background image

12

Step 5 — 

Field Fabricate Ductwork

NOTE:  Cabinet  return-air  static  pressure  (a  negative  condition)

shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in.

wg (112 Pa) without economizer.

For vertical ducted applications, secure all ducts to roof curb and

building structure. Do not connect ductwork to unit.

Fabricate supply ductwork so that the cross sectional dimensions

are equal to or greater than the unit supply duct opening dimen

-

sions for the first 18-in. (458 mm) of duct length from the unit

basepan.

Insulate and weatherproof all external ductwork, joints, and roof

openings with counter flashing and mastic in accordance with ap

-

plicable codes.

Ducts  passing  through  unconditioned  spaces  must  be  insulated

and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be

ducted through the roof deck to comply with applicable fire codes.

Step 6 — 

Rig and Place Unit

When the unit is ready to be rigged and no longer will be lifted by

a fork truck, the wood protector under the basepan must be re

-

moved. Remove 4 screws from each base rail. Wood protector will

drop to the ground. See instructions on the unit base rails.

Keep unit upright and do not drop. Spreader bars are not required.

Rollers may be used to move unit across a roof. Level by using

unit frame as a reference. See Table 2 and Fig. 7 for additional in

-

formation.

Lifting holes are provided in base rails as shown in Fig. 7. Refer to

rigging instructions on unit.

Rigging  materials  under  unit  (cardboard  or  wood)  must  be  re

-

moved PRIOR to placing the unit on the roof curb.

When  using  the  standard  side  drain  connection,  ensure  the  red

plug in the alternate bottom connection is tight. Do this before set

-

ting the unit in place. The red plug can be tightened with a 

  1

/

2

-in.

square socket drive extension. For further details, see “Install Ex

-

ternal Condensate Trap and Line” on page 18.

Before setting the unit onto the curb, recheck gasketing on curb.

NOTES:

1. Dimensions in ( ) are in millimeters.

2.

Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity.

3. Use wooden top to prevent rigging straps from damaging unit.

Fig. 7 — 

Rigging Details

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in damage to roofing

materials.

Membrane roofs can be cut by sharp sheet metal edges. Be

careful when placing any sheet metal parts on such roof.

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.

All panels must be in place when rigging. Unit is not designed

for handling by fork truck when packaging is removed.

If using top crate as spreader bar, once unit is set, carefully

lower wooden crate off building roof top to ground. Ensure

that no people or obstructions are below prior to lowering the

crate.

DETAIL “A”

PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING 
UNIT ON ROOF CURB.

DUCT END

SEE DETAIL “A”

914 - 1371

( 36” - 54” )

“B”

“A”

“C”

UNIT

MAX WEIGHT

DIMENSIONS

A

B

C

LB

KG

IN

MM

IN

MM

IN

MM

48LC*008

2460

1116

116

2945

57

1448

59.5

1510

48LC*009

2465

1118

116

2945

58

1473

59.5

1510

48LC*012

2465

1118

116

2945

58

1473

59.5

1510

Содержание 48LC Series

Страница 1: ... Factory Installed Option 31 SystemVu Controller Factory Installed Option 31 Integrated Staging Control ISC Board 32 ISC BOARD SEQUENCE OF OPERATION EconoMi er X Factory Option 34 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS INTERFACE OVERVIEW SETUP AND CONFIGURATION ENTHALPY SETTINGS TWO SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING Staged Air Volu...

Страница 2: ...ctives ne sont pas suivies cela peut entraîner des blessures graves ou une intoxication au monoxyde de carbone pouvant causer la mort si des produits de combustion s infil trent dans le bâtiment Vérifier que toutes les ouvertures pratiquées dans le mur ex térieur autour du ou des tuyaux d évent et de la prise d air sont scellées de manière à empêcher l infiltration de produits de combustion dans l...

Страница 3: ...cy rating for the units covered in this document WARNING FIRE HAZARD Failure to follow this warning could result in severe personal injury and or property damage Manifold pressure tap set screw must be tightened and 1 8 in NPT pipe plug must be installed to prevent gas leaks MANIFOLD GAS VALVE MANIFOLD PRESSURE TAP SET SCREW Table 1 Rated Indoor Airflow cfm MODEL NUMBER FULL LOAD AIRFLOW CFM 48LC ...

Страница 4: ...Cu Al Cu B Precoat Al Cu Al Cu C E coat Al Cu Al Cu D E coat Al Cu E coat Al Cu E Cu Cu Al Cu F Cu Cu Cu Cu M Al Cu Al Cu Louvered Hail Guard N Precoat Al Cu Al Cu Louvered Hail Guard P E coat Al Cu Al Cu Louvered Hail Guard Q E coat Al Cu E coat Al Cu Louvered Hail Guard R Cu Cu Al Cu Louvered Hail Guard S Cu Cu Cu Cu Louvered Hail Guard Voltage 1 575 3 60 5 208 230 3 60 6 460 3 60 Design Revisio...

Страница 5: ...5 Fig 2 Unit Dimensional Drawing Size 08 Unit ...

Страница 6: ...6 Fig 2 Unit Dimensional Drawing Size 08 Unit cont ...

Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 09 and 12 Units ...

Страница 8: ...8 Fig 3 Unit Dimensional Drawing Size 09 and 12 Units cont ...

Страница 9: ...rces of contaminated air Although unit is weatherproof avoid locations that permit water from higher level runoff and overhangs to fall onto the unit Select a unit mounting system that provides adequate height to al low installation of condensate trap per requirements Refer to In stall External Condensate Trap and Line on page 18 for required trap dimensions ROOF MOUNT Check building codes for wei...

Страница 10: ...cessory roof curb in accordance with in structions shipped with the curb NOTE The gasketing of the unit to the roof curb is critical for a watertight seal Install gasket supplied with the roof curb as shown in Fig 6 Improperly applied gasket can also result in air leaks and poor unit performance Curb should be level This is necessary for unit drain to function properly Unit leveling tolerances are...

Страница 11: ...11 Fig 6 Roof Curb Details Size 08 12 Units ...

Страница 12: ...ging materials under unit cardboard or wood must be re moved PRIOR to placing the unit on the roof curb When using the standard side drain connection ensure the red plug in the alternate bottom connection is tight Do this before set ting the unit in place The red plug can be tightened with a 1 2 in square socket drive extension For further details see Install Ex ternal Condensate Trap and Line on ...

Страница 13: ...CRDUCTCV002A00 to cover the vertical supply duct opening Use the return duct cover removed from the unit end panel to cov er the vertical return duct opening Use the screws to install the covers on vertical duct openings with the insulation side down The panels must be inserted into the notches on the basepan to properly seal The notches are covered by the tape used to secure the insulation to the...

Страница 14: ...sory is to be installed on the unit the hood shipped with the unit will not be used and must be discarded Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be used as the top of the hood If the panel is still attached to the unit remove the screws along the sides and bottom of the panel See Fig 15 Fig 15 Indoor Coil Access Panel Relocation 2 Sw...

Страница 15: ...appli ances This unit is factory equipped for use with natural gas fuel at eleva tions up to 2000 ft 610 m above sea level Unit may be field con verted for operation at elevations above 2000 ft 610 m and or for use with liquefied petroleum fuel See accessory kit installation in structions regarding these accessories NOTE In U S A the input rating for altitudes above 2000 ft 610 m must be derated b...

Страница 16: ...ce the gasket over the embossed area in the basepan aligning the holes in the gasket to the holes in the basepan See Fig 21 5 Install the connector plate assembly to the basepan using 8 of the washer head screws NOTE If gas and or electrical connections are not going to occur at this time tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim...

Страница 17: ... Direct Drip Leg Fig 24 Gas Piping with Offset Drip Leg Fig 25 Gas Piping Thru Base Connections When installing the gas supply line observe local codes pertaining to gas pipe installations Refer to the NFPA 54 ANSI Z223 1 NFGC latest edition in Canada CAN CSA B149 1 In the ab sence of local building codes adhere to the following pertinent recommendations 1 Avoid low spots in long runs of pipe Grad...

Страница 18: ...pipe size smaller than the unit connection 3 4 in Fig 27 Condensate Drain Pan Side View Fig 28 Condensate Drain Piping Details Step 12 Make Electrical Connections NOTE Field supplied wiring shall conform with the limitations of minimum 63 F 33 C rise FIELD POWER SUPPLY For those units without through the curb power conduit must be used to route the main power from the condenser end via the power e...

Страница 19: ... switch or HACR Refer to Table 7 for maxi mum wire size at connection lugs Use copper wire only See Fig 33 NOTE TEST LEADS Unit may be equipped with short leads pigtails on the field line connection points off the optional non fused disconnect switch or HACR These leads are for factory run test purposes only remove and discard before connecting field power wires to unit connection points Make fiel...

Страница 20: ...deviation from average voltage AB 227 224 3 v BC 231 227 4 v AC 227 226 1 v Maximum deviation is 4 v Determine percent of voltage imbalance This amount of phase imbalance is satisfactory as it is below the maxi mum allowable 2 All units except 208 230 v units are factory wired for the voltage shown on the nameplate If the 208 230 v unit is to be connected to a 208 v power supply the control transf...

Страница 21: ...21 Fig 34 48LC 08 12 Electro mechanical Control Wiring Diagram ...

Страница 22: ...22 Fig 35 48LC 08 12 RTU Open Control Wiring Diagram ...

Страница 23: ...23 Fig 36 48LC 08 12 SystemVu Control Wiring Diagram ...

Страница 24: ...24 Fig 37 48LC 08 12 Typical Power Wiring Diagram Electromechanical and RTU Open Controls 208 230 v Unit Shown ...

Страница 25: ...25 Fig 38 48LC 08 12 Typical Power Wiring Diagram SystemVu Control 208 230 v Unit Shown ...

Страница 26: ...ig 2 and 3 2 Remove 3 hex screws on the NFD enclosure 2 on the face of the cover and 1 on the bottom see Fig 41 3 Remove the front cover of the NFD enclosure 4 Make sure the NFD shipped from the factory is at OFF position the arrow on the black handle knob is at OFF 5 Insert the shaft with the cross pin on the top of the shaft in the horizontal position 6 Measure the tip of the shaft to the top su...

Страница 27: ... a hinged waterproof access cover located on the panel be neath the control box See Fig 44 and 45 Non powered type This type requires the field installation of a general purpose 125 volt 15 A circuit powered from a source elsewhere in the building Observe national and local codes when selecting wire size and conduit requirements fuse or breaker requirements and disconnect switch size and location ...

Страница 28: ...ctory mounted due to its depth it must be installed at unit in stallation For shipment the convenience outlet is covered with a blank cover plate The weatherproof cover kit is shipped in the unit s control box The kit includes the hinged cover a backing plate and gasket DISCONNECT ALL POWER TO UNIT AND CONVE NIENCE OUTLET LOCK OUTAND TAG OUTALL POWER Remove the blank cover plate at the convenience...

Страница 29: ...ly from the L bracket and discard the L bracket but retain the washer head screws and the gasket located between the L bracket and the connector plate assembly NOTE Take care not to damage the gasket as it is reused in the following step 3 Place the gasket over the embossed area in the basepan aligning the holes in the gasket to the holes in the basepan See Fig 50 4 Install the connector plate ass...

Страница 30: ...re that it will not be damaged by con tact with the condenser coil See Fig 52 Fig 52 Thermostat Wire Routing NOTE If thru the bottom connections accessory is used refer to the accessory installation instructions for information on routing power and control wiring HEAT ANTICIPATOR SETTINGS Set heat anticipator settings at 0 14 amp for the first stage and 0 14 amp for second stage heating when avail...

Страница 31: ...stat RTU Open Controller Factory Installed Option For details on operating 48LC 08 09 12 units equipped with the factory installed RTU Open option refer to 48 50LC 07 26 Facto ry Installed Option RTU Open Multi Protocol Controller Con trols Start up Operation and Troubleshooting manual SystemVu Controller Factory Installed Option For details on operating 48LC 08 09 12 units equipped with the facto...

Страница 32: ...ED05 1 Check Smoke Detector PMR AUX RED Blinking Green LED Note 1 2 Check HPS LPS COFS RED RED 3 Call for Y3 with no call for Y1 Check Y1 wiring RED 4 Call for Y3 with no call for Y1 Y2 Check Y1 wiring RED RED 5 Call for Y2 with no call for Y1 Check Y1 wiring RED RED 6 Call for W2 with no call for W1 Check W1 wiring RED RED 7 Call for heat W1 W2 and cooling Y1 Y2 Y3 Check thermostat wiring RED RED...

Страница 33: ...economizer will modu late the outdoor air damper to provide a 50 F 10 C to 55 F 13 C mixed air temperature into the zone and run the indoor fan at high speed As mixed air temperature fluctuates above 55 F 13 C or below 50 F 10 C dampers will be modulated open or close to bring the mixed air temperature back within control Upon more call for cooling Y2 on the thermostat the outdoor air damper will ...

Страница 34: ...delay will not change back to 45 seconds unless power is reset to the control ALED indicator is provided on the IGC to monitor operation When additional heat is required W2 closes and initiates power to the second stage of the main gas valve When the thermostat is sat isfied the gas valve closes interrupting the flow of gas to the main burners EconoMi er X Factory Option The EconoMi er X system is...

Страница 35: ...perature accuracy 0 F 2 F Temperature and Humidity C7400S1000 optional S Bus 2 wire 18 to 22AWG Temperature range 40 F to 150 F 40 C to 65 C Temperature accuracy 0 F 2 F Humidity range 0 to 100 RH with 5 accuracy NOTE Up to three 3 S Bus sensors may be connected to the W7220 economizer module for outdoor air OA return air RA and discharge supply air DA 4 Binary Inputs 1 wire 24 vac common GND see ...

Страница 36: ... BUS S BUS S BUS Sylk Bus Enthalpy Control Sensor Polarity Insensitive Connection Bottom Left Terminal Block IAQ 2 10 2 10 vdc Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output Common ACT 24v 24 vac Damper Actuator 24 vac Source Table 11 E...

Страница 37: ... button causes the display to automatically increment or decrement 1 Press the Enter button to accept the displayed value and store it in nonvolatile RAM CHANGE STORED displays 2 Press the Enter button to return to the current menu parameter 3 Press the Menu Up Exit button to return to the previ ous menu Menu Structure Table 14 illustrates the complete hierarchy of menus and parame ters for the Ec...

Страница 38: ... and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F or _ _ _ C 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature Displays _ _ _F if sensor sends invalid value short or out of range OA HUM _ _ 0 to 100 OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of out...

Страница 39: ...halpy curves DCV SET 1100ppm 500 to 2000 ppm increment by 100 DEMAND CONTROLLED VENTILATION Displays only if CO2 sensor is connected Set point for Demand Controlled Ventilation of space Above the set point the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the set point MIN POS 2 8 V 2 to 10 vdc VENTILATION MINIMUM POSITION Displays ONLY if a CO2 sensor...

Страница 40: ...c out for second exhaust fan SYS use output as an alarm signal OCC INPUT INPUT or ALWAYS OCCUPIED MODE BY EXTERNAL SIGNAL When using a setback thermostat with occupancy out 24 vac the 24 vac is input INPUT to the OCC terminal If no occupancy output from the thermostat then change program to ALWAYS OR add a jumper from terminal R to OCC terminal FACTORY DEFAULT NO NO or YES Resets all set points to...

Страница 41: ...he fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1 O N A N A Energizes the AUX output If Aux setting is NONE no action taken ERV 24 vac out Turns on or signals an ERV that the conditions are not good for economizing but are for ERV operation SYS 24 vac out Issues a system alarm CONNECT EXH1 N A N A Closes the power ...

Страница 42: ...ed indoor fan with or without DCV see Tables 20 and 21 For enthal py operation with a 2 speed indoor fan with or without DCV see Tables 22 and 23 ALARMS CONT FREEZE ALARM N A N A Check if outdoor temperature is below the LOW Temp Lockout on set point menu Check if Mixed air temperature on STATUS menu is below the Lo Set point on Advanced menu When conditions are back in normal range the alarm will...

Страница 43: ...ENTILATION DCV OUTSIDE AIR GOOD TO ECONOMIZE Y1 I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v On 24 v On VENTMIN Closed Yes Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Off VENTMIN to Full...

Страница 44: ...CUPIED UNOCCUPIED Below CO2 set No Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 24 v On 0 v Off VENTMIN Closed On On High 24 v On 24 v On VENTMIN Closed Yes Off Off High 0 v Off 0 v Off VENTMIN Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open Closed to Full Open On On High 24 v On 0 v Off VENTMIN to Full Open Closed to Full Open Above CO2 set No Off Off High 0 v Off 0 v Off VENTM...

Страница 45: ...I Y2 I FAN SPEED Y1 O Y2 O OCCUPIED UNOCCUPIED Below CO2 Set No OFF OFF LOW 0v Off 0v Off VENTMIN Closed ON OFF LOW 24v On 0v Off VENTMIN Closed ON ON HIGH 24v On 24v On VENTMIN Closed Yes OFF OFF LOW 0v Off 0v Off VENTMIN Closed ON OFF LOW 0v Off 0v Off VENTMIN to Full Open Closed to Full Open ON ON HIGH 24v On 0v Off VENTMIN to Full Open Closed to Full Open Above CO2 Set No OFF OFF LOW 0v Off 0v...

Страница 46: ...tus to determine the speed of the supply fan and controls the OAdamper to the required posi tion see Table 24 The W heating mode is not controlled by the W7220 but it re quires the status to know where to position the OA damper for minimum position for the fan speed The 2 speed fan delay is available when the system is pro grammed for 2 speed fan in the System Setup menu item The 2 speed fan delay...

Страница 47: ...rs 3 Press the Enter button to start the test The unit pauses and then displays IN PROGRESS When the test is complete DONE appears 4 When all desired parameters have been tested press the Menu Up button to end the test The Checkout tests can all be performed at the time of installation or at any time during the operation of the system as a test that the system is operable TROUBLESHOOTING Alarms Th...

Страница 48: ...heating operation see Fig 64 and 65 Per ASHRAE 90 1 2016 during the first stage of cooling operation the SAV system will adjust the fan motor to provide 66 of the design airflow rate for the unit When the call for the second stage of cooling is required the SAV system will allow the design airflow rate for the unit established 100 During the heating mode the SAV system will allow total design airf...

Страница 49: ...tion in the figure above indicates motor direction The arrow point either clockwise or counter clockwise to show the motor s current direction 5 The position of the triangle indicates the currently selected menu Status Quick Menu or Main Menu Off Reset Hand On Alarm Warn On Com OK B a c k Auto On Status Menu Quick Menu Main Menu 1 20 Motor Power 2 0 12KW 0 16HP Setup 1 ALPHA NUMERIC DISPLAY MENU K...

Страница 50: ...le to the VFD 2 Connect the female end of the cable to the back panel of the VFD Remote keypad Secure the cable to the remote keypad using the 2 remaining screws from the kit PROGRAM THE VFD FOR 3 DISCRETE INDOOR FAN SPEEDS NOTE This procedure requires use of the VFD Keypad which is included as part of the field installed Multi Speed VFD display kit PN CRDISKIT002A00 If the VFD keypad is not alrea...

Страница 51: ...lowing display appears f Press OK to highlight the number in the bracket g Press Down Arrow until the following display appears h Press OK i Press Off Reset The Alarm indicator disappears 4 Entering Grid Type a Press the Menu key to move the triangle icon so it is positioned over Main Menu The display shows the following b Press OK twice the display changes to c Press Down Arrow three times to rea...

Страница 52: ...he and Up and Down Arrow keys to select the number provided in Tables 26 28 Press OK again to set the selected value g Press Down Arrow twice the following display appears h Press OK to highlight the number in the bracket and then use the and Up and Down Arrow keys to select the number provided in Table 26 28 Press OK again to set the selected value i Press the Back key once the following display ...

Страница 53: ...e following display appears f Press Down Arrow again the following display appears NOTE Press OK to highlight the Hz value and then use the and Up and DownArrow keys to enter the required values g Press Down Arrow once the following display appears NOTE Press OK to highlight the value and then use the and Up and Down Arrow keys to enter the required value See Tables 26 28 for proper selection of t...

Страница 54: ...ghlight the number in the bracket g Use the and Up and DownArrow keys to change the number to 3 for 3 automatic resets and then press OK The display changes to h Press Down Arrow once the following display appears i Press OK to highlight the number of seconds and use the and Up and Down Arrow keys to select 600 sec onds Press OK again to set the selected value j Press the Back key once the followi...

Страница 55: ...31N0227 1 132 11 575 60 4 9 1710 ULTRA 208 230V HD60FK658 HK30WA372 131L9797 1 102 13 230 60 13 6 1745 460V HD60FK658 HK30WA379 131L9866 1 122 13 460 60 6 8 1745 575V HD60FE576 HK30WA387 134F0217 1 132 13 575 60 6 0 1745 START DELAY SEC FLYING START MIN SPEED FOR FUNCTION Hz MOTOR THERMAL PROTECTION PRESET REFERENCE Motor Option Voltage 1 71 1 73 1 82 1 90 3 10 0 3 10 1 3 10 2 3 10 3 3 10 4 3 10 5...

Страница 56: ...10 0 60 3 600 0 575V 2 10 0 60 3 600 0 HIGH 208 230V 2 10 0 60 3 600 0 460V 2 10 0 60 3 600 0 575V 2 10 0 60 3 600 0 ULTRA 208 230V 2 10 0 60 3 600 0 460V 2 10 0 60 3 600 0 575V 2 10 0 60 3 600 0 Table 27 VFD Unit Parameters 48LC 09 Units REGIONAL SETTINGS GRID TYPE MOTOR POWER MOTOR VOLTAGE MOTOR FREQUENCY Hz MOTOR CURRENT MUST HOLD AMPS MOTOR NOMINAL SPEED RPM Motor Option Voltage Motor P N VFD ...

Страница 57: ... 18 DIGITAL INPUT TERMINAL 19 DIGITAL INPUT TERMINAL 27 DIGITAL INPUT TERMINAL 29 DIGITAL INPUT Motor Option Voltage 3 41 3 42 4 18 5 10 5 11 5 12 5 13 STD 208 230V 10 00 10 00 100 8 16 17 18 460V 10 00 10 00 100 8 16 17 18 575V 10 00 10 00 100 8 16 17 18 MID 208 230V 10 00 10 00 100 8 16 17 18 460V 10 00 10 00 100 8 16 17 18 575V 10 00 10 00 100 8 16 17 18 HIGH 208 230V 10 00 10 00 100 8 16 17 18...

Страница 58: ...100 100 0 0 0 575V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 MID 208 230V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 460V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 575V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 HIGH 208 230V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 460V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 575V 2 0 1 1 0 4 0 66 50 66 50 100 100 0 0 0 RAMP UP TIME SEC RAMP DOWN TIME SEC CURRENT LIMIT TERM...

Страница 59: ...ensor module at unit installation See Fig 74 for the as shipped location COMPLETING INSTALLATION OF RETURN AIR SMOKE SENSOR 1 Unscrew the two screws holding the return air smoke detector assembly See Fig 75 Step 1 Save the screws 2 Turn the assembly 90 degrees and then rotate end to end Make sure that the elbow fitting is pointing down See Fig 75 Step 2 3 Screw the sensor and detector plate into i...

Страница 60: ... leys Measure the distance between the motor shaft and the blower shaft 2 Set the tension gage to the desired tension see Table 1 in Fig 76 Place the large O ring at that point 3 Press the tension checker downward on the belt until the large O ring is at the bottom of the straightedge 4 Adjust the belt tension as needed Adjust belt tension by loosing the motor mounting plate front bolts and rear b...

Страница 61: ......

Страница 62: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480301 01 Printed in U S A Form 48LC 8 12 07SI Pg 62 5 2020 Replaces 48LC 8 12 06SI 2020 Carrier ...

Страница 63: ...air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y N _____ Verify that unit is level Y N _____ Check fan wheels and propeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotating in the correct direction Y N _____...

Страница 64: ...______ PSIG C Entering air temperature _______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N _____ F Check for correct ramp up of outdoor fan motor as condenser coil warms Y N _____ 4 Check unit charge per charging chart Y N _____ Jumper 32L Motormaster temperature sensor during this check Remove jumper when complete 5 ...

Отзывы: