GB - 8

Refrigerant connections

Connection to the unit

Insufficient tightening torque will cause gas leaks.
Overtightening the fittings will damage the tube flaring and cause
gas leaks.

         Tubing diameter

Torque

mm

(inches)

Nm

6.35

(1/4”)

18

9.52

(3/8”)

42

12.70

(1/2”)

55

Once all connections have been completed, check for leaks by
applying soapy water to them.

If incorrect connection or removal of the unit results in a refrigerant
gas leak, check the refrigerant charge as indicated in the
“OUTDOOR UNIT INSTALLATION MANUAL”.

Finally wrap connections with anti-condensate insulation and
tighten with tape, without exerting great pressure on the insulation.

Repair and cover any possible cracks in the insulation.

Connection pipes and electric cables between indoor and outdoor
units must be fixed to the wall with appropriate conduits.

Check

Pour water into the condensate drain pan and check that it flows
freely to the drain.

Make refrigerant connections before connecting the system to
the power supply.
Refer to the outdoor unit installation manual for tube sizing,
and limitations (slopes, length, number of curves allowed,
refrigerant charge, etc.)

           Tubing diameter

                              Gas                              Liquid

Model                     (Suction)                     (Discharge)

mm

(inches)

 mm

(inches)

009

9.52

(3/8”)

6.35

(1/4”)

012

12.70

(1/2”)

6.35

(1/4”)

014

12.70

(1/2”)

6.35

(1/4”)

018

12.70

(1/2”)

6.35

(1/4”)

024

12.70

(1/2”)

6.35

(1/4”)

• For refrigerant tubes use seamless, insulated refrigeration grade

tube, (Cu DHP type according to ISO 1337), degreased and
deoxidized, suitable for operating  pressures of at least 4200 kPa.
Under no circumstances use sanitary type copper pipe.

Note:
• Do not kink or flatten the tubes.
• Avoid bends with a bending radius of less than 100 mm.
• Do not bend copper tubes more than three times at the same point.
• Do not remove flare fittings from unit tubes before actually making

the connections.

• Do not fasten the insulation too tightly to the tubes with straps or

tape.

Flaring the end of the tubing

Remove protective caps from the copper tube ends. Position tube
end downward, cut the tube to the required length and remove the
burrs with a reamer.

Remove flare nuts from the unit connections and place them on the
tube end.
Flare the tube with a flaring tool.

Flare end must not have any burrs or imperfections.
The length of the flared walls must be uniform.

Finger-tighten the fitting several turns, then tighten it fully with two
wrenches by applying the tightening torque indicated in the table.

Adijustable wrench or
torque wrench

Connecting pipes

Unit connections

Tube insulation

Fastening tape

L

L

Содержание 42VMC Console night & day

Страница 1: ...42VMC Console T h e S t andards Institutiono f I s r a e l Q u ality Assured Fi r m SI ISO 9001 INSTALLATION MANUAL...

Страница 2: ...ge Dimensions and weight 2 Nominal data 2 Minimum clearances 2 Connections 3 Material supplied 3 Operating limits 3 General information 4 Warnings avoid 5 Installation 6 7 Refrigerant connections 8 El...

Страница 3: ...m 540 540 600 600 600 kg kg 15 16 18 18 20 Table I Nominal data Unit is not suitable for operation in laundry premises For sizing of power supply wires and delay type fuses refer to the outdoor unit i...

Страница 4: ...g limits Cooling Heating Refer to outdoor unit installation manual Mains power supply Nominal single phase voltage 230V 50Hz Operating voltage limits min 198V max 264V Photocatalytic filter Acrylic fi...

Страница 5: ...its which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resulting from unapproved couplin...

Страница 6: ...lose to heating sources which may damage the unit connecting condensate piping to sewage system drain without appropriate trap Trap height must be calculated according to the unit discharge head in or...

Страница 7: ...grille To remove suction grille remove the central lock using a pliers then with a screwdriver remove the two side screws fixing the fasteners Locate the mounting template supplied with the unit Insta...

Страница 8: ...ections see illustra tion For exit to the rear the wall hole must be made in the position shown in the illustration Drill a 70 or 80 mm diameter hole The hole must have a 5 10 mm downward slope toward...

Страница 9: ...s Liquid Model Suction Discharge mm inches mm inches 009 9 52 3 8 6 35 1 4 012 12 70 1 2 6 35 1 4 014 12 70 1 2 6 35 1 4 018 12 70 1 2 6 35 1 4 024 12 70 1 2 6 35 1 4 For refrigerant tubes use seamles...

Страница 10: ...gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type or higher with synthetic rubber insulation with Neoprene coating according to EN 60335 2 40 and HD277 S1 codes The m...

Страница 11: ...ng contact Mains supply connecting cable field wiring Connecting cable indoor outdoor units field wiring Indoor unit Outdoor unit Main switch Time delay fuse or circuit breaker see outdoor unit instal...

Страница 12: ...ction indoor outdoor unit R Live connection indoor outdoor unit C Neutral connection indoor outdoor unit Y Compressor interlocking contact O Reversing valve control W2 Outdoor fan signal S Defrost end...

Страница 13: ...ng temperature range F min and max CL 12 12 12 hour clock AM PM Time format AM morning PM afternoon 24 24 24 hour clock Default is 12 12 Table IV Item Shown on Explanation Description display A remote...

Страница 14: ...ol and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item CH remote address and the time segments will display the...

Страница 15: ...pplied separately and controlled by a bipolar ON OFF switch with safety fuses field installed To adjust the fan motor air flow to the required values it is advisable to install a speed controller Fres...

Страница 16: ...nzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 14489 74 April 2002 Supersedes Order No 14489 74 Januar...

Отзывы: