11
Fig. 17 —
TXV Valve and Sensing Bulb Location
Refrigerant System Pressure Access Ports
There are two access ports in the system: on the suction tube
near the compressor and on the discharge tube near the com
-
pressor. These are brass fittings with black plastic caps. The
hose connection fittings are standard 1/4-in. SAE male flare
couplings.
The brass fittings are two-piece high flow valves, with a recep
-
tacle base brazed to the tubing and an integral spring-closed
check valve core screwed into the base. See Fig. 18. This check
valve is permanently assembled into this core body and cannot
be serviced separately; replace the entire core body if neces
-
sary. Service tools are available from RCD that allow the re
-
placement of the check valve core without having to recover
the entire system refrigerant charge. Apply compressor refrig
-
erant oil to the check valve core’s bottom o-ring. Install the fit
-
ting body with 96 ± 10 in.-lb (10.85 ± 1.1 Nm) of torque; do
not over-tighten.
Fig. 18 —
CoreMax
1
Access Port Assembly
TXV SENSING
BULB
CLAMP
THERMAL EXPANSION
(TXV) VALVE
SENSING BULB INSULATION REMOVED FOR CLARITY
1. CoreMax is a registered trademark of Fastest, Inc.
5/8
” HEX
0.47
30°
0.596
1/2-20 UNF RH
1/2
” HEX
45°
WA
S
HER
O-RING
7/16-20 UNF RH
DEPRE
SS
OR PER AHRI 720
+.01/-.035
FROM FACE OF BODY
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
S
EAT
CORE
(Part No. EC39EZ067)
Содержание 48JC04-06
Страница 15: ...15 Fig 26 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab...
Страница 30: ...30 Fig 52 Integrated Gas Controller IGC Board RED LED STATUS...
Страница 64: ...64 APPENDIX D WIRING DIAGRAMS Fig B 48JC 04 06 Control Wiring Diagram...
Страница 65: ...65 APPENDIX D WIRING DIAGRAMS Fig C 48JC 04 06 Power Wiring Diagram 208 230 460 3 60...