FILE NO. SVM-13035
<For remote controller>
1. Remove cover of remote controller by sliding down
and take it out.
2. If batteries are exist, please take them out. The
combination of using wire controller and batteries may
cause of batteries explosion.
3.
Make hole for insert control wire by use screwdriver
break the polyester sheet as shown on figure
7
.
4. Insert control wire from rear side of remote controller
as shown on figure
8
.
5. Fix control wire which arrange as shown on figure
9
and
10
to terminal by provided screws (tighten firmly
but not over : 0.25 N·m (0.03 kgf·m).
6. Set control wire through gutter way at rear side of
remote controller as shown on figure
11
.
7. Fix provided screw (
∅
3.1 x 16L) on the wall to hang
remote controller as shown on figure
12
.
8. Mark and arrange hole for fix below screw
(
∅
3.1 x 25L) as shown on figure
12
.
9. Assembly battery cover which provided with accessory
bag then use provide screw (
∅
3.1 x 25L) to fix battery
Fig. 10-3-10
Fig. 10-3-11
Polyester sheet close hole
for insert control wire
Control wire
30 mm
10 mm
* Wire size 28-22 AWG (0.08~0.32 mm
2
)
Outer diameter not over 4.7 mm,
control wire length 50 m. or less.
9
Control wire
Terminal
!
Tighten fi rmly but not over
0.25 N·m (0.03 kgf·m)
7
8
connect remote control and air conditioner.
1. Recommend to use double insulation lead wire for
2. For wire operation, 1 remote control can control only
*Remark :
1 indoor unit.
<How to install the air inlet grille on the indoor unit>
•
When attaching the air inlet grille, perform the same
process as for removal but in severse order.
10-3-6. Piping and drain hose installation
<Piping and drain hose forming>
* Since dewing results in a machine trouble, make
sure to insulate both connecting pipes. (Use
polyethylene foam as insulating material.)
Fig. 10-3-12
Control wire
Control wire
Hole for hang
remote controller
Remote controller
Screw (
∅
3.1 x 16L) for
hang remote controller
Wall
Screw (
∅
3.1 x 25L) for
fi x battery cover
Remote controller
"
#
Battery cover
Screw
$
Tighten fi rmly but
not over 0.15 N·m
(0.02 kgf·m)
condition (PRESET, TIMER and CLOCK will return to
3. In wire operation, remote controller will return to initial
initial condition) when user shutdown power supply
of air conditioner.
* Wire size 28-22 AWG (0.08~0.32 mm
2
)
Outer diameter not over 4.7 mm,
control wire length 50 m. or less.
70 mm
5 mm
4
5
6
Control wire out position
Control wire through out position
Control wire
Terminal
Control wire
Tighten fi rmly
but not over
0.12 N·m (0.01 kgf·m)
cover together with wall as shown on figure
13
(tighten firmly but not over 0.15 N.m (0.02 kgf.m)).
10. Reassembly cover of remote controller.
–
53
–