38
RTU
−
OPEN CONTROL SYSTEM
The RTU (Roof Top Unit) Open controller is an integrated
component of the Carrier rooftop unit. Its internal
application programming provides optimum performance
and energy efficiency. RTU Open enables the unit to run
in 100% stand
−
alone control mode, Carrier’s I
−
Vu Open
network, or a Third Party Building Automation System
(BAS). On
−
board DIP switches allow you to select your
protocol (and baud rate) of choice among the four most
popular protocols in use today: BACnet, Modbus, Johnson
N2 and LonWorks.
The RTU Open control is factory
−
mounted in the 48TC
unit’s main control box, to the left of the Light
Commercial Terminal Board (LCTB). See Fig. 45.
Factory wiring is completed through harnesses connected
to the LCTB. Field connections for RTU Open sensors
will be made at the Phoenix connectors on the RTU Open
board. The factory
−
installed RTU Open control includes
the supply
−
air temperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er2 package.
Sensory/Accessory Installation
There are a variety of sensors and accessories available
for the RTU
−
OPEN. Some of these can be factory or field
installed, while others are only field installable. The
RTU
−
OPEN controller may also require connection to a
building network system or building zoning system. All
field control wiring that connects to the RTU
−
OPEN must
be routed through the raceway built into the corner post of
the unit or secured to the unit control box with electrical
conduit. The unit raceway provides the UL required
clearance between high and low
−
voltage wiring. Pass the
control wires through the hole provided in the corner post,
then feed the wires thorough the raceway to the
RTU
−
OPEN. Connect the wires to the removable Phoenix
connectors and then reconnect the connectors to the board.
IMPORTANT
: Refer to the specific sensor or accessory
instructions for its proper installation and for rooftop unit
installation refer to base unit installation instructions and
the unit’s wiring diagrams.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death, and/or equipment damage.
Disconnect and lockout/tagout electrical power before
wiring the RTU
−
OPEN controller.
!
WARNING
Additional RTU
−
OPEN Installation and
Troubleshooting
Additional installation, wiring and troubleshooting
information for the RTU
−
OPEN Controller can be found
in the following manuals:
“Controls, Start
−
up, Operation
and Troubleshooting Instructions,”
and
“RTU Open
Installation and Start
−
up Guide.”
Содержание 48TC 17 Series
Страница 39: ...39 C10818 Fig 45 RTU OPEN Control Module ...
Страница 82: ...82 APPENDIX IV WIRING DIAGRAMS cont C12615 Fig 73 48TC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Страница 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C12616 Fig 74 48TC D17 D28 Power Diagram 208 230 3 60 ...
Страница 84: ...84 APPENDIX IV WIRING DIAGRAMS cont C12266 Fig 75 48TC D17 D28 Power Diagram 460 3 60 ...
Страница 85: ...85 APPENDIX IV WIRING DIAGRAMS cont C12618 Fig 76 48TC D17 D28 Power Diagram 575 3 60 ...
Страница 86: ...86 APPENDIX IV WIRING DIAGRAMS cont C14061 Fig 77 48TC D17 D28 Control Diagram with Humidi MiZer ...
Страница 87: ...87 APPENDIX IV WIRING DIAGRAMS cont C12620 Fig 78 48TC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer ...
Страница 88: ...88 APPENDIX IV WIRING DIAGRAMS cont C12621 Fig 79 48TC D17 D28 Power Diagram 460 3 60 with Humidi MiZer ...
Страница 89: ...89 APPENDIX IV WIRING DIAGRAMS cont C12622 Fig 80 48TC D17 D28 Power Diagram 575 3 60 with Humidi MiZer ...
Страница 91: ...91 APPENDIX IV WIRING DIAGRAMS cont C13766 Fig 82 PremierLinkt System Control Wiring Diagram with Humidi MiZer ...
Страница 92: ...92 APPENDIX IV WIRING DIAGRAMS cont C13767 Fig 83 RTU OPEN Wiring Diagram ...
Страница 93: ...93 APPENDIX IV WIRING DIAGRAMS cont C13768 Fig 84 RTU OPEN Wiring Diagram with Humidi MiZer ...