страница 22: ...R DRIER Use the following steps to replace the filter drier 1 Using a Puron R 410A gage set recover all refrigerant from the system 2 Use a tubing cutter to remove the filter drier from the line NOTE...

Страница 23: ...filter Unit undersized for load Decrease load or replace with larger unit Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Leaking valves in compressor Re...

Страница 24: ...f primary power source is a custom er option If local codes permit the transformer primary leads can be connected at the line side terminals on a unit mounted non fused disconnect or circuit breaker s...

Страница 25: ...ation to confirm full closing and latching Fig 34 Weatherproof Cover Installation SMOKE DETECTORS Smoke detectors are available as factory installed options on 48TC models Smoke detectors may be speci...

Страница 26: ...nal an alarm state but dust and debris accumulated over time does not For installations using two sensors the duct smoke detector does not differentiate which sensor signals an alarm or trouble condit...

Страница 27: ...al board CTB all unit oper ations cease immediately PREMIERLINK AND RTU OPEN CONTROLS Unit operating functions fan cooling and heating are terminated as described above Highlight D On smoke alarm cond...

Страница 28: ...onsid ered 100 dirty and requires cleaning or replacing Use a field provided SD MAG test magnet to initiate a sensor dirty test The sensor s Dirty LED indicates the results of the dirty test as shown...

Страница 29: ...n the duct smoke sensor when the Dirty LED is flashing con tinuously or sooner if conditions warrant 1 Disconnect power from the duct detector then remove the sensor s cover See Fig 42 Table 6 Dirty L...

Страница 30: ...ne is pulled to ground Trouble state The SuperDuct duct smoke detector enters the trouble state under the following conditions A sensor s cover is removed and 20 minutes pass before it is properly sec...

Страница 31: ...has internal linebreak motor protection Reset is automatic after compressor motor has cooled OVERTEMPERATURE Each compressor has an internal protector to protect it against ex cessively high discharg...

Страница 32: ...rol For details on operating units equipped with the factory installed PremierLink controller option refer to the PremierLink Retrofit Rooftop Controller Version 3 x Installation Start Up and Config u...

Страница 33: ...at the IGC circuit will initiate an Ignition Fault 5 flashes lockout Reset of the low pressure switch is automatic on rise in supply line pressure Reset of the IGC re quires a recycle of unit power af...

Страница 34: ...move the motor cooling fan by removing one setscrew 5 Remove the nuts that hold the motor to the mounting plate 6 To reinstall reverse the procedure outlined above Burners and Igniters MAIN BURNERS To...

Страница 35: ...brush to clean the burners and cross over port as required 4 Adjust the spark gap The gap should be 0 12 to 0 14 in 3 06 to 3 60 mm and spaced 0 18 in 4 60 mm from the end of the burner See Fig 55 5 I...

Страница 36: ...nifold pressure 7 When the main burners ignite check all fittings manifold and orifices for leaks 8 Adjust the high stage pressure to the specified setting by turn ing the plastic adjustment screw clo...

Страница 37: ...t 5 seconds LEGEND LED Light Emitting Diode A 3 second pause exists between LED error code flashes If more than one error code exists all applicable codes will be displayed in numerical sequence Orifi...

Страница 38: ...pical MRT Spark Adjustment 0 18 4 60 mm 0 12 0 14 3 05 3 56 mm SPARK GAP NOTE SPARK GAP MUST BE AT THE BOTTOM OF THE BURNER IGNITER AND SENSOR LOCATIONS BRACKET HEAT COVER NOT SHOWN FOR CLARITY 9 CELL...

Страница 39: ...7 LH32RF104 0 1040 38 LH32RF102 0 1015 39 LH32RF103 0 0995 40 LH32RF098 0 0980 41 LH32RF096 0 0960 42 LH32RF094 0 0935 43 LH32RF089 0 0890 44 LH32RF086 0 0860 45 LH32RF082 0 0820 46 LH32RF080 0 0810 4...

Страница 40: ...40 Fig 56 Typical IGC Wiring Diagram...

Страница 41: ...41 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...

Страница 42: ...og input J1 1 3 FS T1 Flame sensor gas section switch input W Heat stage 1 LCTB 24 VAC J2 2 RS Rollout switch gas section switch input J2 5 6 LS Limit switch fan section switch input J2 7 8 CS Centrif...

Страница 43: ...000 351 186 000 351 240 000 11 000 3353 372 123 200 372 173 600 372 224 000 12 000 3658 372 114 400 372 161 200 372 208 000 13 000 3962 392 105 600 392 148 800 392 192 000 14 000 4267 392 96 800 392 1...

Страница 44: ...ter in gas line Drain water and install drip leg to trap water No power to furnace Check power supply fuses wiring and circuit breaker No 24 v power supply to control circuit Check transformer Transfo...

Страница 45: ...Off Power reset for LED reset 4 consecutive limit switch faults within a single call for heat See Limit Switch Fault 5 Flashes Ignition Fault No gas heating Heat call W Off Power reset for LED reset U...

Страница 46: ...conoMi er 2 Component Locations IMPORTANT Any economizer that meets the economizer re quirements as laid out in California s Title 24 mandatory sec tion 120 2 fault detection and diagnostics and or pr...

Страница 47: ...47 Fig 62 RTU Open Overlay for Economizer Wiring...

Страница 48: ...48 Fig 63 VFD Overlay for W2770 Controller Wiring...

Страница 49: ...ion for economizer to operate 2 PremierLink control requires that the standard 50HJ540569 out side air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077 enthalpy sensor 3 50H...

Страница 50: ...ir sensor signal Modulation is based on the DCV signal Modulation is based on the greater of DCV and supply air sensor signals between minimum position and either maximum position DCV or fully open su...

Страница 51: ...above the setpoint the EconoMi er IV will adjust the outside air dampers to minimum position If the outdoor air temperature is below the setpoint the position of the outside air dampers will be contro...

Страница 52: ...When using this mode of changeover control turn the enthalpy setpoint potentiometer fully clockwise to the D setting INDOOR AIR QUALITY IAQ SENSOR INPUT The IAQ input can be used for demand controlle...

Страница 53: ...EconoMi er IV controller the minimum position of the damper can be controlled from a remote location To control the minimum damper position remotely remove the factory installed jumper on the P and P1...

Страница 54: ...e normal operation CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units As such these kits may contain parts that will not be needed for installation 33ZCSENCO2 is an ac...

Страница 55: ...oting DCV MINIMUM AND MAXIMUM POSITION To check the DCV minimum and maximum position 1 Make sure EconoMi er IV preparation procedure has been performed 2 Connect a 9 v battery to AQ positive node and...

Страница 56: ...30 vac RMS 50 60 Hz Transformer 100 va maximum system input Nominal Power Consumption at 24 vac 60 Hz 11 5 VA without sensors or actuators Relay Digital Output Rating at 30 vac maximum power from Clas...

Страница 57: ...CT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output Common ACT 24v 24 vac Damper Actuator 24 vac Source NA AUX2 OCC E GND EXH1 AUX1 O Y2 Y1 Y2 O Y1 O C R 50048848 002 R...

Страница 58: ...a menu s item and return to the list of menus Fig 79 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests andAlarms 1 Navigat...

Страница 59: ...c on terminal Y1 I COOL Y1 OUT OFF ON OFF FIRST STAGE COOLING RELAY OUTPUT Cool stage 1 Relay Output to stage 1 mechanical cooling Y1 OUT terminal COOL Y2 IN OFF ON OFF SECOND STAGE COOLING DEMAND Y2...

Страница 60: ...ressor lockout At or below the set point the Y1 O and Y2 O will not be energized on the controller DRYBLB SET 63 F 17 C 48 F to 80 F 9 C to 27 C increment by 1 F OA DRY BULB TEMPERATURE CHANGEOVER SET...

Страница 61: ...mode for W Shutdown is not available in 2 speed fan mode In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump on heat FAN SPEED 2 speed 1 speed 2 speed Sets the economizer c...

Страница 62: ...Allows for operator to adjust for an out of calibration humidity sensor DA T CAL 0 0 F 2 5 F DISCHARGE AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration temperat...

Страница 63: ...T ERR RETURN AIR S BUS SENSOR ERROR Return air enthalpy sensor has failed or become disconnected check wiring then replace sensor if the alarm continues RA SYLK H ERR DA SYLK T ERR DISCHARGE AIR S BUS...

Страница 64: ...Closed On On High 24 v On 24 v On MIN POS Closed Yes Off Off High 0 v Off 0 v Off MIN POS Closed On Off High 0 v Off 0 v Off MIN POS to Full Open Closed to Full Open On On High 24 v On 0 v Off MIN PO...

Страница 65: ...Off High 0 v Off 0 v Off MIN POS Closed On Off High 0 v Off 0 v Off MIN POS to Full Open Closed to Full Open On On High 24 v On 0 v Off MIN POS to Full Open Closed to Full Open Table 31 Enthalpy Oper...

Страница 66: ...Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No OFF OFF LOW 0v Off 0v Off VENTMIN Closed ON OFF LOW 24v On 0v Off VENTMIN Closed ON ON HIGH 24v On 24v On VENTMIN Closed Yes OFF OFF LOW...

Страница 67: ...he supply fan and controls the OAdamper to the required posi tion see Table 36 The W heating mode is not controlled by the W7220 but it re quires the status to know where to position the OA damper for...

Страница 68: ...the Checkout menu using the and buttons 2 Press the Enter button to select the item RUN appears 3 Press the Enter button to start the test The unit pauses and then displays IN PROGRESS When the test...

Страница 69: ...f output operation Controller configuration is also part of start up This is especially important when field accessories have been added to the unit The factory pre configures options in stalled at th...

Страница 70: ...ve room temperature and verify that the burners light and evaporator fan is energized Check heating ef fect then lower the thermostat setting below the room temperature and verify that the burners and...

Страница 71: ...ing this period the evaporator fan off delay will increase by 15 seconds A maxi mum of 9 trips can occur extending the evaporator fan off delay to 180 seconds To restore the original default value res...

Страница 72: ...ard Q E coat Al Cu E coat Al Cu Louvered Hail Guard R Cu Cu Al Cu Louvered Hail Guard S Cu Cu Cu Cu Louvered Hail Guard Coil Options Novation Outdoor Indoor Hail Guard G Al Al Al Cu H Al Al Cu Cu J Al...

Страница 73: ...Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N Precoat Al Cu Al Cu Louvered Hail Guard P E coat Al Cu Al Cu Louvered Hail Guard Q E coat Al Cu E coat Al Cu Louvered Ha...

Страница 74: ...3 7 Max BHP 3 7 RPM Range 679 863 Max blower shaft RPM 1200 Motor frame size 56 Fan qty Type 2 Centrifugal Fan diameter in 15 x 15 High Static Motor qty Belt qty Drive type 1 1 Belt Nominal nameplate...

Страница 75: ...or drive type 3 direct 3 direct 4 direct 4 direct Motor HP RPM 1 4 1100 1 4 1100 1 4 1100 1 4 1100 Fan diameter in 22 22 22 22 FILTERS RA filter size in 6 20 x 25 x 2 6 20 x 25 x 2 6 20 x 25 x 2 9 16...

Страница 76: ...ugal 2 Centrifugal 2 Centrifugal 2 Centrifugal Fan diameter in 15 x 15 15 x 15 15 x 15 15 x 15 Medium Static Motor qty Belt qty Drive type 1 1 Belt 1 1 Belt Nominal nameplate HP 3 7 3 7 Max BHP 3 7 3...

Страница 77: ...17 2 17 2 17 Total face area ft2 21 4 21 4 21 4 21 4 COND FAN MOTOR Qty Motor drive type 3 direct 3 direct 3 direct 3 direct Motor HP RPM 1 4 1100 1 4 1100 1 4 1100 1 4 1100 Fan diameter in 22 22 22 2...

Страница 78: ...Belt qty Drive type 1 1 Belt Nominal nameplate HP 5 0 Max BHP 208 230 460 575v 6 5 6 9 7 0 8 3 RPM Range 751 954 Max blower shaft RPM 1300 Motor frame size 56 Fan qty Type 2 Centrifugal Fan diameter...

Страница 79: ...t 4 direct 4 direct 6 direct Motor HP RPM 1 4 1100 1 4 1100 1 4 1100 1 4 1100 1 4 1100 Fan diameter in 22 22 22 22 22 FILTERS RA filter size in 6 20 x 25 x 2 6 20 x 25 x 2 9 16 x 25 x 2 9 16 x 25 x 2...

Страница 80: ...entrifugal Fan diameter in 18 x 15 15 X 11 18 x 15 15 X 11 18 x 15 15 X 11 18 x 15 15 X 11 Medium Static Motor qty Belt qty Drive type 1 1 Belt 1 1 Belt 1 1 Belt 1 1 Belt Nominal nameplate HP 3 7 3 7...

Страница 81: ...e 3 direct 3 direct 4 direct 4 direct Motor HP RPM 1 4 1100 1 4 1100 1 4 1100 1 4 1100 Fan diameter in 22 22 22 22 FILTERS RA filter size in 6 20 x 25 x 2 6 20 x 25 x 2 6 20 x 25 x 2 6 20 x 25 x 2 OA...

Страница 82: ...6 9 7 0 8 3 RPM Range 835 1021 835 1021 755 923 755 923 Max blower shaft RPM 1100 1100 1100 1100 Motor frame size 184T 184T 184T 184T Fan qty Type 2 Centrifugal 2 Centrifugal 2 Centrifugal 2 Centrifug...

Страница 83: ...115 195 115 195 115 195 115 Temperature rise 30 60 30 60 30 60 30 60 30 60 HIGH of stages of burners total 2 10 2 10 2 10 2 10 2 10 Connection size 3 4 in NPT 3 4 in NPT 3 4 in NPT 3 4 in NPT 3 4 in...

Страница 84: ...closes 195 115 195 115 195 115 195 115 Temperature rise 30 60 30 60 30 60 30 60 HIGH of stages of burners total 2 10 2 10 2 10 2 10 Connection size 3 4 in NPT 3 4 in NPT 3 4 in NPT 3 4 in NPT Rollout...

Страница 85: ...804 2 78 863 3 24 6400 634 1 81 701 2 20 765 2 64 826 3 10 883 3 59 6750 662 2 07 725 2 49 787 2 94 846 3 42 902 3 92 7150 694 2 42 754 2 85 813 3 31 869 3 81 923 4 33 7500 722 2 74 779 3 19 836 3 67...

Страница 86: ...21 8300 787 3 62 839 4 09 891 4 61 941 5 16 990 5 73 8750 825 4 18 874 4 68 923 5 22 971 5 78 1018 6 38 CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP RPM BH...

Страница 87: ...50 1011 5 97 1055 6 44 9500 911 5 32 959 5 81 1005 6 30 1048 6 79 1090 7 29 10000 954 6 15 1000 6 66 1044 7 18 1086 7 70 1126 8 22 CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 RPM...

Страница 88: ...5 6 05 10000 934 4 85 986 5 36 1035 5 88 1082 6 40 1126 6 93 10650 988 5 78 1038 6 33 1084 6 88 1129 7 44 1172 8 00 11250 1038 6 74 1086 7 32 1130 7 91 1173 8 49 11900 1093 7 91 1138 8 52 1181 9 14 12...

Страница 89: ...71 11 64 13750 1249 11 97 1289 12 67 CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 8250 1056 5 05 1101 5 51 1144 5 98 1185 6 45 1225 6 93 895...

Страница 90: ...600 2 13 664 2 73 723 3 37 776 4 05 825 4 76 6000 629 2 47 691 3 10 747 3 77 799 4 48 6400 663 2 91 721 3 57 776 4 28 6750 693 3 34 749 4 03 801 4 76 7150 727 3 88 781 4 61 7500 757 4 40 CFM AVAILABL...

Страница 91: ...792 5 06 841 5 85 888 6 68 933 7 54 8300 827 5 78 874 6 61 920 7 47 8750 867 6 69 912 7 55 CFM AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 525...

Страница 92: ...954 6 10 998 6 81 8500 843 4 73 896 5 45 945 6 18 991 6 93 1034 7 68 9000 886 5 52 937 6 28 984 7 06 1029 7 84 1071 8 63 9500 929 6 40 978 7 21 1024 8 02 1067 8 84 10000 973 7 38 1020 8 22 1064 9 08...

Страница 93: ...00 886 5 52 937 6 28 984 7 06 1029 7 84 1071 8 63 9500 929 6 40 978 7 21 1024 8 02 1067 8 84 10000 973 7 38 1020 8 22 1064 9 08 10500 1017 8 45 1062 9 33 11000 1061 9 63 11500 CFM AVAILABLE EXTERNAL S...

Страница 94: ...tandard Static 954 934 913 893 873 853 832 812 792 771 751 Medium Static 1175 1155 1135 1114 1094 1074 1054 1034 1013 993 973 High Static 1299 1271 1242 1214 1185 1157 1129 1100 1072 1043 1015 Factory...

Страница 95: ...84 F D20 208 230 3 60 50HE500751 K 50HE500889 L 50HE502181 F 50HE502186 D 460 3 60 50HE500752 L 50HE502183 F 575 3 60 50HE500888 L 50HE502184 F D24 208 230 3 60 50HE500751 K 50HE500889 L 50HE502181 F...

Страница 96: ...96 Fig C 48TC D17 D30 Control Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS...

Страница 97: ...97 Fig D 48TC D17 D30 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS...

Страница 98: ...98 Fig E 48TC D17 D30 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS...

Страница 99: ...99 Fig F 48TC D17 D30 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS...

Страница 100: ...100 Fig G 48TC D17 D30 Control Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 101: ...101 Fig H 48TC D17 D30 Power Diagram 208 230 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 102: ...102 Fig I 48TC D17 D30 Power Diagram 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 103: ...103 Fig J 48TC D17 D30 Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 104: ...104 Fig K PremierLink System Control Wiring Diagram APPENDIX D WIRING DIAGRAMS...

Страница 105: ...105 Fig L PremierLink System Control Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 106: ...106 Fig M RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS...

Страница 107: ...107 Fig N RTU OPEN Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...

Страница 108: ...108 Fig O Motormaster Sensor Locations D17 D20 and D24 Fig P Motormaster Sensor Location D28 D30 SENSOR LOCATION SENSOR LOCATION APPENDIX E MOTORMASTER SENSOR LOCATIONS...

Страница 109: ......

Страница 110: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480288 01 Printed in U S A Form 48TC 17 30 02SM Pg 110 10 2020 Replace...

Страница 111: ...door air filters are clean and in place Y N _____ Verify that unit installation is level Y N _____ Check fan wheels and propeller for location in housing orifice and setscrew tightness Y N _____ Check...

Страница 112: ...pressure _______________ PSIG C Entering air temperature _______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N _____ F Ch...

Отзывы: