TEST RUNNING
(Cont.)
19.4 STEPS FOR HEATING TEST RUNNING
a. Move circuit breaker to ON position.
b. After system operation becomes stabilized:
-
Measure high and low pressures to check
correct refrigerant charge. (See figure)
-
Measure total Amps consumed by the system.
-
Measure system-working voltage.
System Heating Test Running
SYSTEM MODEL
53QG18-H
53QG24-H
AMBIENT TEMP ºC
7
7
HIGH PRESSURE PSI
240
260
LOW PRESSURE PSI
52
50
TOTAL AMPS
8.5
11.8
Notes:
1- Readings at 220 volt and 20 ºC return air to indoor unit
and high speed of indoor unit motor.
2- System with Standard mild ambient outdoor unit with rotary compressor.
SYSTEM MODEL
53QG18-H
53QG24-H
AMBIENT TEMP ºC
7
7
HIGH PRESSURE PSI
230
250
LOW PRESSURE PSI
60
60
TOTAL AMPS
7.5
11.3
Notes:
1- Readings at 220 volt and 20 ºC return air to indoor unit
and high speed of indoor unit motor.
2- System with High ambient outdoor unit with rotary compressor.
1. Low Pressure Measuring.
2.
High Pressure Measuring.
(1)
(2)
Outdoor Unit
Details