7
NOTES:
1. Unit weights (shown in pounds), ± 10 percent, are based on the
largest water-filled coil.
2. The operating weight information is based on 8-row water-filled
coils and double wall cabinet construction. For a different coil and
cabinet options, use the weight adjustment table (Table 1).
Fig. 7 — 42DV Vertical Unit —
Weight Distribution Calculations
Step 2 — Install Mixing Box
1. Mixing boxes are pre-assembled from the factory for ease of
installation. A linkage kit consisting of two crank arms,
2 swivels, and either a 25 in. (sizes 06-16) or a 34 in. (sizes
20-30) length of 5/16 in. rod is provided for field-installation
of an actuator. Mixing boxes are only compatible with side/
bottom (horizontal units) and side/top (vertical units)
access-style filter frames (non-magnetic latching doors). See
Fig. 14 for dimensional information.
2. Assemble the base rails (provided with mixing box. (See
Fig. 8.) All hardware required for assembly is included and
the base rails are letter coded for ease of assembly. (See
Fig. 9.)
Fig. 8 —
Base Rails
Fig. 9 —
Letter Coding on Base Rail Parts
PLACE UNIT ON THE BASE RAILS
42DH- Horizontal Units
Unit is mounted flush to the outer edge of the end base rail at the
aligning unit mounting holes. (See Fig. 10.) It may be necessary to
remove factory installed sheet metal screws to enable access to all
mounting holes and to ensure proper fit. Do not remove screws
unless necessary. Secure unit to base rail using No. 8 x 1/2 in. fas
-
teners at the locations shown in Fig. 9 and 10. Use two fasteners
per side.
42DV UNIT
NO ELECTRIC HEAT (lb)
A
B
C
D
Total
06
76
38
35
42
191
08
85
39
37
38
199
10
78
45
44
78
245
12
84
45
46
80
255
16
85
74
62
82
306
20
90
84
77
88
339
22
110
90
73
90
363
30
147
140
113
128
528
42DV UNIT
WITH ELECTRIC HEAT (lb)
A
B
C
D
Total
06
85
40
44
49
218
08
94
48
44
47
234
10
86
58
55
84
283
12
97
62
58
92
309
16
105
79
70
92
346
20
111
88
81
99
379
22
133
88
92
99
412
30
160
140
131
137
568
C
D
A
B
B
D
C
A
RH Coil
LH Coil