Optimal Start

The RTU--OPEN may utilize Optimal Start, which adjusts

the effective setpoints to achieve the occupied setpoints

by the time scheduled occupancy begins. The Optimal

Start recovery period may begin as early as 4 hours prior

to occupancy. The algorithm works by moving the

unoccupied setpoints toward the occupied setpoints. The

rate at which the setpoints move is based on the outside

air temperature, design temperatures, and capacities. The

following conditions must be true for unoccupied free

cooling to operate:

S

Under SETPOINT, Optimal Start Value must be set
greater than zero and less than or equal to four (0
disables Optimal Start.)

S

The system is unoccupied

S

The RTU--OPEN has a valid outside air temperature

S

The RTU--OPEN is running occupancy based on a
schedule, were next time occupied is known.

Fire Shutdown

Fire Shutdown may be configured on Binary Input 5. A

typical application involves a smoke detector or fire

shutdown contact, which, when active, immediately shuts

down equipment operation.

Compressor Safety

Compressor Safety may be configured on Binary Input 3.

A compressor safety tripped indicator circuit is available

on most Carrier rooftop equipment. A Compressor Safety

Alarm indicates that the equipment requires attention.

Cooling, heating, and supply fan outputs are not

interrupted except where the RTU--OPEN is configured

for Heat Pump operation. When configured for Heat

Pump, and in the heating mode, a compressor safety fault

will cause the available stages of electric heating to be

enabled in place of mechanical heating. Normal operation

resumes when the compressor safety circuit is

de--energized.

Fan Status

Fan Status may be configured on any unused binary input

channel. A typical application would be an airflow switch,

current sensing relay, or other device that provides a

supply fan running verification. Enabling this function

displays the supply fan’s status on the equipment graphic.

If the controller loses fan status during operation, heating

and cooling are disabled, the economizer damper (if

available) is closed, and an alarm for loss of status is

indicated. If the fan status is on when the controller is

commanding the fan off, the unit remains in the off state.

An alarm is generated indicating that the fan is running

when it should be off.

Filter Status

Filter status may be configured on any unused binary

input channel. A typical application is a differential

pressure switch that senses the pressure drop across a filter

bank. When the pressure across the filter bank exceeds the

setpoint of the differential pressure switch, the Filter

status is displayed as Dirty on the controller graphic. An

alarm indicates a dirty filter.

Door Switch

A Door Contact may be configured on any unused binary

input. A typical application is an occupancy sensor

mounted within the space served by a single zone rooftop.

Door Contact disables mechanical cooling and electric or

gas heating, when active. Economizer cooling, if

available, continues to operate.

Linkage

The RTU--OPEN may serve as an air source to an OPEN

Variable Volume Terminal (VVT) system. When the

RTU--OPEN is part of a VVT system and the controllers

are wired together to form a network, the controllers may

use a method of communication known as Linkage

t

.

Linkage is a method by which an air source and its

subordinate zone terminals exchange data to form a

coordinated HVAC system. The system’s air source

controller, zone controllers, and bypass controller are

linked so that their data exchange can be managed by one

zone controller configured as the VVT Master. The VVT

Master gathers the following information from the slave

zone controllers:

S

occupancy status

S

setpoints

S

zone temperature

S

relative humidity

S

CO

2

level

S

damper position

S

optimal start data

The VVT Master performs mathematical calculations and

algorithms on the data and then sends the composite

information to the air source. The VVT Master receives

information from the air source such as mode, supply air

temperature, and outside air temperature, and passes that

information to all linked controllers.

Linkage Air Source Modes

In a linked system, the air source determines its operating

mode and qualifies that mode based on its own Supply Air

Temperature (SAT). The following modes can be sent by

the air source depending on its configuration:

S

Off – Air source fan is off

S

Fan Only – Air source fan is on and providing
ventilation (neutral SAT) without heating or cooling

S

Economizer Cooling – Air source fan is on and
providing cooling, using economizer only

S

Cooling – Air source fan is on and cooling is provided
by economizer and mechanical cooling

S

Heating – Air source fan is on and heating is provided
(gas or electric)

S

Dehumidification – Air source fan is on and
Humidi--MiZer] is active

S

Test – The RTU Open Service Test mode is active

S

Shutdown – Air source fan is off due to Safety Chain,
Fire Shutdown, or invalid SAT sensor

S

Unocc Free Cooling – Air source fan is on, with the
economizer providing cooling while unoccupied

Содержание 48/50HC04---14

Страница 1: ...mpressor 2 Test 13 Heat 1 and Heat 2 Test 13 Reversing Valve Test 13 Dehumidification Test 14 Power Exhaust Test 14 Economizer Test 14 Analog Output 2 Test 14 Configuration 14 Setpoint 14 Unit 14 Inpu...

Страница 2: ...RNING GENERAL The RTU OPEN controller is an integrated component of the Carrier rooftop unit Its internal application programming provides optimum performance and energy efficiency RTU OPEN enables th...

Страница 3: ...3 C10818 Fig 1 RTU OPEN Control Module...

Страница 4: ...d S Space temperature sensor SPS SPPL SPP SPPF 33ZCT55SPT 33ZCT56SPT or 33ZCT59SPT S Indoor air quality sensor 33ZCSENCO2 33ZCT55CO2 33ZCT56CO2 required for demand control ventilation S Outdoor air qu...

Страница 5: ...5 C10819 Fig 2 Typical Factory Option Wiring...

Страница 6: ...rs and BACview6 must be addressed Use the jumpers on the SPS sensor s circuit board and refer to the BACview6 s installation instructions for addressing For Rnet wiring up to 500ft 152m use 18 AWG 4 c...

Страница 7: ...7 BLK RED SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION LEGEND Factory Wiring Field Wiring 1 2 C07133 Fig 5 Space Temperature Averaging C10820 Fig...

Страница 8: ...actory default control for the Humidi MiZert option To wire in the field S J5 8 24 VAC source for dry contact S J5 7 Signal input Single Enthalpy Outdoor Enthalpy The outdoor enthalpy switch receiver...

Страница 9: ...NIT SHUTDOWN Smoke Alarm Signal input to RTU OPEN NOTE Input 5 can also be wired into J5 3 Filter Status The filter status accessory is a field installed accessory This accessory detects plugged filte...

Страница 10: ...to the RTU OPEN is through plug J19 See Fig 13 for wiring Refer to the RTU OPEN 3rd Party Integration Guide for more detailed information on protocols 3rd party wiring and networking NOTE Power must...

Страница 11: ...ev J The speed of a Modbus network can range from 9600 to 76 8K baud Physical Addresses can be set from 01 to 99 Johnson N2 N2 is not a standard protocol but one that was created by Johnson Controls I...

Страница 12: ...ere is a 10 minute auto logout if a screen is left idle See Appendix A for navigation and screen content Virtual BACview Virtual BACview is a freeware computer program that functions as the BACview6 H...

Страница 13: ...Service Test function can be used to verify proper operation of compressors heating stages indoor fan power exhaust fans economizer and dehumidification Use of Service Test is recommended at initial...

Страница 14: ...upied Cooling Setpoint The cooling setpoint the controller maintains during the unoccupied period Range 55 99_F Effective Heating Setpoint The current setpoint value heating operation will control to...

Страница 15: ...nsor Default Enable Setpoint Adjustment Range Sets the slider range of a space sensor with built in function The slider is used to offset the control setpoint Range 0 5n_F Default 5n_F Cooling Lockout...

Страница 16: ...able on a specific unit Set this point to One Stage if there is one compressor in the specific unit set to Two Stage if there are two compressors in the unit and set to None if economizer cooling ONLY...

Страница 17: ...ing a local or OPEN schedule The push button will override an unoccupied period to occupied for the specified time duration BAS On Off When Occupancy Source is set to BAS On Off RTU OPEN follows occup...

Страница 18: ...ons must be true for economizer operation S Indoor Fan has been on for at least 30 seconds S Enthalpy is Low if the Enthalpy input is enabled S SAT reading is available S OAT reading is available S SP...

Страница 19: ...figured as one of the two analog input channels inputs 1 or 2 on J4 or a humidistat can be installed and configured as switch input 9 on J5 When using a relative humidity sensor to control dehumidific...

Страница 20: ...a differential pressure switch that senses the pressure drop across a filter bank When the pressure across the filter bank exceeds the setpoint of the differential pressure switch the Filter status i...

Страница 21: ...nsor To check accuracy use a high quality digital volt ohmmeter Connect the meter to the thermistor leads to obtain a resistance value Use Table 2 to convert that resistance to a temperature Next step...

Страница 22: ...per second Off Normal 2 flashes per second 2 flashes alternating with Run LED Five minute auto restart delay after system error 2 flashes per second 3 flashes then off Control module has just been for...

Страница 23: ...e value is less then the low allowed value or Space value is greater then the high allowed value Alarming Temperature spt_alrm_temp Shows temperature that caused alarm N A N A Alarm Limit Exceeded spt...

Страница 24: ...aced by Aux Heat Stage 2 The compressor output stays on when the safety alarm is present For cooling the alarm indicates the compressors are down Space Temp Sensor This alarm occurs if the space senso...

Страница 25: ...ndicates the space humidity falls below the alarm configuration Low Space Humidity Alarm Limit for 5 minutes This alarm is inhibited until the RTU runs for 5 minutes to allow for system stabilization...

Страница 26: ...and contain embedded information ORT These first three digits are unique to RTU OPEN and are used as an identifier YM These two digits identify the last digit of the year and month in hex A 10 Oct of...

Страница 27: ...vice Configuration Maintenance Alarms Linkage BACview Navigation STATUS MAINT ALARM BACnet LINKAGE SETPOINT Alarm Login Keypad Sched UserPw Weekly schedule Network Exceptions ClockSet ALARMS DST LINKA...

Страница 28: ...SETTINGS BACnet BACnet Device Instance xxxxxxx 1610100 Base BACnet Device ID xxxxxxx 1610100 Autogenerate Device ID Y N Y Keypad Keypad Configuration Inactivity Timeout 1 255 minutes 10 BACnet Write...

Страница 29: ...re sa_temp xxx F Outdoor Air Temperature oa_temp xxx F Space Relative Humidity space_rh 0 100 Indoor Air CO2 iaq 0 5000 ppm Outdoor Air CO2 oaq 0 5000 ppm Economizer Output econ_output 0 100 open LINK...

Страница 30: ...ty Set point unocc_de hum_stpt 30 100 rh 95 DCV Max Ctrl Setpoint iaq_stpt_max 0 9999 ppm 650 Power Exhaust Setpoint pexh_stpt 20 90 Open 50 Sched Weekly schedule MON SUN none BACview Only Exceptions...

Страница 31: ...lter Service Alarm Timer filter_service_hrs 0 9999 hr 600 Pushbutton Override pb_enable Disable En able Enable Setpoint Adjustment stpt_adj_enable Disable En able Enable Setpoint Adjustment Range stpt...

Страница 32: ...Contact Compressor Safety Input 3 Switch Configuration di3_type N O N C N O Input 5 Function di5_function 1 No Function 2 Fire Shut down 3 Fan Status 4 Filter Status 5 Remote Oc cupancy 6 Door Contac...

Страница 33: ...3 phase gas units HC04 09 3 phase gas units and All 12 30 gas units Continuous Occupied Exhaust occ_exh No Yes No Indoor CO2 Sensor Value Min mA iaq_ref_lo_ppm 0 9999ppm 0 Indoor CO2 Sensor Value Max...

Страница 34: ...ble Active Compressor Stages comp_run x Active Heat Stages heat_run x Enthalpy Status enthalpy_status High Low Humidistat Input Status humstat_status Low High Filter Status filter_status Clean Dirty D...

Страница 35: ...t_alrm_status Normal Alarm Alarming Temperature spt_alrm_temp xxx F Alarm Limit Exceeded spt_alrm_lmt xxx F High Supply Air Temperature sat_hi_alarm Normal Alarm Low Supply Air Temperature sat_lo_alar...

Страница 36: ...rete in 10030 BI 30 SNVT_switch 95 nvo CompSafety Compressor Safety Status R comp_status BV 1008 Continuous Occu pied Exhaust R W occ_exh BV 9002 Cooling Lockout Temperature R W oat_cl_lockout AV 9002...

Страница 37: ...R filter_status BV 1004 Fire Shutdown R fire_alarm BV 7007 discrete in 10032 BI 32 SNVT_switch 95 nvoFireShut down Fire Shutdown Status R fire down_status BV 1005 Heat Stage 1 Relay State R heat_1 BV...

Страница 38: ...Low Space Temp Alarm R spt_lo_alarm BV 7012 discrete in 10039 BI 39 SNVT_switch 95 nvo LoSpaceTemp Low Supply Air Tem perature R sat_lo_alarm BV 7021 discrete in 10040 BI 40 SNVT_switch 95 nvoLoSATAl...

Страница 39: ...emp_p 105 nviUnoc cCoolSP Setpoint Effective Cooling Setpoint R W eff_cl_stpt AV 4 Setpoint Effective Heating Setpoint R W eff_ht_stpt AV 5 Setpoint Heating Occupied Setpoint R W occ_ht_stpt AV 3002 f...

Страница 40: ...10024 BI 24 SNVT_switch 95 nvoFanStatus Switch Configuration R di_cfg_alarm BV 7025 System Cooling De mand Level R cool_de mand_level AV 9006 System Heating De mand Level R heat_de mand_level AV 9036...

Страница 41: ...y Setpoint occ_dehum_stpt 0 unocc setpoint rh 60 Unocc Relative Humidity Setpoint unocc_de hum_stpt 30 100 rh 95 DCV Max Ctrl Setpoint iaq_stpt_max 0 9999 ppm 650 Power Exhaust Setpoint pexh_stpt 20 9...

Страница 42: ...s 0 9999 hr 0 Filter Service Alarm Timer filter_service_hrs 0 9999 hr 600 Pushbutton Override pb_enable Disable Enable Enable Setpoint Adjustment stpt_adj_enable Disable Enable Enable Setpoint Adjustm...

Страница 43: ...Switch Configuration di3_type N O N C N O Input 5 Function di5_function 1 No Function 2 Fire Shutdown 3 Fan Status 4 Filter Status 5 Remote Occu pancy 6 Door Contact Fire Shutdown Input 5 Switch Confi...

Страница 44: ...s heat_stages 1 2 0 no heat 0 50 series cooling only units 1 All TCQs and HCQs Low Nox units single phase gas units TC04 09 low and TC05 07 med heat 3 phase gas units 2 TC04 and 08 09 med TC05 09 high...