FAN PERFORMANCE
GENERAL FAN PERFORMANCE NOTES
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference
between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean fil
-
ters, unit casing, high gas heat (on gas heat models) and
wet coils.
4. Factory options and accessories may effect static pressure
losses. Gas heat unit fan tables assume high gas heat mod
-
els, for fan selections with low or medium heat models, the
user must deduct low and medium heat static pressures.
Selection software is available, through your salesperson,
to help you select the best motor/drive combination for
your application.
5. The Fan Performance tables offer motor/drive recommen
-
dations. In cases when two motor/drive combinations
would work, the lower horsepower option is recom
-
mended.
6. The EPACT (Energy Policy Act of 1992) regulates energy
requirements for specific types of indoor fan motors.
Motors regulated by EPACT include any general purpose,
T-frame (three-digit, 143 and larger), single-speed, foot
mounted, polyphase, squirrel cage induction motors of
NEMA (National Electrical Manufacturers Association)
design A and B, manufactured for use in the United
States. Ranging from 1 to 200 Hp, these continuous-duty
motors operate on 230 and 460 volt, 60 Hz power. If a
motor does not fit into these specifications, the motor
does not have to be replaced by an EPACT compliant
energy-efficient motor. Variable-speed motors are exempt
from EPACT compliance requirements.
Содержание 48JC04-06
Страница 15: ...15 Fig 26 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab...
Страница 30: ...30 Fig 52 Integrated Gas Controller IGC Board RED LED STATUS...
Страница 64: ...64 APPENDIX D WIRING DIAGRAMS Fig B 48JC 04 06 Control Wiring Diagram...
Страница 65: ...65 APPENDIX D WIRING DIAGRAMS Fig C 48JC 04 06 Power Wiring Diagram 208 230 460 3 60...