9
Fan Status
If a Fan Status accessory was field installed, the unit must be
configured for it by setting
Configuration
→
UNIT
→
FN.SW
to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
IMPORTANT
: Fan Status input is not on the terminals marked
Fan Status.
Filter Status
If a Filter Status accessory was field installed, the unit must be
configured for it by setting
Configuration
→
UNIT
→
FL.SW
to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Table 4 — Setting an Occupied Time Schedule - Weekdays Only for 7:30 to 22:30
DISPLAY
MENU
SUB
SUB
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
TIMECLOCK
SCH.L
ENTER
Local Occupancy Schedule
PER.1
ENTER
OCC.1
Period Occupied Time
ENTER
00.00
Scrolling stops
ENTER
00.00
Hours Flash
Y
07.00
Select 7
ENTER
07.00
Change accepted, minutes flash
Y
07.30
Select 30
ENTER
07.30
Change accepted
ESCAPE
OCC.1
07.30
Period Occupied Time
Item/Value/Units scrolls again
B
UNC.1
00.00
Period Unoccupied Time
ENTER
00.00
Scrolling stops
ENTER
00.00
Hours Flash
Y
22.00
Select 22
ENTER
22.00
Change accepted, minutes flash
Y
22.30
Select 30
ENTER
22.30
Change accepted
ESCAPE
UNC.1
22.30
Period Unoccupied Time
Item/Value/Units scrolls again
B
MON.1
NO
Monday In Period
ENTER
NO
Scrolling stops
Y
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
MON.1
YES
Monday In Period
Item/Value/Units scrolls again
B
TUE.1
NO
Tuesday In Period
ENTER
NO
Scrolling stops
Y
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
TUE.1
YES
Tuesday In Period
Item/Value/Units scrolls again
B
WED.1
NO
Wednesday In Period
ENTER
NO
Scrolling stops
Y
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
WED.1
YES
Wednesday In Period
Item/Value/Units scrolls again
B
THU.1
NO
Thursday In Period
ENTER
NO
Scrolling stops
Y
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
THU.1
YES
Thursday In Period
Item/Value/Units scrolls again
B
FRI.1
NO
Friday In Period
ENTER
NO
Scrolling stops
Y
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
FRI.1
YES
Friday In Period
Item/Value/Units scrolls again
ESCAPE
ESCAPE
48/
50P
D