18
Fig. 25 —
42DV Unit with Mixing Box Submittal Drawing
NOTES:
1. Right hand unit shown; left hand unit opposite.
2. All dimensions are ± 1/4 in.
3. Product specifications are subject to changes without notice.
4. Dimensions are in inches (mm).
5. Allow adequate spacing or maneuverability around unit to allow service through recommended access area.
6. C dimension is measured from coil side of unit.
7. Mixing box option will vary return duct dimensions, refer to mixing box drawing.
8. Mixing box option includes: a) knockdown base rails which are letter-coded for field assembly, all assembly hardware included; b) pre-assem-
bled mixing box.
9. Linkage kit supplied with Mixing Box is provided for field installation of actuator. Kit consists of 2 crank arms, 2 swivels, and either a 25 in.
(sizes 06-16) or 34 in.(sizes 20-30) length of 5/16 in. rod.
10. Add 2 in. if using a prefilter or 4 in. filter.
UNIT
SIZE
FAN
SIZE
DEPTH
UNIT
DEPTH WIDTH HEIGHT
SUPPLY DUCT FLANGES
RETURN
DUCT
FLANGES
MIX
BOX
AUX.
CTRL.
BOX
UNIT SIDE TO
DUCT FLANGE
UNIT BOTTOM TO
DUCT FLANGE
A
B
C
E
F
H
L
M
N
06
9 x 6
35-1/2
20
28
36-1/2
8-7/8
10-7/8
15-1/8
24
6
11
4-1/2
1-7/8
2-7/8
08
9 x 6
35-1/2
20
28
36-1/2
8-7/8
10-7/8
15-1/8
24
6
11
4-1/2
1
2-7/8
10
9 x 6
39-1/2
22
37
39-3/8
10-1/4
10-7/8
21-1/2
33
8
13
0
1-7/8
2-7/8
12
9 x 6
39-1/2
22
37
39-3/8
10-1/4
10-7/8
21-1/2
33
8
13
0
1-7/8
2-7/8
16
10 x 7
39-1/2
22
47
39-3/8
13
12
16-5/8
43
8
13
3
1-5/8
2-7/8
20/22
11 x 10
41-1/2
24
48
45-1/8
16-1/4
13
17-1/8
44
8
13
2-1/2
1-7/8
3-1/8
30
12 x 12
47-1/2
28
48
54-1/4
16-1/4
14
16
44
10
15
3-5/8
1-7/8
2-7/8